VR8215S,M,T SINGLE STAGE DIRECT IGNITION GAS CONTROLS

69-2253EF—01

4

Fig. 3. Proper use of wrench on gas control.

Wiring

Follow the wiring instructions furnished by the appliance 

manufacturer, if available, or use the general instructions 

provided below. When these instructions differ from the 

appliance manufacturer, follow the appliance 

manufacturer instructions.

IMPORTANT

All wiring must comply with applicable electrical 

codes and ordinances. 

WARNING

Electrical Shock Hazard or Equipment Damage 

Hazard.

Can cause serious injury, death or equipment 

damage.

Disconnect power supply before making wiring 

connections to prevent electrical shock or 

equipment damage.

1.

Check the power supply rating on the gas control 

and make sure it matches the available supply. 

Install a transformer and other controls as 

required.

2.

Connect the control circuit to the gas control 

terminals. See Fig. 4 and 5.

3.

For single stage controls (VR8215S,M,T):

 

adjust thermostat heat anticipator to 0.50A rating 

stamped on valve label.

 

Fig. 4. Typical wiring connections for 24 volt 

control in S87 Direct Ignition System.

Fig. 5. Typical wiring connections with 24 volt 

control in S89 Direct Ignition System.

M27669A

24V

24V (GND)

S87B CONTROL MODULE

ALARM

VALVE

VALVE

GND

TEMPERATURE 

CONTROLLER

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 

PROTECTION AS REQUIRED.  

ALTERNATE LIMIT CONTROLLER LOCATION.

MAXIMUM IGNITER-SENSOR CABLE LENGTH:  3 ft. (0.9 m) OR LESS.

3A REPLACEABLE FUSE.

ALARM TERMINAL PROVIDED ON SOME MODELS.

M27697

L1

(HOT)

L2

1

2

1

2

3

DUAL VALVE

COMBINATION

GAS CONTROL

Q347 IGNITER-SENSOR

BURNER

4

4

5

IGNITER-SENSOR AND 

BURNER GROUND

3

5

ALARM, IF USED

WHITE
BLUE
BLACK
BLUE

HOT 

SURFACE

IGNITER-

SENSOR

VALVE

VALVE (GND)
24V

TH-W

24V (GND)

GND (BURNER)

S89C,G,J/S890C,G,J 

HOT SURFACE 

IGNITION CONTROL

L2

HSI

L1

HSI

LIMIT

CONTROLLER

BURNER 

GROUND

THERMOSTAT

OR CONTROLLER

DUAL VALVE 

COMBINATION

GAS CONTROL

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 

PROTECTION AS REQUIRED.  MAKE SURE L1 AND L2 ARE NOT 

REVERSED; THIS WOULD PREVENT FLAME DETECTION.

ALTERNATE LIMIT CONTROLLER LOCATION.

SEN TERMINAL AND Q354 FLAME SENSOR ON D MODELS ONLY.

M27628

L1

(HOT)

L2

VENT 

DAMPER PLUG

1

2

1

2

3

3

SEN

Q354 FLAME

SENSOR

Summary of Contents for VR8215

Page 1: ...6 4 mm Body Pattern Straight through see Table 1 for inlet and outlet size Electrical Ratings Voltage and Frequency 24 Vac 50 60 Hz Current Draw Single Stage 0 5 A Field Wiring Single Stage Two 1 4 in...

Page 2: ...Dust or Grease Accumulation Heavy accumulations of dust or grease can cause the control to malfunction Where dust or grease can be a problem provide covers for the control to limit contamination Heat...

Page 3: ...d pipe that is free from chips If tubing is used make sure the ends are square deburred and clean All tubing bends must be smooth and without deformation 2 Run pipe or tubing to the control If tubing...

Page 4: ...valve label Fig 4 Typical wiring connections for 24 volt control in S87 Direct Ignition System Fig 5 Typical wiring connections with 24 volt control in S89 Direct Ignition System M27669A 24V 24V GND S...

Page 5: ...to main burner is properly adjusted for complete combustion Follow appliance manufacturer instructions 2 IF CHECKING GAS INPUT BY CLOCKING GAS METER Make certain there is no gas flow through the meter...

Page 6: ...sure all controls operate properly MAINTENANCE WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Do not disassembly the gas control it contains no replaceable component...

Page 7: ...ctured gas Single Stage Single stage controls with standard and slow opening regulators model numbers with suffix S M T can be converted from one gas to the other with a conversion kit See Table 4 for...

Page 8: ...d the procedures outlined in your appliance manufacturer instructions can differ requiring special instructions To Turn ON Appliance STOP Read the Warnings Above Before Proceeding 1 The lighting seque...

Page 9: ...mm 1 4 po Configuration du corps passage direct reportez vous au Tableau 1 pour conna tre la taille d entr e et de sortie Caract ristiques lectriques Tension et fr quence 24 V c a 50 60 Hz Appel de co...

Page 10: ...tine vitez tout contact avec le r gulateur Lorsque des produits chimiques sont en suspension dans l air comme c est le cas dans le cadre de certaines applications industrielles ou agricoles prot gez l...

Page 11: ...ait tre expos des vapeurs de produits chimiques ou des gouttes d eau Installation de la tuyauterie sur le r gulateur Toute la tuyauterie doit tre conforme aux codes et r glements locaux ou au code nat...

Page 12: ...MM MINIMUM MONT E R GULATEUR DE GAZ ALIMENTATION EN GAZ TUBE HORIZONTAL MONT E MF3077C 2 1 2 2 1 2 TOUS LES COUDES DES TUBES M TALLIQUES DOIVENT TRE LISSES MISE EN GARDE COUPER L ARRIV E DE GAZ PRINC...

Page 13: ...le br leur principal est correctement r gl e pour assurer une combustion totale Suivez les instructions du fabricant de l appareil 2 POUR UNE V RIFICATION DE L ENTR E DE GAZ EN CHRONOM TRANT LE COMPT...

Page 14: ...ut causer des d g ts ou des blessures graves voire mortelles Ne d montez pas le r gulateur gaz car il ne contient pas de composants qui peuvent tre remplac s Toute tentative de d montage de r paration...

Page 15: ...n n cessaire de conversion Reportez vous au Tableau 4 pour plus d informations sur le num ro de pi ce du n cessaire de conversion correspondant 1 Coupez la vanne d alimentation en gaz de l appareil 2...

Page 16: ...c dures d finies par le fabricant de votre appareil peuvent diff rer et n cessiter des instructions sp ciales Pour mettre l appareil en marche ARR TEZ Lisez les avertissements ci dessus avant de conti...

Reviews: