6.2 Cable Specifications
6.2.1 Power Cables
Brake chopper
model
Fuse (gG)
Power cables installation
mode
PE cable
Torque / Screw
B1
B2
E
[mm
2
] [mm
2
] [mm
2
] [mm
2
]
[N·m / lb·in] (Mx)
FEAE07.1-EA1-NNNN
100
10.0
10.0
10.0
10.0
1.76 / 15.6 (M4)
FEAE07.1-EA2-NNNN
160
10.0
10.0
10.0
10.0
1.76 / 15.6 (M4)
Tab. 6-1: Fuse and cable dimensions for international without USA / Canada
Brake chopper
model
Fuse (Class J)
Power cables
PE cable
Torque / Screw
[AWG]
[AWG]
[N·m / lb·in] (Mx)
FEAE07.1-EA1-NNNN
100
8
8
1.76 / 15.6 (M4)
FEAE07.1-EA2-NNNN
175
6
6
1.76 / 15.6 (M4)
Tab. 6-2: Fuse and cable dimensions for USA / Canada
●
The recommended values of the fuse listed in the tables above are
based on the Max. output current, please select the proper fuse
according to the actual application.
●
For cable specification for international without USA / Canada,
ONLY USE copper wires of 90 ℃ or above with XLPE or EPR insu-
lation according to IEC60364-5-52.
●
For cable specification for USA / Canada, ONLY USE copper wires
of 75 ℃ or above according to UL 61800-5-1.
Dimensioning variables of the table values
1. Installation types:
●
B1 according to IEC 60364-5-52, e.g. stranded wires routed in cable
duct
●
B2 according to IEC 60364-5-52, e.g. multi-core line routed in cable duct
●
E according to EN 60204-1, e.g. multi-core line routed on open cable tray
●
According to NFPA 79 (external wiring), UL 508A (internal wiring), NEC,
NFPA 70:
– 1 cable with 3 conductors, 1 neutral conductor and 1 equipment
grounding conductor
– Routed in pipe on the wall
Internal wiring: Routing inside of control cabinet or of devices.