Make sure that terminals (+), (-) of frequency converter are con-
nected to the corresponding terminals P, N of brake chopper re-
spectively. Incorrect connection may damage the brake chopper.
●
Please connect to frequency converter directly or install a termi-
nal block.
●
The master / slave control mode of the brake chopper supports
the following two connections, which currently supports up to
three brake choppers in parallel.
– Two devices: slave
– Three devices: slave + slave
Brake Chopper
Bosch Rexroth AG
Brake Chopper Wiring
DOK-RCON03-EFC*BRAKE**-IT01-EN-P
25/65