6.3 UNIT START-UP

6.3.1 Fixed-Speed Units 
Most fixed-speed units do not have any external controlling signals and only require turning 
on the disconnect switch, located on the E-Box. When the disconnect switch is turned ON, any 
dampers will first move into their correct operating positions and then power is suppled to the 
motor contactors, causing the fans to run. 
Some fixed-speed units are wired to receive an actuating signal from an external source. 
If there is an external actuating signal source, verify the type of signal and that it is wired 
according to the low-voltage wiring diagrams found in Section 5.6 of this manual. Turn on the 
disconnect switch and then turn ON the actuating device. After any dampers have moved into 
their correct positions, power is then applied to the motor contactors and the fans will begin 
running.

NOTE: The tubing 
should extend in 
the pressure port 

approx. 1".

OPERATION

It is important to balance the airflows after the unit is operational and all ductwork has been installed. 
Balancing the airflows is typically required by state and/or local codes, and is often specified by the 
HVAC design engineer. 
Optimum efficiency of the enthalpic cores is achieved when the airstreams are properly balanced. 

IMPORTANT

NOTE: Make sure 
clean filters are 
installed before 

balancing airflow. Dirty 
or clogged filters reduce 
airflow through the unit.

6.4 BALANCING AIRFLOW

Equipment Required:

u

   A magnehelic gauge or other device capable of measuring 0–1.0 in. water of differential 

pressure.

u

  2 pieces of natural rubber latex tubing, 1/8" ID, 1/16" Wall works the best. 

The individual differential static pressures (DP) are measured using the installed pressure ports 
located in the front of the units core access doors. 
Do not relocate pressure ports.
Procedure: 

u

   To read SCFM of Fresh Air (FA) install the “high” pressure side (+) of your measuring device 

to the Outside Air (OA) port and the “low” pressure side (-) to the Fresh Air (FA) port.

u

   To read SCFM of Room Air (RA) install the “high” pressure side (+) of your measuring device 

to the Room Air (RA) port and the “low” pressure side (-) to the Exhaust Air (EA) port.

u

   Use the reading displayed on your measurement device to cross reference the CFM output 

using the conversion chart.

NOTE: These 
ports are carefully 
located on the unit 

to give the most accurate 
airflow measurement. 
Do not relocate pressure 
ports.

www.renewaire.com     (800) 627- 4499 

[email protected]

PRESSURE PORTS (4)

FIGURE 6.4.0 HE1.5XINH PRESSURE PORT LOCATIONS, TYPICAL

NOTE: ERV airflows 
are to be balanced 
after all ductwork is 

installed. Balancing of air-
flows is typically required by 
local or state building codes 
or by the HVAC design 
engineer.

Summary of Contents for HE ERV Series

Page 1: ...HE1 5XINH HE1 5XINV HE SERIES ERV Installation Operation and Maintenance Manual Model HE1 5XINH shown...

Page 2: ...Allow the motor to fully cool to reset the thermal protector you should feel or hear a click when the thermal protector resets while pushing the reset button WARNING ARC FLASH AND ELECTRIC SHOCK HAZA...

Page 3: ...data from the Option Code H 5 1 I E J N Option Code Serial Number SO NOTE This page is to be completed by the installing contractor The completed document is to be turned over to the owner after start...

Page 4: ...ipped loose Backdraft damper OA or EA Digital time clock wall mount TC7D W in exterior enclosure TC7D E Carbon dioxide sensor control wall mount CO2 W duct mount CO2 D IAQ sensor wall mount IAQ W duct...

Page 5: ...tions Typ EA Model HE1 5XINH Drawing Type Unit Dimension Version MAY18 ABBREVIATIONS EA Exhaust Air to outside OA Outside Air intake RA Room Air to be exhausted FA Fresh Air to inside INSTALLATION ORI...

Page 6: ...e Backdraft damper OA or EA Digital time clock wall mount TC7D W in exterior enclosure TC7D E Carbon dioxide sensor control wall mount CO2 W duct mount CO2 D IAQ sensor wall mount IAQ W duct mount IAQ...

Page 7: ...Unit Configurations Typ Model HE1 5XINV Drawing Type Unit Dimension Version MAY18 ABBREVIATIONS EA Exhaust Air to outside OA Outside Air intake RA Room Air to be exhausted FA Fresh Air to inside INST...

Page 8: ...Wire Control Unpowered 21 5 6 2 Control Sending 24 VAC On Signal 21 5 6 3 Control System with two Non Powered Relay Contacts 21 5 6 4 Control System Sending two 24 VAC On Signals from an external powe...

Page 9: ...endent Blower Control 20 Figure 5 6 0 A Switch or Non Powered Control Using Unit s 24 VAC Power Supply 21 Figure 5 6 1 24 VAC from an External Source 21 Figure 5 6 2 Two External Non Powered Relay Con...

Page 10: ...er both Airstreams with no Bypass Digit 24 Paint and Customization E Motorized Damper EA Airstream with no Bypass None F Motorized Damper FA Airstream with no Bypass W White Paint S Backdraft Damper O...

Page 11: ...e HE1 5XRT Installation and Operation Manual These ERVs are commonly installed as part of an air handling system that provides heating and cooling of Supply Air They can also be installed to operate a...

Page 12: ...ic plate enthalpic core The enthalpic cores transfer both latent and sensible energies between the airstreams Gasketing is pre installed on the cores and must be positioned to provide a proper air sea...

Page 13: ...t The hoisting slings must be positioned around the ends of the unit so they do not touch the unit doors Unit hoisting weights and Center of Gravity are detailed in Sections 3 1 and 3 2 in this manual...

Page 14: ...HE1 5XINH_CORNER_WEIGHTS_ AUG19 dwg HE1 5XINH Corner Weights LR RR RF LF UNIT COG RANGE BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 75 HP 365 86 81 96 101 ADDITIONAL WEIGHTS FOR OPTIONS lbs Motors...

Page 15: ...Comply with all local building codes in the positioning of the duct openings Do not position the exhaust air outlet in a location where it will dump exhaust air into any enclosed or occupied space Th...

Page 16: ...INSTALLATION 5 2 FLOOR INSTALLATION Most units are installed in a location specified by others In general it is preferable to install the unit on a flat reasonably level surface such as a concrete fl...

Page 17: ...pt s pour une utilisation avec regulateur de vitesse elec tronique 5 4 1 Electronically Commutated Motors These ERVs may be ordered with factory installed features including Electronically Commutated...

Page 18: ...transformer When it trips the circuit breaker s button pops up Shut off the primary side power to the unit and remove the excessive load or the short The circuit breaker can be reset about fifteen sec...

Page 19: ...BK BK RD BK BK BU RD OR YL YL FIGURE 5 5 0 HE1 5XIN SINGLE PHASE UNIT STANDARD CHANGES NAME REV DATE Description Family Config No Damper RenewAire A B C D E New 0 11 3 2017 austine 1 6 7 2018 austine...

Page 20: ...BL YL FIGURE 5 5 2 HE1 5XIN SINGLE PHASE UNIT WITH INDEPENDENT BLOWER CONTROL CHANGES NAME REV DATE Description Family Config No Damper RenewAire 1 A B C D E New 0 11 3 2017 austine 1 6 7 2018 austine...

Page 21: ...IED 24VAC FROM AN EXTERNAL SOURCE Isolation Relay Coil Image 3 from filename Control Connections EV450 HE1XIN_DEC14 KMC 12 11 14 RED YEL YEL BLUE Unit 24VAC Power Supply Connect Blue First Yellow Lead...

Page 22: ...ower is available at the blue and red leads u Connect one of the yellow leads to the blue lead u Connect the switched output of the Control to the red lead to operate the ERV s isolation relay FIGURE...

Page 23: ...sary 2 Support the impeller subassembly Remove the eight 20 bolts B retaining the impeller subassembly plate to the side rails and front and back tabs 3 Lift the entire impeller subassembly C out of t...

Page 24: ...ation from the desired opening 3 Seal the edges of the cut insulation to prevent erosion of the insulation edges and having debris in the airstream 4 Install the patch pan over the undesired opening 5...

Page 25: ...mer wired for 208 VAC If the unit is receiving 230 VAC make sure the black primary side wire on the transformer s 208 V terminal has been moved to the 230 V terminal 6 2 3 Inspect Filters Clean filter...

Page 26: ...eams are properly balanced IMPORTANT NOTE Make sure clean filters are installed before balancing airflow Dirty or clogged filters reduce airflow through the unit 6 4 BALANCING AIRFLOW Equipment Requir...

Page 27: ...0 1400 1600 Clean filter Pressure Drop in w g Unit Airflow CFM Initial Pressure Drop of MERV 8 Filters supplied with this unit FIGURE 6 4 1 INITIAL PRESSURE DROP OF MERV 8 FILTERS SUPPLIED WITH THIS U...

Page 28: ...TENANCE 24 HRS AFTER START UP 24 hours after unit start up u In new installations check the air filters since they will often collect dust dirt and debris at time of start up 7 2 MAINTENANCE 30 DAYS A...

Page 29: ...aterial that must be kept clean at all times As a minimum cores should be cleaned once per year u DO NOT WASH OR ALLOW THE ENTHALPIC CORES TO GET WET u DO NOT EXPOSE THE ENTHALPIC CORES TO HIGH HEAT O...

Page 30: ...800 627 4499 30 HE Series Indoor ERV MAINTENANCE 7 7 MAINTENANCE RECORDS MAINTENANCE LOG ENTER DATES OF SERVICE OA FILTER CHANGE RA FILTER CHANGE INSPECTION CLEANING CLEAN CORE CLEAN BLOWERS INITIALS...

Page 31: ...you have the information called for in the Unit Information page in the front of this manual The person you speak with at the factory will need that information to properly identify the unit To contac...

Page 32: ...bility derived from innovative design practices expert workmanship and Quick Response Manufacturing QRM As the pioneer of static plate core technology in North America RenewAire is the largest ERV pro...

Reviews: