15
1.800.627.4499
HE-Series Indoor
ERV
UNIT PLACEMENT
3.4 STORAGE
Units that must be stored prior to installation should be left on their pallets and protected from
weather and physical damage. Units must be placed on a level surface to prevent wracking of
the pallet and the HE1.5XIN. All access doors must be secured with all available hardware (door
latches and securing bolts) and all openings into the cabinet must be sealed to prevent entry of
dust, dirt and debris.
4.0 UNIT PLACEMENT
4.1 BEFORE YOU BEGIN
Units that must be stored prior to installation should be left on their pallets and protected from
weather and physical damage. Units must be placed on a level surface to prevent wracking of
the pallet and the HE1.5XIN. All access doors must be secured with all available hardware (door
latches and securing bolts) and all openings into the cabinet must be sealed to prevent entry of
dust, dirt and debris.
The HE1.5XIN is designed for installation in a sheltered location, out of the weather. The
preferred mounting location is to place the unit on a concrete floor, although it can also be
suspended from a ceiling or other structural support. See Section 5.3, Suspended Mount, in this
manual.
For all installations, maintain needed service clearances as shown on the dimensioned drawings
located in Section 4.2 of this manual. In addition, if the optional Bypass Economizer is ordered,
additional clearance will be required for the extra bypass duct. See the
RenewAire Supplemental
Manual for Bypass
or further information and clearance details specific to the HE1.5XIN units.
For all floor-mount installations, the unit should be set on its factory-provided adjustable legs
and leveled. Select a location that is central to the inside duct runs and close to both the
exhaust duct (to the outside) and also to the fresh air duct (from the outside).
The exhaust outlet and the outside air inlet on the outside of the building should be at least 10'
apart to avoid cross-contamination. Comply with all local building codes in the positioning of the
duct openings. Do not position the exhaust air outlet in a location where it will dump exhaust
air into any enclosed or occupied space. The duct inlets and outlets should be screened against
insects and vermin and should be shielded from the weather to prevent entry of rain or snow.
4.2 SERVICE CLEARANCES
48 3/4"
Overall
1 1/8" Typ.
3 1/4"
5" Damper
Frames Typ.
RA
FRONT VIEW
Pressure
Ports (4) Typ.
Door-interlocked
Disconnect Switch
FA
OA
6 3/8" Typ.
52 3/4" Case 32"
6"
LEFT VIEW
Power Wiring
Inlet 7/8" dia.
Control Wiring
Inlet 7/8" dia.
EA Damper
Location
(Optional)
FA Damper
Location
(Optional)
18" X 18"
Duct
Receiving
Flange Typ.
53 5/8" Overall
6 3/8" Typ.
6"
32"
49 3/8"
Minimum Service
Area
20 1/8"Minimum
Service Area
(Doors can be
Removed from Hinges.)
24 1/2"
RIGHT VIEW
18" X 18"
Duct
Receiving
Flange Typ.
Door
Swing
Door
Swing
32 5/8" Case
34 1/2" Overall
42 5/8" Case
TOP VIEW
Patch Pan
(Opening Used
for Alternative
Unit Configurations)
Typ.
EA
Model: HE1.5XINH
Drawing Type: Unit Dimension
Version: MAY18
ABBREVIATIONS
EA: Exhaust Air to outside
OA: Outside Air intake
RA: Room Air to be exhausted
FA: Fresh Air to inside
INSTALLATION ORIENTATION
Unit may be installed in any
orientation.
NOTE
1. UNLESS OTHERWISE SPECIFIED,
DIMENSIONS ARE ROUNDED TO THE
NEAREST EIGHTH OF AN INCH.
2. SPECIFICATIONS MAY BE SUBJECT
TO CHANGE WITHOUT NOTICE.
3. MIN. DUCT CLEARANCE
FROM DAMPER BLADE WHEN FULLY
OPENED TO BE 2". SMACNA RULES
APPLY.
BYPASS AIRFLOW SCHEMATIC
FRONT VIEW
RA
FA
BP
EA
OA
2 7/8"
1 1/4"
3 1/4"
59 1/2" Overall
5" Damper
Frames Typ.
RA
FA
OA
EA
FRONT VIEW
Door-Interlocked
Disconnect Switch
Pressure
Ports (4) Typ.
BP
48 1/2" Overall
45 3/4" Case
6 1/4"
Typ.
4 1/4"
24 5/8"
LEFT VIEW
18" X 18"
Duct Receiving
Flange Typ.
6 1/4"
4 1/4"
6 1/4"
Typ.
24 5/8"
RIGHT VIEW
Control Wiring
Inlet 7/8"
Power Wiring
Inlet 7/8"
16" X 14" Isolation
Damper (Optional)
Acts as Face
Damper for
Bypass Units
49 5/8" Case
12"
11 5/8"
15 1/4"
24 1/2"
20 1/8" Minimum Service Area (Doors can be Removed from Hinges.)
49 1/2" Minimum
Service Area
31 7/8" Case
34 1/2" Overall
TOP VIEW
Door
Swing
Door
Swing
Patch Pan
(Opening Used
for Alternative
Unit Configurations.)
Typ.
Plug Location
12" Bypass
Damper
(Not Shown)
12" Round Bypass Duct Connection
(Direct Mount to Damper, By Others)
Bypass
Damper
Face Damper
FA Damper
Location
(Optional)
Model: HE1.5XINV [Bypass]
Drawing Type: Unit Dimension
Version: MAY18
ABBREVIATIONS
EA: Exhaust Air to outside
OA: Outside Air intake
RA: Room Air to be exhausted
FA: Fresh Air to inside
BP: Bypass Air outlet
INSTALLATION ORIENTATION
Unit may be installed in any
orientation.
NOTE
1. UNLESS OTHERWISE SPECIFIED,
DIMENSIONS ARE ROUNDED TO THE
NEAREST EIGHTH OF AN INCH.
2. SPECIFICATIONS MAY BE SUBJECT
TO CHANGE WITHOUT NOTICE.
3. MIN. DUCT CLEARANCE
FROM DAMPER BLADE WHEN FULLY
OPENED TO BE 2". SMACNA RULES
APPLY.
4. UNITS WITH BYPASS WILL REQUIRE
ADDITIONAL SPACE FOR THE
CONNECTION OF THE BYPASS DUCT
(BY OTHERS).
5. FOR INSTALLATION DETAILS, REFER
TO I&O MANUAL SUPPLEMENT FOR
BYPASS.
FIGURE 4.2.0 HE1.5XINH SERVICE CLEARANCE
FIGURE 4.2.1 HE1.5XINV SERVICE CLEARANCE