en
27
27
en
System 19: Solar system with east-/west collectors and return preheating
The controller compares the temperatures at the collector sensors S1 and S5 to
the store temperature at sensor S2. If one of the measured temperature difference
is higher than the adusted switch-on temperature difference, the corresponding
pump (R1 and / or R2) will be switched on, thus loading the store until either the
switch-off temperature difference or the store maximum temperature is reached.
With another temperature differential function (S3 heat source/S4 heat sink) re-
turn preheating (heating circuit backup) is possible via another valve (R3).
Hydraulic variant 1
Hydraulic variant 2
Sensors
S1
Temperature collector
1 / GND
S2
Temperature store
base
2 / GND
S3
Temperature store
return preheating
3 / GND
S4
Temperature
heating return
4 / GND
S5
Temperature collec-
tor 2
5 / GND
S6
Free
S6
Relay
R1
Solar pump collector
R1 / N / PE
R2
Solar pump collector 2
R2 / N / PE
R3
Valve solar circuit
R3 / N / PE
R4
Free
R4 /R4
R2
R1
S5
S3
S2
S1
VBus
VBus
S5/V
40
S4
S3
GND
S6
S7
Sensors
Relais
S2
S1
N
R3
R2
R1
L
R4
PW
M
A
0-10
V
PW
M
B
0-10
V
R4
N
N
N
N
R3
R2
R1
L
1
2
3
4
5
6
7
8
9
10
11
2
2
3
3
2
2
2
3
3
R3
S4
Netz
Mains
Flow direction
when normally open
Summary of Contents for DeltaSol SL