Cooling unit on top of the control cabinet
Cooling unit at the front of the control cabinet
Tab. 5-1: Arranging the cooling units
1: Cooling unit
2: Interior of control cabinet
3: Air duct (protects devices against condensation water)
4: Device in control cabinet
Avoiding moisture condensation
Moisture condensation occurs when the temperature of the device is lower than
the ambient temperature.
●
Set cooling units with temperature adjustment to the maximum surrounding
temperature and not lower!
●
Set cooling units with follow-up temperature in such a way that the interior
temperature of the control cabinet is not lower than the temperature of the
surrounding air. Set the temperature limitation to the maximum surrounding
temperature!
●
Only use well-sealed control cabinets so that moisture condensation cannot
arise as a result of warm and moist external air entering the cabinet.
●
In the event that control cabinets are operated with the doors open (commis-
sioning, servicing etc.), it is essential to ensure that after the doors are closed
the drive controllers cannot at any time be cooler than the air in the control
cabinet. For this reason, sufficient circulation must be provided inside the
control cabinet.
Bosch Rexroth AG
Instructions for Use
40/69
DOK-RCON01-REX*F*UL***-IN10-EN-P
Summary of Contents for EFC3600 Series
Page 17: ...Rexroth 60 15 Bosch Rexroth AG DOK RCON01 REX F UL IN10 EN P XV...
Page 18: ...Bosch Rexroth AG XVI DOK RCON01 REX F UL IN10 EN P...
Page 31: ...Fig 2 2 Type code Fv Bosch Rexroth AG Identification DOK RCON01 REX F UL IN10 EN P 11 69...
Page 32: ...Fig 2 3 Type code EFC 3600 Bosch Rexroth AG Identification 12 69 DOK RCON01 REX F UL IN10 EN P...
Page 33: ...Fig 2 4 Type code EFC x610 Bosch Rexroth AG Identification DOK RCON01 REX F UL IN10 EN P 13 69...
Page 89: ...Notes Bosch Rexroth AG...