Euro-C 4000 RJL-GBEN
22/26
8.3 Limit Control Fault Finding Chart (limit control trips)
WARNING
: Fault finding may only be carried out by appropriately qualified persons
Note
: EURO-C 4000 RJL air heaters are equipped with 2 limits (a recycling limit and a manual reset limit).
During normal operation, neither limit should trip even if the main electric supply is interrupted during
operation. In the event of motor failure, the recycling limit will trip opening the gas valve.
yes
no
yes
no
yes
yes
no
yes
no
no
yes
yes
no
Has any non-factory authorized air distribution
device been placed on the heater? Is there excessive
static pressure in the ductwork? Did the motor overload
trip?
Does the fan control
energize the fan motor
in less than 75"?
Adjust thermostat
temp. setting above
ambient to energize fan
& gas solenoid valve
Replace
the motor
Consult fan
fault finding
Check for excessive
main burner pressur
Are filters
clean?
clean filters
Does the fan
motor operate?
Remove the
restrcition
Does the limit trip
before the fan is
energized?
Place system in normal
operation
Consult fan
fault finding
Is there 220-240V at
terminals N and 3?