background image

HE4XRT               

Due to continuing product development, specifications are subject to change without notice.

               © 2012 RenewAire LLC

134775_005                      HE4XRTMan_Jan12.indd                      Revised 01/2012                       www.renewaire.com                      

Page 4

Inside Ductwork System

Follow Engineer’s Ductwork Design

Ductwork should be designed by an engineer to allow the unit to 

provide the required airflow.

Duct Insulation

If the inside ducts run through un-conditioned spaces, they must 

be insulated, with a sealed vapor barrier on both inside and 

outside of insulation.

Use Static Taps in Doors to Measure Airflow Rates

See “Cross-Core Static Drop” in MEASURING AIRFLOW table. These 

may be used to directly measure airflow in the unit.

Change Sheaves if required to Set and Balance Air Flow

In most applications, the airflow rate for both the Fresh Air and 

the Exhaust Air should be roughly equal (or “balanced”) for best 

performance of the HE4XRT Unit. 

In most cases, the job engineer will specify flow rates and ESP 

requirements. The blower motors will also be specified to provide 

the required performance.

See  unit  specification  sheet  for  CFM/ESP  curves  for  available 

horsepower motors.

See drawings below for examples of some common installation 

approaches:

Sound Attenuation

General Practices

Take these simple steps to attenuate noise from the unit.

Outside the building:

The exhaust hood is the primary source of noise outside the 

building. When practical, orient the exhaust air hood to point 

away from houses or public areas.

At the Curb:

Cut the holes in the roof deck to fit closely around the duct(s) 

passing through the roof deck. Seal all gaps around the duct(s) 

at the roof deck.

Ducts:

Make sure the ductwork at the unit outlets is stiff enough to 

resist the flexure and resulting booming associated with system 

start-up and shut-off, as well as the turbulent flow conditions at 

the blower outlets.

In general, provide smooth transitions from the ERV’s outlets to the 

duct. The ducts connecting to the outlets should be straight for a 

sufficient distance, with gradual transitions to the final duct size.

These guidelines are consistent with SMACNA recommended duct 

layout  practices  for  efficient  and  quiet  air  movement.  Follow 

SMACNA guidelines.

Radiated Noise

The HE4XRT is insulated with high-density fiberglass. This provides 

significant attenuation of radiated sound from the unit itself.

The  outlet  ducts  can  be  significant  sources  of  radiated  sound 

as well. The FA duct should be insulated for sound control. This 

insulation  should  start  at  the  unit. At  a  minimum  the  first  ten 

feet of duct should be insulated. All parts of the FA and RA ducts 

located in a mechanical space with noise-generating equipment 

also should be insulated for sound control, both to minimize 

sound radiation out of the FA duct, and also to control sound 

radiation into both ducts.

Aerodynamic (Velocity) Noise

When sound attenuation is a design concern, the primary 

consideration is velocity noise at the unit’s Fresh Air blower 

outlet. The average velocity at the Fresh Air blower outlet is 

1230 FPM when the unit is operating at 4290 CFM. The average 

velocity at the Exhaust Hood outlet is 1420 FPM when the unit is 

operating at 4290 CFM.

Danger of Electrical Shock when servicing an installed unit.

ALWAYS DISCONNECT POWER SOURCE BEFORE 

SERVICING! More than one disconnect switch may be 

required. 

Proper Wiring Size Selection and Wiring Installation 

are the Responsibility of the Electrical Contractor.

Electrical Specifications

Electrical Options are identified on the Unit Label (located near 

electrical box). Find the complete Unit Model Number in the 

lower left corner of the Unit Label.

HE-4X_RTV

ROOF

Unit connected to

Return Duct of

nearby AHU.

HE-4X_RTR

Rooftop AHU

ROOF

RTR Unit with dedicated ducts

collecting Room Air.  

Fresh Air is ducted into 

horizontal return connection 

of adjacent AHU.

HE-4X_RTV

ROOF

Stand-alone installation with 

independent ducts for 

exhaust and supply air.

AHU

Summary of Contents for HE4XRT

Page 1: ...fficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment that might be installed in the area affected by this equipment If this unit is e...

Page 2: ...s of unit base into the Roof Curb to secure the unit against high winds On Equipment Rails Review drawing of Roof Curb and specify Equipment Rail to fit Before installing HE4XRT apply roofing and coun...

Page 3: ...flow measuring stations and manometers in the ductwork connected to the unit These also can be used to determine when filters should be cleaned or changed Use Static Taps in Doors to Measure Airflow R...

Page 4: ...ide smooth transitions from the ERV s outlets to the duct The ducts connecting to the outlets should be straight for a sufficient distance with gradual transitions to the final duct size These guideli...

Page 5: ...ARD UNIT CONTROL WIRING V ONBOARD VFD BOTH AIRSTREAMS F ONBOARD VFD FA AIRSTREAM E ONBOARD VFD EA AIRSTREAM DAMPERS NO DAMPERS STANDARD D DAMPERS BOTH AIRSTREAMS E DAMPER EA AIRSTREAM F DAMPER FA OA A...

Page 6: ...DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY JUMPER PROVIDED MOTOR EA FACTORY SETTINGS Overload Relay Trip Settings Motor Nameplate FLA Overload Relay Mode Settings Manua...

Page 7: ...Operation Call for EA Blower Operation OUT 24VAC Class II RELAY TRANSFORMER AND CIRCUIT BREAKER DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY 24VAC JUMPER PROVIDED FACTORY...

Page 8: ...the control terminals of this unit 5 Unit is not equipped to receive analog signals such as 1 10vdc or 4 20mA 6 Unit is not equipped to communicate directly with Building Management Systems such as BA...

Page 9: ...nnect Terminals 2 3 Connect Switch between Terminals 1 4 UNIT INTERNAL CONTROL WIRING SIMPLIFIED A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY UNIT INTERNAL CONTROL WIRING SIMPLIFIED...

Page 10: ...1598 2 3350 2 6 2950 2 6 2590 2 3 2175 2 0 1670 1 3210 3 0 2870 2 7 2500 2 4 1742 0 2800 2 9 5 b 1623 4 4165 3 7 3965 3 5 3750 3 3 3475 3 0 3055 2 5 2685 2 3 2290 2 0 1728 2 4240 4 3 4050 4 0 3820 3 7...

Page 11: ...located on the unit as to give you the most accurate airflow measurement NOTE Do not relocate pressure ports To read SCFM of Fresh Air FA install the high pressure side of your measuring device to the...

Page 12: ...unds 3 HP BLOWER 4 pounds 5 HP BLOWER 5 pounds GENERAL CLEANING AND INSPECTION Perform general cleaning and inspection when changing filters Remove dust from blower wheels periodically Remove paper le...

Reviews: