Euro-C 4000 RJL-GBEN
10/26
3.7 Gas Connection
EURO-C 4000 RJL air heaters are designed to
operate on either natural gas (G20) or propane
(G31) / butane (G30) gas. Refer to the
specifications in section 2 of this document and to
the data plate for details of supply pressures.
The gas meter and gas service must be checked by
the supply undertaking to ensure that they are
adequate to deal with the total load of all gas fired
apparatus installed.
Connection to a gas service may only be carried out
by appropriately qualified persons. The gas
installation must comply with the rules in force
using materials appropriate for gas installations.
Check that the gas category is in accordance with
the data described on the air heater.
An adequate gas supply sized to provide the
dynamic pressure for the volume required for the air
heater(s) is essential to maintain the nominal heat
input. Account of other gas fired plant using the
same gas service must also be taken into account.
A 90° action, positive stopped gas service tap
must be fitted adjacent to the appliance, fitted in a
manner to facilitate appliance burner removal for
service purposes, see figure 6.
Ensure that the gas service includes a filter and has
been tested and purged in accordance with
prescribed practice prior to commissioning and
taking the appliance into service.
As a rule, gas service pipes should not be routed
through air ducts. Should it be necessary to do so
then pipe work joints must not be made within the
air duct.
Figure 6 : Detail of gas connection ¾”
4.0 INSTALLATION
4.1 Unpacking and preparation
Prior to dispatch, the air heater was operated and
tested at the factory.
Check the shipping label and data plate to ensure
the specification of gas and electrical supplies are
compatible. Read this document and become
familiar with the installation requirements and the
appliance before commencing installation.
4.2 Electrical connections
The electrical installation may only be carried out by
appropriately qualified persons observing the rules
in force.
All electrical connections should be made in the
heater control compartment.
Screw type terminals are provided. Connections
should be in accordance with the terminal markings
and the wiring diagram affixed to the air heater or
included with this document.
DANGER: THIS APPLIANCE MUST BE EARTHED
The minimum external controls required for the air
heater are a room thermostat.
It is essential the
main input line and neutral to terminals L and N
remains live at all times even when the appliance is
switch off this is to ensure correct operation of the
unit.
An indicator light and burner-reset button are fitted
inside the appliance. To add a remote reset button,
make connections to the terminals in the electric
box as indicated on the wiring diagram.
IMPORTANT: If the reset button requires activating
for any reason the cause should be identified before
resetting. After resetting stay with the appliance for
long enough to ensure that lockout does not
reoccur
(suggest 5 minutes).