background image

HE4XRT               

Due to continuing product development, specifications are subject to change without notice.

               © 2012 RenewAire LLC

134775_005                      HE4XRTMan_Jan12.indd                      Revised 01/2012                       www.renewaire.com                      

Page 8

OBSERVE THESE LIMITS TO WIRE LENGTH AND GAUGE, 

in order to ensure reliable operation of the control system.
Wire Gauge

#22

#20

#18

#16

#14

#12

Circuit Length

100’

150’

250’

400’

700’

1000’

“Circuit Length” is distance from ERV to Control Device.

How to Reset the 24VAC Circuit Breaker

If the transformer is subjected to an excessive load or a short 

circuit, the circuit breaker will trip to prevent the failure of the 

transformer. When it trips the circuit breaker’s button pops up. 

Shut off the primary-side power to the unit, and remove the 

excessive load or the short. The circuit breaker can be reset 

about fifteen seconds after it trips by pressing in the button.

NOTE: 

INSTALLING CONTRACTOR:

If primary-side voltage is 230VAC, move black primary-side lead 

from transformer’s “208V” terminal to the transformer’s terminal 

marked “240V” (“230V” in some units).
Do not move the black primary-side lead that is connected to the 

transformer’s “COM” terminal.

Limits of Power Output

If limits on wire gauge and length are observed, you may connect 

control devices that draw up to 8VA to the blue and red wires. 

More than one device can be connected as long as total steady-

state load does not exceed 8VA.

This ERV is provided with a Class II 24VAC power supply system that 

operates the unit’s contactor(s) for EV450 and HE1X. The ERV’s 

24VAC Power Supply can also be used to power the externally-

installed controls system: up to 8VA of power is available.
The unit’s power supply system includes isolation relay(s) so you 

can use external controls whose contact ratings are as low as 50mA 

(1.2VA). Also, it is possible to operate the isolation relays with 24VAC 

power from an external source (with proper wiring connections).
A built-in circuit-breaker prevents damage to the transformer and other 

low-voltage components in the event of a short-circuit or overload. In 

extreme cases, the transformer itself is designed to fail safely.

24VAC Power Supply 

Provided with this ERV Unit

1.  Connect only to components intended for use with 24VAC 

power.

2.  Do not undersize the low-voltage wires connected to this 

device. Observe the wire length and gauge limits indicated 

in this manual.

3.  Do not overload this unit’s 24VAC power supply system. 

Confirm that the power requirements of devices you connect 

to this power supply system do not exceed 8VA in total.

4.  If an external source of 24VAC power is used to control the 

unit, consult the wiring schematics and connect the external 

power  only  to  the  specified  terminals  in  order  to  avoid 

damaging the unit or external controls. Connect only CLASS 

II power to the control terminals of this unit.

5.  Unit is not equipped to receive analog signals (such as 

1-10vdc or 4-20mA).

6.  Unit is not equipped to communicate directly with Building 

Management Systems (such as BACNET, LONWORKS, etc.). 

However, the unit can be controlled by powered or non-

powered contacts operated by any kind of control system.

Specifications 

•  Nominal Output Voltage under load:     24VAC

•  Typical Output Voltage at no load: 

29-31V

•  Minimum contact rating

       for connected control device:   

(50mA (1.2VA)

•  Circuit Breaker Trip Point: 

 

3A

Motor Starters

This unit uses IEC-style motor starters to protect the motors 

against overload.
IEC-style motor starters use Overload Relays to detect excessive 

current and interrupt the control circuit that engages the motor’s 

contactors.

Overload Relays are sized to Full Load Amp (FLA) rating of the 

protected motor. The Overload Relays can be adjusted to trip 

(interrupt the control circuit) at a specific setting within a range.
Overload Relays should initially be set at the FLA rating of the 

motor (see Unit Rating Label). If necessary to prevent nuisance 

tripping at start-up, the Relays can be adjusted to trip no higher 

than 115% of the motor’s FLA rating.
For safest operation, the overload relays should also be used in 

manual reset mode with trip test capability.
NOTE: As factory-wired, if one blower motor is shut down due to 

overload by its Motor Starter, the other motor will also be shut down.
NOTE: Terminals 96 & 97 of the Overload Relays and terminals 14 

& 13 of the Contactors are normally-open dry contacts that may 

be used to signal that the contactors are closed and/or that the 

Overload Relays have tripped.

DANGER OF INJURY OR DAMAGE.
The motors in this unit must not be run at an amperage 

that exceeds the motor’s rated full load amps and 

overload relays on the motor starters must be set at 

or below motor full load amps. For safest operation, 

the overload relays should also be used in hand reset 

mode with trip test capability.
It is the installer’s responsibility to measure the 

operating amperage of each motor. If the full load amp 

rating is exceeded, the amp draw must be reduced by 

substituting a smaller motor pulley or by adjusting 

the variable sheave. Continue these adjustments 

until the actual amperage is no more than the motor’s 

faceplate full load amps.
Failure to make this adjustment may result in 

unsafe motor winding temperatures or tripping of 

the supplied motor starter’s overload relay motor  

protection devices set at full load amps.

DANGER OF INJURY OR DAMAGE.
The relay must be set for correct FLA rating depending 

on the motor horsepower. See Unit Rating Label on 

motor for HP and FLA specifications.

Adhere to applicable local codes when adjusting the 

dial setting of the overload relays.

The Overload Relay output contacts 95 & 96 must 

remain in series with the low-voltage control circuit!  

Altering this will create a hazardous situation in 

which the motor is not protected against overload!

Summary of Contents for HE4XRT

Page 1: ...fficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment that might be installed in the area affected by this equipment If this unit is e...

Page 2: ...s of unit base into the Roof Curb to secure the unit against high winds On Equipment Rails Review drawing of Roof Curb and specify Equipment Rail to fit Before installing HE4XRT apply roofing and coun...

Page 3: ...flow measuring stations and manometers in the ductwork connected to the unit These also can be used to determine when filters should be cleaned or changed Use Static Taps in Doors to Measure Airflow R...

Page 4: ...ide smooth transitions from the ERV s outlets to the duct The ducts connecting to the outlets should be straight for a sufficient distance with gradual transitions to the final duct size These guideli...

Page 5: ...ARD UNIT CONTROL WIRING V ONBOARD VFD BOTH AIRSTREAMS F ONBOARD VFD FA AIRSTREAM E ONBOARD VFD EA AIRSTREAM DAMPERS NO DAMPERS STANDARD D DAMPERS BOTH AIRSTREAMS E DAMPER EA AIRSTREAM F DAMPER FA OA A...

Page 6: ...DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY JUMPER PROVIDED MOTOR EA FACTORY SETTINGS Overload Relay Trip Settings Motor Nameplate FLA Overload Relay Mode Settings Manua...

Page 7: ...Operation Call for EA Blower Operation OUT 24VAC Class II RELAY TRANSFORMER AND CIRCUIT BREAKER DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY 24VAC JUMPER PROVIDED FACTORY...

Page 8: ...the control terminals of this unit 5 Unit is not equipped to receive analog signals such as 1 10vdc or 4 20mA 6 Unit is not equipped to communicate directly with Building Management Systems such as BA...

Page 9: ...nnect Terminals 2 3 Connect Switch between Terminals 1 4 UNIT INTERNAL CONTROL WIRING SIMPLIFIED A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY UNIT INTERNAL CONTROL WIRING SIMPLIFIED...

Page 10: ...1598 2 3350 2 6 2950 2 6 2590 2 3 2175 2 0 1670 1 3210 3 0 2870 2 7 2500 2 4 1742 0 2800 2 9 5 b 1623 4 4165 3 7 3965 3 5 3750 3 3 3475 3 0 3055 2 5 2685 2 3 2290 2 0 1728 2 4240 4 3 4050 4 0 3820 3 7...

Page 11: ...located on the unit as to give you the most accurate airflow measurement NOTE Do not relocate pressure ports To read SCFM of Fresh Air FA install the high pressure side of your measuring device to the...

Page 12: ...unds 3 HP BLOWER 4 pounds 5 HP BLOWER 5 pounds GENERAL CLEANING AND INSPECTION Perform general cleaning and inspection when changing filters Remove dust from blower wheels periodically Remove paper le...

Reviews: