3.10 EFC 3600 UL Ratings and Dimensions 1P 0K40...2K20
Description
Symbol
Unit
0K40
0K75
1K50
2K20
Net weight
m
kg
0.96
1.24
1.61
2.35
Device height (UL)
6)
H
mm
135
145
185
210
Device depth (UL)
7)
T
mm
105
120
125
130
Device width (UL)
8)
B
mm
90
95
95
120
Rated input current (UL)
I
LN
A
5.8
9.6
15.0
19.7
Branch circuit protection fuse (UL)
9)
I
LN
A
10
15
25
30
Required wire size according to
EN 60204-1
10)
A
LN
mm
2
2.5
2.5
4.0
6.0
Required wire size according to UL
508 (internal wiring); (UL)
11)
A
LN
AWG
14
14
10
10
Output current (UL) 200 V
I
out
A
2.3
3.9
7.0
9.7
Output current (UL) 240 V
1.9
3.3
5.8
8.1
Tab. 3-10: EFC 3600 UL ratings and dimensions 1P 0K40...2K20
3.11 EFC 3600 UL Ratings and Dimensions 3P 0K40...4K00
Description
Symbol
Unit
0K40
0K75
1K50
2K20
4K00
Net weight
m
kg
1.18
1.26
1.52
2.25
2.36
Device height (UL)
6)
H
mm
145
145
185
210
210
Device depth (UL)
7)
T
mm
120
120
125
130
130
Device width (UL)
8)
B
mm
95
95
95
120
120
Rated input current (UL)
I
LN
A
1.3
2.3
3.9
5.6
9.8
Branch circuit protection fuse
(UL)
9)
I
LN
A
6
10
10
15
20
Required wire size according to
EN 60204-1
10)
A
LN
mm
2
2.5
2.5
2.5
2.5
2.5
Required wire size according to
UL 508 (internal wiring); (UL)
11)
A
LN
AWG
14
14
14
14
12
Output current (UL) 380 V
I
out
A
1.2
2.1
3.7
5.1
8.8
Output current (UL) 480 V
1.0
1.6
2.9
4.0
7.0
Tab. 3-11: EFC 3600 UL ratings and dimensions 3P 0K40...4K00
Bosch Rexroth AG
Ratings and Dimensions
24/69
DOK-RCON01-REX*F*UL***-IN10-EN-P
Summary of Contents for EFC3600 Series
Page 17: ...Rexroth 60 15 Bosch Rexroth AG DOK RCON01 REX F UL IN10 EN P XV...
Page 18: ...Bosch Rexroth AG XVI DOK RCON01 REX F UL IN10 EN P...
Page 31: ...Fig 2 2 Type code Fv Bosch Rexroth AG Identification DOK RCON01 REX F UL IN10 EN P 11 69...
Page 32: ...Fig 2 3 Type code EFC 3600 Bosch Rexroth AG Identification 12 69 DOK RCON01 REX F UL IN10 EN P...
Page 33: ...Fig 2 4 Type code EFC x610 Bosch Rexroth AG Identification DOK RCON01 REX F UL IN10 EN P 13 69...
Page 89: ...Notes Bosch Rexroth AG...