30

9.3

 

Rack Mount Case (220V) 

Rated Power   

Capacity 

1KVA / 700W 

2KVA / 1400W

3KVA / 2100W

Input 

Voltage 

Single phase 220Vac, 160~300Vac at 100~70% load 

140~300Vac at 70~50% load, 120~300Vac at 0~50% load

Frequency 

50Hz or 60Hz +/- 4Hz 

Power Factor 

 0.95 

 0.97 

Output 

Voltage, Frequency 

Single phase /- 2% (230V or 240V re-settable via 

LCD panel), 50Hz or 60Hz +/-0.2Hz    (Battery mode) 

Transient Response 

+/- 3% (100% load variation) 

Waveform / Distortion 

Sine wave, THD < 3% at 0-100% linear load 

Over Load Capacity 

110~150% 30sec, then switch to bypass and auto 

re-transfer; >150% for 300ms 

Crest Ratio 

3 : 1 

Battery 

Voltage (longer backup 
time is available upon 
request) 

7Ah / 12V * 3pcs

7Ah / 12V * 8pcs 

Recharge Time 

5 hrs to 90% of full capacity after full load discharge 

Bypass 

Automatic: Overload and UPS failure 

By setting:    Voltage Range 176V~ 253V+/-20V (re-settable via LCD panel) 

Transfer Time 

AC fail 0 ms; 2.5ms typical from inverter to bypass and vice versa 

Audible Alarm 

Battery Mode 

Beeping every 4 seconds (re-settable) and per second when 

battery low   

Overload 

> 110% Beeping twice per second 

Fault 

Beep Continuously 

Indicator 

LED 

Normal (green), Warning (yellow), Fault (red) LED 

Communications 

DB9 Connector 

RS-232 Interface; Power monitoring software (Option) 

SNMP Intelligent Slot   

For Net Agent II / Mini (Option) with SNMP manager and Web 

browser 

Network 

Surge Protection 

RJ11 I/O port available for 10 base-T network 

or Fax / Modem 

Environment 

Temperature 

0-40 degree C; 32-104 degree F 

Relative Humidity 

0-95% non-condensing 

Acoustic Noise (at 1 M) 

 

 

Physical 

Net Weight (w/o batt.) 

8.0 kgs 

9.5 kgs 

10.5 kgs 

Net Weight (w/ batt.) 

15.5 kgs 

N/A 

N/A 

Dimension(LxWxH)mm 

465*440*88 

  Specifications are subject to change without notice.

 

 

31

9.4

 

Rack Mount Case (120V) 

Rated Power 

Capacity 

1KVA / 700W 

1.5KVA / 1050W 

3KVA / 2100W 

Input 

Voltage 

60~138VAC 

Base on load 

percentage

(110%-70%/60%-50%/50%-40%/40%-0%)

 

Frequency 

50Hz or 60Hz +/- 4Hz 

Power Factor 

 0.95 

Output 

Voltage, Frequency 

Single phase /- 2% (115V or 120V re-settable via 

LCD panel), 50Hz or 60Hz +/-0.5%    (Battery mode) 

Transient Response 

+/- 3% (100% load variation) 

Waveform / Distortion 

Sine wave, THD < 3% at 0-100% linear load 

Over Load Capacity 

105~150% 30sec, then switch to bypass and auto 

re-transfer; >150% for 200ms 

Crest Ratio 

3 : 1 

Battery 

Voltage (longer backup time 
is available upon request) 

7Ah / 12V * 3pcs

7Ah / 12V * 4pcs 

7Ah / 12V * 8pcs 

Recharge Time 

5 hrs to 90% of full capacity after full load discharge 

Bypass 

Automatic: Overload and UPS failure 

By setting:    Voltage Range 115V+/-20V (re-settable via LCD panel) 

Transfer Time 

AC fail 0 ms; 2.5ms typical from inverter to bypass and vice versa 

Audible Alarm 

Battery Mode 

Beeping every 4 seconds (re-settable) and per second 

when battery low   

Overload 

  Beeping twice per second 

Fault 

Beep Continuously 

Indicator 

LCD 

UPS status, I/P&O/P voltage& frequency, Battery voltage, 

Battery capacity, Loading %, Temperature, History record 

LED 

Normal (green), Warning (yellow), Fault (red) LED 

Communications

DB9 Connector 

RS-232 Interface; Power monitoring software (Option) 

SNMP Intelligent Slot   

For Net Agent II / Mini (Option) with SNMP manager and 

Web browser 

Network 

Surge Protection 

RJ11 I/O port available for 10 base-T network or Fax / Modem

 

Environment 

Temperature 

0-40 degree C; 32-104 degree F 

Relative Humidity 

0-95% non-condensing 

Acoustic Noise (at 1 M) 

< 45 dBA 

< 45 dBA 

< 50 dBA 

Physical 

Net Weight (w/o batt.) 

9.1 kgs 

11.5 kgs 

12.3 kgs 

Net Weight (w/ batt.) 

15.3 kgs 

N/A 

N/A 

Dimension (LxWxH)mm 

465*440*88 

  Specifications are subject to change without notice.

 

Summary of Contents for RP-UPH

Page 1: ...rruptible Power Supply 1 CONTENTS 1 INTRODUCTION 2 2 SAFTY INSTRUCTION 3 3 SYSTEM DESCRIPTION 6 4 CABLE CONNECTION 14 5 OPERATION 15 6 TROUBLE SHOOTING GUIDE 21 7 OPERATION MODES OF THE UPS 24 8 COMPU...

Page 2: ...weight and compact size easy to transport and place 1 3 Important Notices To be sure that the UPS will be operated correctly the following items should be noticed 3 1 Read instructions carefully befo...

Page 3: ...ds or other foreign objects can enter the UPS system 5 2 5 Maintenance and Service 1 Caution risk of electric shock Even after the unit is disconnected from the mains power supply building wiring sock...

Page 4: ...ect Down key 3 It is pressed to select downward the UPS status on LCD Display 7 Display Function LCD Display 1 This indicates the UPS operation information including UPS status input output voltage in...

Page 5: ...8 2KVA 3KVA Tower Case 9 1KVA 2KVA 3KVA Rack Mount Case...

Page 6: ...e Protection 8 Breaker 4 Remote Control Detachable LCD Panel Option 9 Input Socket 5 Output Socket NEMA or IEC 11 1KVA Rack Mount Case 1 Fax Modem Surge Protection 6 Input Socket 2 DB 9 RS 232 Interfa...

Page 7: ...tion 9 Breaker 5 Output Socket NEMA or IEC 10 Input Socket 13 2KVA 3KVA Rack Mount Case 1 Breaker 7 DB 9 RS 232 Interface Port 2 Remote Control Detachable LCD Panel Option 8 Input Socket 3 External Ba...

Page 8: ...is model is with socket types only NEMA or IEC Simply plug the load power cord to the output sockets to complete connection 15 5 Operation 5 1 Check Prior to Start Up 1 Ensure the UPS is in a suitable...

Page 9: ...S is stored over 3 months please keep supplying power to the UPS for at least 24 hours to ensure battery fully recharged 5 4 LCD Display Use Up Down key to select menu displays of the LCD described be...

Page 10: ...w and HI high In this screen press on off Control Key to enter the following steps for LO HI voltage setting B The cursor will pop up to indicate the item newly selected Press on off Control Key to ge...

Page 11: ...ected press on off Control Key again to save the data 21 6 Trouble Shooting Due to careful design and strict tests of our products fail of UPS seldom occurs However once they do fail in some situation...

Page 12: ...per 0 5 second Please reduce the critical load to 100 23 5 AC utility power is normal but the load is supplied by AC utility power via bypass Output power is more than 150 Warning LED lits up and buz...

Page 13: ...DC AC inverter and static switch to support power to load The battery charging voltage comes from AC utility input and converted by AC DC charger to support battery charging power 25 7 3 AC Utility Fa...

Page 14: ...pply RS 232 for monitoring software like RUPSII or UPSilon 2000 of Megatec Company The UPS communicates with the computer by sending out RS 232 data streams to one of the serial ports By this method t...

Page 15: ...465 200 352 465 200 352 Specifications are subject to change without notice 9 SPECIFICATIONS 29 9 2 Tower Case 120V Rated Power Capacity 1KVA 700W 1 5KVA 1050W 3KVA 2100W Input Voltage 60 138VAC Base...

Page 16: ...8 Specifications are subject to change without notice 31 9 4 Rack Mount Case 120V Rated Power Capacity 1KVA 700W 1 5KVA 1050W 3KVA 2100W Input Voltage 60 138VAC Base on load percentage 110 70 60 50 50...

Page 17: ...32...

Reviews: