Danger of carbon monoxide poisoning! Outside air intake should be 10' (minimum) away from
sources of carbon monoxide or other toxic gases such as chimneys, furnace, or water heater
exhausts.
Do not locate outside air intake where vehicles may be serviced or left idling. Do not locate the
outside air intake inside an enclosed space.
WARNING
Danger of Damage Due to Condensation in or on Ducts to Outside.
Both ducts connecting the unit to the outside must be insulated with sealed vapor barriers inside
and out to prevent condensation and/or freezing inside the insulation or on the duct surface.
CAUTION
2.3 FORKLIFT INFORMATION
The assembled PA unit can be moved with a forklift for final positioning.
Minimum fork lengths are as follows:
PA6X and PA8X
PA 9X and PA12X
u
Side lift: 40"
u
Side lift: 40"
u
End lift: 40"
u
End lift: 66"
Avoid damage to unit! Observe the following:
1. Unit weights are shown in dimension drawings at the front of the manual.
2. See drawing for maximum fork size and correct fork spacing.
3. See chart for mimum fork lengths.
4. Keep forks level while entering the unit base.
5. When lifting unit from sides, be careful not to crush the duct flanges.
CAUTION
OPERATION
Danger of injury to people when moving the unit! Observe the following:
1. Only properly trained, certified, and competent forklift operators may move the unit.
2. Units are large and will block forward vision. An assistant must be present to direct the
operator.
3. Keep forks level while entering the unit base.
4. Keep unit level while moving.
WARNING