RGM 465, Mfg No. 175758, Page 35
Troubleshooting Chart Guide
Symptoms
Chart
With thermostat calling for heat, burner motor never attempts to
run (Green “power on” light is lit; Green “system ready” light is not lit). ........
Chart No. 1, page 37
Chart 1 check completed, but burner motor never attempts to run. With
thermostat calling for heat, burner motor runs momentarily. ............................
Chart No. 2, page 39
System does not attempt to ignite. .....................................................................
Chart No. 3, page 40
Burner ignites and burns steadily until system goes into lockout. .....................
Chart No. 4, page 41
Burner operation erratic/unstable flame pattern. ...............................................
Chart No. 5, page 42
Oil delivery system troubleshooting. .................................................................
Chart No. 6, page 43
Oil Burner
Troubleshooting
To diagnose malfunctions properly, the following test equipment is required:
1) An electrical test meter that can measure AC volts, ohms, and amps;
2) A combustion analyzer kit to measure oxygen and/or carbon dioxide,
smoke, stack temperature, and draft; and
3) Two pressure gauges with scales of 0-100 PSIG and 0-30 PSIG.
Before test firing, check the combustion chamber for an excessive accumu-
lation of unburned oil and restore to safe condition before firing. (See page
25.)
WARNING: Do not attempt to start the burner when
excess oil has accumulated, when the combustion
chamber is full of vapor, or when the combustion
chamber is very hot.
NOTE: Refer to the troubleshooting guide below to select the appropriate
troubleshooting chart.
Check the Indicator Lights
Light
Location (on the
Function
Electrical Box)
GREEN
On the side next to
Indicates that the main power is
disconnect (on/off) switch
on to the heater
GREEN
On the fixed-cover portion
Indicates that all limits have been
above the ignition controller satisfied and the unit is ready to
operate
Troubleshooting