resideo VR8215 Installation Instruction Download Page 6

VR8215S,M,T SINGLE STAGE DIRECT IGNITION GAS CONTROLS

69-2253EF—01

6

Check Safety Lockout 
Slow-Opening (T) Controls Only

1.

With the system power off and the thermostat set 

to call for heat, manually shut off the gas supply.

2.

Energize ignition control and start timing safety 

lockout time. When spark ignition terminates, stop 

timing.

NOTE:

When using the VR8215T, the specified 

ignition control safety lockout time must 

exceed 8.5 seconds for the system to 

function properly.

3.

After spark cutoff, manually reopen the gas control 

switch. No gas should flow to the main burner.

4.

Reset the system by adjusting the thermostat 

below room temperature, wait 30 seconds, and 

then move the thermostat setting up to call for 

heat. Normal ignition should occur.

Table 6.  Pressure Regulator Specification Pressures in inches WC (kPa).

1

Some models 3.0 - 5.0 (0.8 - 1.3).

Check Safety Shutdown 
Performance

WARNING

Fire or Explosion Hazard.

Can cause property damage, severe injury 

or death.

Perform the safety shutdown test any time work 

is done on a gas system.

NOTE:

Read steps 1 through 7 before starting, and 

compare to the safety shutdown or safety 

lockout tests recommended for the direct 

ignition (DI) module. Where different, use the 

procedure recommended for the ignition 

module.

1.

Turn off gas supply.

2.

Set thermostat or controller above room 

temperature to call for heat.

3.

Watch for ignition spark or for glow at hot surface 

igniter either immediately or following prepurge. 

See Direct Ignition module specifications.

4.

Time the length of spark operation. See the Direct 

Ignition module specifications.

5.

After the module locks out, open the manual gas 

cock and make sure no gas is flowing to the main 

burner.

6.

Set the thermostat below room temperature and 

wait one minute.

7.

Operate system through one complete cycle to 

make sure all controls operate properly.

MAINTENANCE

WARNING

Fire or Explosion Hazard.

Can cause property damage, severe injury, 

or death.

Do not disassembly the gas control; it contains 

no replaceable components. Attempted 

disassembly, repair, or cleaning can damage 

the control, resulting in gas leakage.

Regular preventive maintenance is important in 

applications in the commercial cooking and agricultural 

and industrial industries that place a heavy load on 

system controls because:

• In many such applications, particularly commercial 

cooking, the equipment operates 100,000 to 200,000 

cycles per year. Such heavy cycling can wear out the 

gas control in one to two years.

• Exposure to water, dirt, chemicals and heat can 

damage the gas control and shut down the control 

system.

The maintenance program should include regular 

checkout of the control as outlined in the Startup and 

Checkout section, and the control system as described in 

the appliance manufacturer literature.

Maintenance frequency must be determined individually 

for each application. Some considerations are:

• Cycling frequency. Appliances that may cycle 20,000 

times annually should be checked monthly.

• Intermittent use. Appliances that are used seasonally 

should be checked before shutdown and again before 

the next use.

• Consequence of unexpected shutdown. Where the 

cost of an unexpected shutdown would be high, the 

system should be checked more often.

• Dusty, wet, or corrosive environments. Since these 

environments can cause the gas control to deteriorate 

more rapidly, the system should be checked more 

often.

The system should be replaced if:

• It does not perform properly on checkout or 

troubleshooting.

• The gas control is likely to have operated for more 

than 200,000 cycles.

• The control is wet or looks as if it has been wet.

Model Type

Type of Gas

Nominal Inlet Pressure 

Range

Factory Set Nominal Outlet 

Pressure

Setting Range

Single Stage

Standard, Slow

NAT

5.0-7.0

(1.2-1.7)

3.5

(0.9)

2.5-3.5

1

(0.6-0.9)

1

LP

12.0-14.0

(3.0-3.5)

10.0

(2.5)

8.0-12.0

(2.0-3.0)

Summary of Contents for VR8215

Page 1: ...6 4 mm Body Pattern Straight through see Table 1 for inlet and outlet size Electrical Ratings Voltage and Frequency 24 Vac 50 60 Hz Current Draw Single Stage 0 5 A Field Wiring Single Stage Two 1 4 in...

Page 2: ...Dust or Grease Accumulation Heavy accumulations of dust or grease can cause the control to malfunction Where dust or grease can be a problem provide covers for the control to limit contamination Heat...

Page 3: ...d pipe that is free from chips If tubing is used make sure the ends are square deburred and clean All tubing bends must be smooth and without deformation 2 Run pipe or tubing to the control If tubing...

Page 4: ...valve label Fig 4 Typical wiring connections for 24 volt control in S87 Direct Ignition System Fig 5 Typical wiring connections with 24 volt control in S89 Direct Ignition System M27669A 24V 24V GND S...

Page 5: ...to main burner is properly adjusted for complete combustion Follow appliance manufacturer instructions 2 IF CHECKING GAS INPUT BY CLOCKING GAS METER Make certain there is no gas flow through the meter...

Page 6: ...sure all controls operate properly MAINTENANCE WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Do not disassembly the gas control it contains no replaceable component...

Page 7: ...ctured gas Single Stage Single stage controls with standard and slow opening regulators model numbers with suffix S M T can be converted from one gas to the other with a conversion kit See Table 4 for...

Page 8: ...d the procedures outlined in your appliance manufacturer instructions can differ requiring special instructions To Turn ON Appliance STOP Read the Warnings Above Before Proceeding 1 The lighting seque...

Page 9: ...mm 1 4 po Configuration du corps passage direct reportez vous au Tableau 1 pour conna tre la taille d entr e et de sortie Caract ristiques lectriques Tension et fr quence 24 V c a 50 60 Hz Appel de co...

Page 10: ...tine vitez tout contact avec le r gulateur Lorsque des produits chimiques sont en suspension dans l air comme c est le cas dans le cadre de certaines applications industrielles ou agricoles prot gez l...

Page 11: ...ait tre expos des vapeurs de produits chimiques ou des gouttes d eau Installation de la tuyauterie sur le r gulateur Toute la tuyauterie doit tre conforme aux codes et r glements locaux ou au code nat...

Page 12: ...MM MINIMUM MONT E R GULATEUR DE GAZ ALIMENTATION EN GAZ TUBE HORIZONTAL MONT E MF3077C 2 1 2 2 1 2 TOUS LES COUDES DES TUBES M TALLIQUES DOIVENT TRE LISSES MISE EN GARDE COUPER L ARRIV E DE GAZ PRINC...

Page 13: ...le br leur principal est correctement r gl e pour assurer une combustion totale Suivez les instructions du fabricant de l appareil 2 POUR UNE V RIFICATION DE L ENTR E DE GAZ EN CHRONOM TRANT LE COMPT...

Page 14: ...ut causer des d g ts ou des blessures graves voire mortelles Ne d montez pas le r gulateur gaz car il ne contient pas de composants qui peuvent tre remplac s Toute tentative de d montage de r paration...

Page 15: ...n n cessaire de conversion Reportez vous au Tableau 4 pour plus d informations sur le num ro de pi ce du n cessaire de conversion correspondant 1 Coupez la vanne d alimentation en gaz de l appareil 2...

Page 16: ...c dures d finies par le fabricant de votre appareil peuvent diff rer et n cessiter des instructions sp ciales Pour mettre l appareil en marche ARR TEZ Lisez les avertissements ci dessus avant de conti...

Reviews: