Euro-C 4000 RJL-GBEN
4/26
Table 2A :
Injector size and burner pressure
G20 natural gas
inlet pressure = 17.5 mbar for UK
20.0 mbar for IE
Injector size
Model
Quantity
mm
marking
Burner pressure
(mbar) (1)
4011
3
1.85
185
9.00
4015
4
1.85
185
8.90
4018
5
1.85
185
9.00
4024
5
2.20
220
7.70
4030
6
2.20
220
9.20
4036
8
2.20
220
7.00
4047
10
2.20
220
8.10
4060
8
2.70
270
8.50
4072
10
2.70
270
8.30
4100
12
3.00
300
7.85
Table 2B : Injector size and burner pressure
G30/G31 butane/propane
inlet pressure G30 = 28mbar
inlet pressure G31 = 37mbar
Injector size
Burner pressure
(mbar) (1)
Model
Quantity
mm
marking
Butane
Propane
4011
3
100
100
27.9
36.9
4015
4
1.00
100
27.8
36.8
4018
5
1.00
100
27.8
36.9
4024
5
1.15
120
28.7
36.5
4030
6
1.20
120
27.5
36.5
4036
8
1.15
120
27.3
36.0
4047
10
1.15
120
26.7
34.8
4060
8
1.50
150
26.7
35.2
4072
10
1.45
145
25.1
34.7
4100
12
1.55
155
25.0
34.0
(1) with open service door