17
Problem
Cause
Correction
Engine is running, but no AC output is
available.
1. Circuit breaker open or defective.
2. Fault in generator.
3. Poor wiring connections or
defective transfer switch.
1. Reset or replace circuit breaker.
2. Contact local service facility.
3. Check and repair.
Engine runs good at no-load but “bogs
down” when loads are connected.
1. Short circuit in a connected load.
2. Generator is overloaded.
3. Shorted generator circuit.
4. Fuel Pressure is incorrect.
5. Natural gas fuel mixture is incorrect.
1. Disconnect shorted electrical load.
2. See
Essential Circuits
.
3. Contact local service facility.
4. See
Gaseous Fuel System
in the
Installation Manual.
5. See
Gaseous Fuel System
in the
Installation Manual.
Engine will not start; or starts and runs
rough.
1. 15 Amp fuse missing or blown.
2. Fuel supply turned off or depleted.
3. Failed battery.
1. Install (new) 15 Amp fuse. See
System Control Panel
.
2. Open fuel valve(s); check propane
tank.
3. Replace battery.
Engine shuts down during operation.
1. Fuel supply turned off or depleted.
2. Fault indicator blinking.
1. Check fuel valves, fill propane tank.
2. Count blinks and refer to
Fault
Detection System
.
Loss of power on essential circuits.
1. Generator circuit breaker is open.
2. Transfer switch problems.
1. Reset circuit breaker.
2. See the transfer switch manual.
Troubleshooting