HE4XRT Airflow Performance

Motor 

HP

Blower 

RPM

Turns 

Open

External Static Pressure (in. w.g.)

0.00

0.25

0.50

0.75

1.00

1.25

1.50

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

2

1186

4

3099

1.5

2790

1.3

2295

1.1

1790

0.8

1150

0.6

1326

2

3465

2.2

3185

1.9

2810

1.7

2335

1.4

1885

1.2

1290

0.9

1466

0

2451

1.8

2026

1.5

1485

1.2

(a)

1455

4

3812

2.7

3550

2.5

3285

2.3

2820

2.0

2400

1.7

1970

1.5

1450

1.2

1527

3

3750

2.9

3500

2.7

3085

2.4

2676

2.1

2300

1.9

1815

1.5

1598

2

3350

2.6

2950

2.6

2590

2.3

2175

2.0

1670

1

3210

3.0

2870

2.7

2500

2.4

1742

0

2800

2.9

(b)

1623

4

4165

3.7

3965

3.5

3750

3.3

3475

3.0

3055

2.5

2685

2.3

2290

2.0

1728

2

4240

4.3

4050

4.0

3820

3.7

3450

3.3

3050

3.0

2720

2.6

1832

0

4345

4.9

4140

4.5

3850

4.2

3490

3.7

3145

3.3

(a) Sheaves for 3HP motors can be adjusted from 1742 RPMs at 0 turns to 1419 RPM at 4.5 turns. Operating range shown is best for motor efficiency.

(b) Sheaves for 5HP motors can be adjusted from 1832 RPMs at 0 turns to 1493 RPM at 6.5 turns. Operating range shown is best for motor efficiency.

HE4XRT Replacement Parts

M

N

P

L

R

S

A CORES

B FILTERS

C BLOWER DOOR

D TURN  LATCH

E DISCONNECT SWITCH

F TRANSFORMER

G ISOLATION RELAY

H OVERLOAD RELAY

J CONTACTOR

K CORE DOOR

L MOTOR

M MOTOR MOUNT

N BLOWER

P MOTOR SHEAVE

R BELT

S BLOWER SHEAVE
T INTAKE HOOD

U EXHAUST HOOD

A

B

C

G

D

H

E

J

F

K

T

U

Summary of Contents for HE4XRT

Page 1: ...fficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment that might be installed in the area affected by this equipment If this unit is e...

Page 2: ...s of unit base into the Roof Curb to secure the unit against high winds On Equipment Rails Review drawing of Roof Curb and specify Equipment Rail to fit Before installing HE4XRT apply roofing and coun...

Page 3: ...flow measuring stations and manometers in the ductwork connected to the unit These also can be used to determine when filters should be cleaned or changed Use Static Taps in Doors to Measure Airflow R...

Page 4: ...ide smooth transitions from the ERV s outlets to the duct The ducts connecting to the outlets should be straight for a sufficient distance with gradual transitions to the final duct size These guideli...

Page 5: ...ARD UNIT CONTROL WIRING V ONBOARD VFD BOTH AIRSTREAMS F ONBOARD VFD FA AIRSTREAM E ONBOARD VFD EA AIRSTREAM DAMPERS NO DAMPERS STANDARD D DAMPERS BOTH AIRSTREAMS E DAMPER EA AIRSTREAM F DAMPER FA OA A...

Page 6: ...DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY JUMPER PROVIDED MOTOR EA FACTORY SETTINGS Overload Relay Trip Settings Motor Nameplate FLA Overload Relay Mode Settings Manua...

Page 7: ...Operation Call for EA Blower Operation OUT 24VAC Class II RELAY TRANSFORMER AND CIRCUIT BREAKER DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY 24VAC JUMPER PROVIDED FACTORY...

Page 8: ...the control terminals of this unit 5 Unit is not equipped to receive analog signals such as 1 10vdc or 4 20mA 6 Unit is not equipped to communicate directly with Building Management Systems such as BA...

Page 9: ...nnect Terminals 2 3 Connect Switch between Terminals 1 4 UNIT INTERNAL CONTROL WIRING SIMPLIFIED A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY UNIT INTERNAL CONTROL WIRING SIMPLIFIED...

Page 10: ...1598 2 3350 2 6 2950 2 6 2590 2 3 2175 2 0 1670 1 3210 3 0 2870 2 7 2500 2 4 1742 0 2800 2 9 5 b 1623 4 4165 3 7 3965 3 5 3750 3 3 3475 3 0 3055 2 5 2685 2 3 2290 2 0 1728 2 4240 4 3 4050 4 0 3820 3 7...

Page 11: ...located on the unit as to give you the most accurate airflow measurement NOTE Do not relocate pressure ports To read SCFM of Fresh Air FA install the high pressure side of your measuring device to the...

Page 12: ...unds 3 HP BLOWER 4 pounds 5 HP BLOWER 5 pounds GENERAL CLEANING AND INSPECTION Perform general cleaning and inspection when changing filters Remove dust from blower wheels periodically Remove paper le...

Reviews: