0108X1DHGBEN
3
SECTION 2. TECHNICAL DATA
Table 1.
APPLIANCE DATA
Type EURO-X ...
1025D
1030D
1035D
1045D
1055D
1075D
1095D
Gas category 'Cat.'
II
2H3+
Air supply and flue type
B11 or B14
1
Heat input (Hs) 'Qn'
kW
30,28
34.94
43,26
52,00
64,67
88,96
118,7
Heat input (Hi) 'Qn'
kW
27,30
31,50
39,00
46,90
58,30
80,20
107,0
High heat output
kW
23,8
27,5
34,2
40,8
50,8
69,9
93,2
Number of jets
4
5
7
9
12
16
natural gas
∅
mm
2,4
2,2
2,4
2,6
Jet size
propane/butane
∅
mm
1,35
1,30
1,25
1,35
1,40
natural gas
mbar
(GB)
=17,5
(IE)
= 20,0
propane
mbar
37,0
Gas supply
pressure 'P'
2
butane
mbar
28,0
Burner pressure
natural gas
mbar
8,4
6,0
natural gas
3
m
3
/h
2,89
3,33
4,13
4,96
6,17
8,49
11,33
butane G30
kg/h
2,21
2,55
3,15
3,80
4,72
6,49
8,66
Gas consumption
propane G31
kg/h
2,16
2,49
3,09
3,71
4,62
6,35
8.48
Gas service connection (not supply line size)
Rc ¾
Electrical service (protection class IP 20)
230/240V 1 N ~ 50 Hz
Total electrical rating
4
kW
Weight net
kg
Weight shipping
± kg
1 Category B14 only applies when used with a Reznor "EUROVENTER" flue gas fan
2 Maximum gas pressure at inlet to appliance = 50,0 mbar
3 Natural gas G 20, calorific heating value 10,48 kWh/m
3
on Hs @ 15
°
C & 1013 mbar
Propane G 31, calorific heating value 14,0 kWh/kg. Butane G 30, calorific heating value 13,7 kWh/kg
4 Total electrical rating for appliances with hot surface ignition is exceeded by 130 W for ± 30s at start up
Table 2 Minimum air volumes for maximum temperature rise.
Standard model Euro-X...
1025D
1030D
1035D
1045D
1055D
1075D
1095D
Minimum air volume
m
3
/h
1800
2200
2660
3110
3940
5400
7190
Maximum temperature rise
∆
T
K
39
37
39
39
38
38
38
NOTE:
The maximum static pressure that may be applied to the EURO-X...D series is 800 Pa