background image

11

1.800.627.4499

HE-Series Indoor

ERV

1.0 OVERVIEW

NOTE: This unit is 
an Energy Recovery 
Ventilator, or ERV. 

It is commonly referred to 
throughout this manual as 
an ERV.

1.1 DESCRIPTION

OVERVIEW

The HE1.5XIN Energy Recovery Ventilator is a device for recovering both sensible energy (heat) and 
latent energy (moisture) from the Exhaust Air from an Occupied Space and injecting those energies 
into an incoming Outside Airstream. It accomplishes this task by forcing the two airstreams through 
enthalpic cores, where the energy exchange takes place. The two airstreams pass through the 
enthalpic cores at right angles and the airstreams never mix together. See Section 2.2 Enthalpic 
Cores in this manual.
Each ERV has two electric blowers, one for each airstream. Fan speeds can be either single 
speed, or they can have electronically commutated motors. There are a number of different 
control devices available to control the operation or speed of the unit fans. For further 
information on available control accessories, see the

 HE RenewAire catalog.

There are two types of HE1.5X units, one for indoor installations and one for rooftop, or outdoor, 
installation. This manual is for the HE1.5XIN which is the indoor unit. For information on the outdoor 
version of this product, see the 

HE1.5XRT Installation and Operation Manual

.

These ERVs are commonly installed as part of an air handling system that provides heating and 
cooling of Supply Air. They can also be installed to operate as stand-alone devices when ducted 
directly to and from the Occupied Space. 
Each HE1.5XIN unit is available in either a horizontal or a vertical model. The difference between 
the two models is in the airflow/ducting configuration. Horizontally ducted units are identified by the 
model name HE1.5XINH and vertically ducted units are identified as model HE1.5XINV. 
Each unit has an integral 24 VAC power supply that is used internally and can also be used as a 
power source for other optional control devices.
The HE1.5XIN units are low-maintenance, requiring periodic replacement of the air filters and 
annual vacuuming of the enthalpic cores. See Section 7.0 Unit Maintenance in this manual.

IMPORTANT

It is important to understand and use the equipment airstream terminology as it is used in this 

manual. The airstreams are defined as:

u

   OUTSIDE AIR (OA): Air taken from the external atmosphere and, therefore, not previously circu-

lated through the system. 

u

   FRESH AIR (FA): Air that is downstream of the enthalpic cores and is ready for conditioning or 

for return to the Occupied Space. 

u

  RETURN AIR (RA): Air that is returned to the ERV from a conditioned space. 

u

   EXHAUST AIR (EA): Air that is removed from a heating or cooling appliance or from the Occu-

pied Space and discharged. 

Summary of Contents for HE ERV Series

Page 1: ...HE1 5XINH HE1 5XINV HE SERIES ERV Installation Operation and Maintenance Manual Model HE1 5XINH shown...

Page 2: ...Allow the motor to fully cool to reset the thermal protector you should feel or hear a click when the thermal protector resets while pushing the reset button WARNING ARC FLASH AND ELECTRIC SHOCK HAZA...

Page 3: ...data from the Option Code H 5 1 I E J N Option Code Serial Number SO NOTE This page is to be completed by the installing contractor The completed document is to be turned over to the owner after start...

Page 4: ...ipped loose Backdraft damper OA or EA Digital time clock wall mount TC7D W in exterior enclosure TC7D E Carbon dioxide sensor control wall mount CO2 W duct mount CO2 D IAQ sensor wall mount IAQ W duct...

Page 5: ...tions Typ EA Model HE1 5XINH Drawing Type Unit Dimension Version MAY18 ABBREVIATIONS EA Exhaust Air to outside OA Outside Air intake RA Room Air to be exhausted FA Fresh Air to inside INSTALLATION ORI...

Page 6: ...e Backdraft damper OA or EA Digital time clock wall mount TC7D W in exterior enclosure TC7D E Carbon dioxide sensor control wall mount CO2 W duct mount CO2 D IAQ sensor wall mount IAQ W duct mount IAQ...

Page 7: ...Unit Configurations Typ Model HE1 5XINV Drawing Type Unit Dimension Version MAY18 ABBREVIATIONS EA Exhaust Air to outside OA Outside Air intake RA Room Air to be exhausted FA Fresh Air to inside INST...

Page 8: ...Wire Control Unpowered 21 5 6 2 Control Sending 24 VAC On Signal 21 5 6 3 Control System with two Non Powered Relay Contacts 21 5 6 4 Control System Sending two 24 VAC On Signals from an external powe...

Page 9: ...endent Blower Control 20 Figure 5 6 0 A Switch or Non Powered Control Using Unit s 24 VAC Power Supply 21 Figure 5 6 1 24 VAC from an External Source 21 Figure 5 6 2 Two External Non Powered Relay Con...

Page 10: ...er both Airstreams with no Bypass Digit 24 Paint and Customization E Motorized Damper EA Airstream with no Bypass None F Motorized Damper FA Airstream with no Bypass W White Paint S Backdraft Damper O...

Page 11: ...e HE1 5XRT Installation and Operation Manual These ERVs are commonly installed as part of an air handling system that provides heating and cooling of Supply Air They can also be installed to operate a...

Page 12: ...ic plate enthalpic core The enthalpic cores transfer both latent and sensible energies between the airstreams Gasketing is pre installed on the cores and must be positioned to provide a proper air sea...

Page 13: ...t The hoisting slings must be positioned around the ends of the unit so they do not touch the unit doors Unit hoisting weights and Center of Gravity are detailed in Sections 3 1 and 3 2 in this manual...

Page 14: ...HE1 5XINH_CORNER_WEIGHTS_ AUG19 dwg HE1 5XINH Corner Weights LR RR RF LF UNIT COG RANGE BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 75 HP 365 86 81 96 101 ADDITIONAL WEIGHTS FOR OPTIONS lbs Motors...

Page 15: ...Comply with all local building codes in the positioning of the duct openings Do not position the exhaust air outlet in a location where it will dump exhaust air into any enclosed or occupied space Th...

Page 16: ...INSTALLATION 5 2 FLOOR INSTALLATION Most units are installed in a location specified by others In general it is preferable to install the unit on a flat reasonably level surface such as a concrete fl...

Page 17: ...pt s pour une utilisation avec regulateur de vitesse elec tronique 5 4 1 Electronically Commutated Motors These ERVs may be ordered with factory installed features including Electronically Commutated...

Page 18: ...transformer When it trips the circuit breaker s button pops up Shut off the primary side power to the unit and remove the excessive load or the short The circuit breaker can be reset about fifteen sec...

Page 19: ...BK BK RD BK BK BU RD OR YL YL FIGURE 5 5 0 HE1 5XIN SINGLE PHASE UNIT STANDARD CHANGES NAME REV DATE Description Family Config No Damper RenewAire A B C D E New 0 11 3 2017 austine 1 6 7 2018 austine...

Page 20: ...BL YL FIGURE 5 5 2 HE1 5XIN SINGLE PHASE UNIT WITH INDEPENDENT BLOWER CONTROL CHANGES NAME REV DATE Description Family Config No Damper RenewAire 1 A B C D E New 0 11 3 2017 austine 1 6 7 2018 austine...

Page 21: ...IED 24VAC FROM AN EXTERNAL SOURCE Isolation Relay Coil Image 3 from filename Control Connections EV450 HE1XIN_DEC14 KMC 12 11 14 RED YEL YEL BLUE Unit 24VAC Power Supply Connect Blue First Yellow Lead...

Page 22: ...ower is available at the blue and red leads u Connect one of the yellow leads to the blue lead u Connect the switched output of the Control to the red lead to operate the ERV s isolation relay FIGURE...

Page 23: ...sary 2 Support the impeller subassembly Remove the eight 20 bolts B retaining the impeller subassembly plate to the side rails and front and back tabs 3 Lift the entire impeller subassembly C out of t...

Page 24: ...ation from the desired opening 3 Seal the edges of the cut insulation to prevent erosion of the insulation edges and having debris in the airstream 4 Install the patch pan over the undesired opening 5...

Page 25: ...mer wired for 208 VAC If the unit is receiving 230 VAC make sure the black primary side wire on the transformer s 208 V terminal has been moved to the 230 V terminal 6 2 3 Inspect Filters Clean filter...

Page 26: ...eams are properly balanced IMPORTANT NOTE Make sure clean filters are installed before balancing airflow Dirty or clogged filters reduce airflow through the unit 6 4 BALANCING AIRFLOW Equipment Requir...

Page 27: ...0 1400 1600 Clean filter Pressure Drop in w g Unit Airflow CFM Initial Pressure Drop of MERV 8 Filters supplied with this unit FIGURE 6 4 1 INITIAL PRESSURE DROP OF MERV 8 FILTERS SUPPLIED WITH THIS U...

Page 28: ...TENANCE 24 HRS AFTER START UP 24 hours after unit start up u In new installations check the air filters since they will often collect dust dirt and debris at time of start up 7 2 MAINTENANCE 30 DAYS A...

Page 29: ...aterial that must be kept clean at all times As a minimum cores should be cleaned once per year u DO NOT WASH OR ALLOW THE ENTHALPIC CORES TO GET WET u DO NOT EXPOSE THE ENTHALPIC CORES TO HIGH HEAT O...

Page 30: ...800 627 4499 30 HE Series Indoor ERV MAINTENANCE 7 7 MAINTENANCE RECORDS MAINTENANCE LOG ENTER DATES OF SERVICE OA FILTER CHANGE RA FILTER CHANGE INSPECTION CLEANING CLEAN CORE CLEAN BLOWERS INITIALS...

Page 31: ...you have the information called for in the Unit Information page in the front of this manual The person you speak with at the factory will need that information to properly identify the unit To contac...

Page 32: ...bility derived from innovative design practices expert workmanship and Quick Response Manufacturing QRM As the pioneer of static plate core technology in North America RenewAire is the largest ERV pro...

Reviews: