resideo Aquastat L4006 Series Installation Instructions Manual Download Page 4

L4006,L4007 AQUASTAT CONTROLLERS

© 2020 Resideo Technologies, Inc. All rights reserved.
 This product is manufactured by Resideo Technologies, Inc. and its affiliates.

www.resideo.com

Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
95-6120B—05    M.S.  Rev. 05-20 | Printed in United States

Fig. 7. Typical wiring diagram for 24 V gas system using 

L4006C. 

Fig. 8. Typical Powerpile system wiring diagram, using 

L4006C.

Fig. 9. Typical systems with 120 V electrical heal 

primaries, using L4006C. 

OPERATION

For proper selection of settings, follow the boiler 

manufacturer's recommendations. 

1.

High limit controller—shuts off burner if water 

temperature exceeds high limit setting. Burner 

restarts when temperature drops to high limit set-

ting, less differential.

NOTE:

If L4006E, see Manual Reset below. 

2.

Low limit controller—maintains minimum boiler 

temperature for domestic hot water. Turns on 

burner at temperature setting, minus differential. 

3.

Circulator controller—prevents circulation of water 

that is not hot enough. Breaks circulator circuit at 

temperature setting minus differential, remakes at 

setting. 

ADJUSTING

Set the differential to correspond with the boiler 

manufacturer's recommendations. To adjust models 

with adjustable differential, rotate the wheel on the back 

of the snap switch until the desired reading is aligned 

with the “V” notch in the frame. The wheel provides an 

adjustment from 5 F to 30 F (3 C to 1 7 C). Replace the 

cover on the Aquastat controller. 

Adjust the control point to correspond with the boiler 

manufacturer's recommendations. To adjust insert a 

screwdriver in the slotted screw type head located 

beneath the window in the cover. Turn the scale to the 

desired control point. 

Manual Reset 

If the device includes manual reset (model L4006E), be 

sure to press the red reset button on the front of the 

case to make sure that the controller is not locked out 

on safety. In checking out the system, adjust the limit 

setting low enough so that temperature of the controlled 

medium reaches the high limit setting. When the limit 

setting is reached, the Aqua stat controller locks out and 

the burner shuts down. When temperature of the 

controlled medium drops to the high limit setting, minus 

differential, push the manual reset button and the 

system should again be operative. Reset control to 

proper high limit setting. 

CHECKOUT

Check to make certain the Aquastat controller has been 

installed and adjusted properly. Put the system into 

operation and observe the action of the device through 

several cycles to make certain that it provides proper 

control of the system as described under OPERATION. 

Further adjustments then can be made to meet more 

exact comfort requirements. 

24 VOLT

THERMOSTAT

L4006C

HIGH LIMIT

CONTROLLER

VALVE OPERATOR

TRANSFORMER

M1154

1

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS 

AND OVERLOAD PROTECTION AS REQUIRED.

L1 

(HOT)

L2

MILLIVOLTAGE

THERMOSTAT

L4006

HIGH LIMIT

CONTROLLER

MILLIVOLTAGE

VALVE OPERATOR

SAFETY

SHUTOFF

PILOTSTAT¨

POWER UNIT

POWER UNIT COIL

OPERATOR

COIL

PILOT

BURNER

M1156C

L1 

(HOT)

L2

1

L1 

(HOT)

L2

1

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS 

AND OVERLOAD PROTECTION AS REQUIRED.

LINE VOLTAGE

CONTROL CIRCUIT

L4006

LINE VOLT

THERMOSTAT

LOAD

LOW VOLTAGE

CONTROL CIRCUIT

L4006

LOW VOLTAGE

THERMOSTAT

1K

ELECTRIC

HEAT RELAY

LOAD

M1155C

Summary of Contents for Aquastat L4006 Series

Page 1: ...rained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Disconnect power supply before beginning installation to prevent electrical shock or equipment damage Mounting The boiler manufacturer generally provides a tapping for insertion of the Aqua stat controller s sensing element This tapping is located in a repres...

Page 2: ...howing L4006 model with horizontal well For Installation of Sensing Bulb in Immersion Well 1 Loosen screw at top of case above scale setting and remove cover Loosen 2 screws that secure adapter clamp See Fig 1 2 Insert the sensing element into the immersion well 3 Fasten the case of the Aquastat controller to the well with the adapter clamp Make certain that the clamp is properly positioned over t...

Page 3: ...Hookup for oil fired summer winter hydronic system with domestic hot water using L4006A or B L4007 A or B This Is typical where control for domestic hot water is added or where each Aquastat controller is mounted in a separate location Fig 6 Typical hookup for gas fired system with domestic hot water using L4006A E or L4007A M8774C SENSING BULB BULB COMPRESSION FITTING SEALING WASHER ADAPTER CLAMP...

Page 4: ...urer s recommendations To adjust insert a screwdriver in the slotted screw type head located beneath the window in the cover Turn the scale to the desired control point Manual Reset If the device includes manual reset model L4006E be sure to press the red reset button on the front of the case to make sure that the controller is not locked out on safety In checking out the system adjust the limit s...

Page 5: ...d immersion pour montage horizontal INSTALLATION Avant d installer ce Produit 1 Lire attentivement les instructions Le fait de ne pas les suivre risque d endommager le produit ou de constituer un danger 2 Vérifier les caractéristiques spécifiées dans les instructions et indiquées sur le produit et s assurer que celui ci correspond bien à l application à laquelle il est destiné 3 L installateur doi...

Page 6: ... proposées Selon l ouverture du raccord de chaudière l utilisation d un réducteur peut s avérer nécessaire 4 Remplir le système S assurer que la gaine est bien vissée afin d éviter les fuites NE PAS utiliser le boitier comme poignée pour serrer la gaine après que le régulateur ait été fixé à la gaine Fig 1 Vue interne du L4006 modèle avec gaine montée horizontalement Installation de l élément sens...

Page 7: ...lumage au mazout avec eau chaude domestlque utilisant un L4006A ou B L4007A ou B Ce genre de raccordement est courant lorsqu on ajoute un régulateur d eau chaude domestique ou lorsque chaque régulateur Aquastat est monté à un endroit différent Fig 6 Raccordement type d un système à allumage au gaz avec eau chaude domestique utilisant un L4006A E ou un L4007 A MF8774B BULBE RACCORD DE SERRAGE DU BU...

Page 8: ... chaudière À l aide d un tournevis à lame droite toumer la vis située sous la fenétre du couvercle jusqu au point de contrôle voulu Réarmement manuel Si l appareil offre une fonction de réarmement manuel modèle L4006E s assurer d appuyer sur le bouton de réarmement rouge sur le devant du boîtier afin que le régulaleur ne soit pas mis sous sécurité Pendant la vérification du système régler la limit...

Reviews: