Measuring Airflow

Equipment Required

•  A magnehelic gauge or other device capable of measuring 0 

to 1.5 in. water of differential pressure.

•  2 pieces of natural rubber latex tubing, 1/8” ID, 1/16” Wall 

works the best. NOTE: Be sure to remove cap from pressure 

port before inserting tubing. Insure tubing is well seated 

in pressure ports. NOTE: The tubing should extend in the 

pressure port approx. 1 inch.

Cross Core Static Pressure Measurement Instructions

•  The individual differential static pressures (DSP) can be 

measured using the installed pressure ports located in the 

front of the units core access doors. NOTE: These ports 

have been carefully located on the unit as to give you the 

most accurate airflow measurement. NOTE: Do not relocate 

pressure ports. 

•  To read SCFM of Fresh Air (FA) install the “high” pressure side 

(+) of your measuring device to the Outside Air (OA) port and 

the “low” pressure side (-) to the Fresh Air (FA) port.

•  To read SCFM of Room Air (RA) install the “high” pressure 

side (+) of your measuring device to the Room Air (RA) port 

and the “low” pressure side (-) to the Exhaust Air (EA) port.

•  Use the reading displayed on your measurement device to 

cross reference the CFM output using the conversion chart. 

NOTE: Be sure to replace cap into pressure port when air 

flow measuring is completed.

ONLY

RTH, RTF

RA

OA

FA

RTV, RTF

ONLY

RTV, RTR

ONLY

RA

RTH, RTR

FA

ONLY

FRONT

VIEW

E-box

Pressure Taps (4)

EA

Differential Static Across Core DSP vs. CFM

HE4XR

T

DSP 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00

Fresh Air

 (FA)

CFM 1450 2030 2600 3180 3760 4340 4910 5490 6070

Room Air

 (RA)

CFM 840 1370 1900 2430 2960 3480 4020 4550 5080

The proper operating airflow range for this model is 1000 - 

4400 CFM.

Summary of Contents for HE4XRT

Page 1: ...fficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment that might be installed in the area affected by this equipment If this unit is e...

Page 2: ...s of unit base into the Roof Curb to secure the unit against high winds On Equipment Rails Review drawing of Roof Curb and specify Equipment Rail to fit Before installing HE4XRT apply roofing and coun...

Page 3: ...flow measuring stations and manometers in the ductwork connected to the unit These also can be used to determine when filters should be cleaned or changed Use Static Taps in Doors to Measure Airflow R...

Page 4: ...ide smooth transitions from the ERV s outlets to the duct The ducts connecting to the outlets should be straight for a sufficient distance with gradual transitions to the final duct size These guideli...

Page 5: ...ARD UNIT CONTROL WIRING V ONBOARD VFD BOTH AIRSTREAMS F ONBOARD VFD FA AIRSTREAM E ONBOARD VFD EA AIRSTREAM DAMPERS NO DAMPERS STANDARD D DAMPERS BOTH AIRSTREAMS E DAMPER EA AIRSTREAM F DAMPER FA OA A...

Page 6: ...DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY JUMPER PROVIDED MOTOR EA FACTORY SETTINGS Overload Relay Trip Settings Motor Nameplate FLA Overload Relay Mode Settings Manua...

Page 7: ...Operation Call for EA Blower Operation OUT 24VAC Class II RELAY TRANSFORMER AND CIRCUIT BREAKER DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY 24VAC JUMPER PROVIDED FACTORY...

Page 8: ...the control terminals of this unit 5 Unit is not equipped to receive analog signals such as 1 10vdc or 4 20mA 6 Unit is not equipped to communicate directly with Building Management Systems such as BA...

Page 9: ...nnect Terminals 2 3 Connect Switch between Terminals 1 4 UNIT INTERNAL CONTROL WIRING SIMPLIFIED A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY UNIT INTERNAL CONTROL WIRING SIMPLIFIED...

Page 10: ...1598 2 3350 2 6 2950 2 6 2590 2 3 2175 2 0 1670 1 3210 3 0 2870 2 7 2500 2 4 1742 0 2800 2 9 5 b 1623 4 4165 3 7 3965 3 5 3750 3 3 3475 3 0 3055 2 5 2685 2 3 2290 2 0 1728 2 4240 4 3 4050 4 0 3820 3 7...

Page 11: ...located on the unit as to give you the most accurate airflow measurement NOTE Do not relocate pressure ports To read SCFM of Fresh Air FA install the high pressure side of your measuring device to the...

Page 12: ...unds 3 HP BLOWER 4 pounds 5 HP BLOWER 5 pounds GENERAL CLEANING AND INSPECTION Perform general cleaning and inspection when changing filters Remove dust from blower wheels periodically Remove paper le...

Reviews: