RGM 465, Mfg No. 175758, Page 23
Every Six months:
•
Clean the oil strainer at the burner.
•
Clean the foot valve screen.
•
Replace the air filter.
•
Clean the end cone.
•
Replace the oil nozzle.
•
Check for oil leaks.
•
Inspect the electrodes
•
Inspect the combustion chamber liner.
•
Clean the pre-heater.
•
Clean the external surfaces.
NOTE:
A maintenance record chart is provided in the Appendix.
Replacing the Supply Line Filter
and Cleaning Internal Pump Screen
Replacing the filter and cleaning the pump screen requires breaking the
suction line. The suction line is the portion of the supply line from the tank
to the remote pump. If air leaks develop in the suction line, the burner will
not operate properly.
Follow all instructions, including “recharging the Suction Line,” (page 24)
to avoid creating an air leak.
Replacing the Supply Line Filter
Unscrew the replaceable “canister” portion from the bottom of the supply
line filter and replace (Replacement filter canister is P/N 176535.)
Be sure replacement filter canister is tight so there are no air leaks created.
Maintenance
Procedures
Supply
Line
Filter
Cleaning the Internal Pump Screen
1. Check the Screen
•
Disconnect the inlet oil line from the pump.
•
Using a flashlight, look into the pump inlet.
a) If the portion of screen visible at the inlet appears to be
clogged, go to Step 2.