THERMOSTATIC EXPANSION VALVES
SYMPTOMS
POSSIBLE CAUSE
CHECK OR REMEDIES
Superheat is low to normal
Unequal evaporator circuit loading
Ensure air flow is equally distributed
with low suction pressure
through evaporator
Check for blocked distributor
tubes
Low load or airflow entering
Ensure blower is moving proper air
evaporator coil
CFM
Remove/Correct any air flow
restriction
Superheat and suction
Expansion valve is oversized
Install correct TEV
pressure fluctuate (valve is hunting)
Sensing bulb is affected by liquid
Relocate sensing bulb in another
refrigerant or refrigerant oil flowing
position around the circumference of
through suction line
the suction line
Unequal refrigerant flow through
Ensure sensing bulb is located
evaporator circuits
properly
Check for blocked distributor
tubes
Improper superheat adjustment
Replace TEV or adjust superheat
(only possible with TEV having
superheat adjustment)
Moisture freezing and partially
Recover refrigerant, change filter-
blocking TEV
drier, evacuate system and
recharge
Valve does not regulate at all
External equalizer line not connected
Connect equalizer line in proper
or line plugged
location, or remove any blockage
Sensing bulb lost its operating charge
Replace TEV
Valve body damaged during soldering
Replace TEV
or by improper installation