System 25: 2-store solar system with pump logic
The controller compares the temperature at sensor S1 to the temperatures at
sensors S2 and S4. If the measured temperature differences are higher than the
adjusted switch-on temperature differences, the pump (R1 and / or R2) will be
activated and the corresponding store will be loaded up to the adjusted store
maximum or set temperature respectively at most. The priority logic effects prior
loading of store 1.
Afterheating (R3 and R4) can be carried out with a thermostat function (S3). If the
value at S3 reaches the switch-on temperature for the afterheating, the relay is
switched on. If the value exceeds the switch-off temperature for the afterheating,
the relay is switched off again.
R1
R2
S4
S1
S2
S3
R3
R4
2
3
3
2
2
3
2
3
VBus
VBus
S5/V
40
S4
S3
GND
S6
S7
Sensors
Relais
S2
S1
N
R3
R2
R1
L
R4
PW
M
A
0-10
V
PW
M
B
0-10
V
R4
N
N
N
N
R3
R2
R1
L
1
2
3
4
5
6
7
8
9
10
11
2
Netz
Mains
Hydraulic variant 1
Hydraulic variant 3
Hydraulic variant 2
Sensors
S1
Temperature collector
1 / GND
S2
Temperature store
base
2 / GND
S3
Temperature
afterheating
3 / GND
S4
Temperature store
2 base
4 / GND
S5
Free
5 / GND
S6
Free
S6
Relay
R1
Solar pump store 1
R1 / N / PE
R2
Solar pump store 2
R2 / N / PE
R3
Pump
R3 / N / PE
R4
Afterheating
R4 /R4