background image

23

1.800.627.4499

HE-Series Indoor

ERV

INSTALLATION

5.7 QUICK-START FOR TESTING CORRECT 3PH WIRING

All units that run on 3 phase power should be test-run immediately after high voltage wiring 
connections are made. This will verify that the three phases are properly connected, that the 
dampers will open and close properly and the fans are working properly. 
For purposes of testing correct phase connections, the internal 24 VAC power supply will be 
used to power-up the fans and all external control devices will be disabled, when applicable.

NOTE: Any changes 
to unit low-voltage 
wiring should be 

made with the disconnect 
switch in the OFF position.

5.8 FIELD CONVERSION OF OPENINGS

The HE1.5XIN is designed to allow field conversion of the unit openings. This means the 
motorized impeller sub-assemblies can be moved to an adjacent wall of the unit if that opening 
is preferred. The outlet openings can also be moved to an adjacent wall.
Before you start, plan the duct work layout. Determine which openings are to be converted. 

u

   Turn off the disconnect switch on the unit. Make sure electrical power is shut off to the unit 

and disconnect switch.

u

  Open the access doors to the unit.

 

u

  Remove the core strap, filters, and energy exchanger cores from the unit. 

 
5.7.1 To Field Convert the Inlet Opening
1.  Disconnect motor harness connector (A) by the motor. Move the wire harness out of the way 

if necessary.

2.  Support the impeller subassembly. Remove the eight ¼-20 bolts (B) retaining the impeller 

subassembly plate to the side rails and front and back tabs.

3.  Lift the entire impeller subassembly (C) out of the unit and set aside. Leave the rails in the 

unit.

4.  Remove the patch pan (D) from the desired opening.
5.  Using the exposed sheet metal cutout, cut the insulation from the desired opening.
6.  Seal the edges of the cut insulation to prevent erosion of the insulation edges and having 

debris in the airstream.

7.  Install the patch pan over the undesired opening.
8.  Install the insulation in the undesired opening. Seal the insulation.
9.  Remove the duct flange from the undesired opening and install it at the desired opening.
10.  If both inlet openings are to be converted, repeat Steps 2–9 for the second inlet opening. 
11.  At this point, if there are outlet openings for conversion, you will want to address them 

before proceeding with the inlet opening.

12.  After converting the outlet openings move the unit floor brackets (E), if necessary, so when 

the unit is re-oriented the floor brackets support the unit on the floor.

13.  Rotate the unit to the desired orientation, if necessary.
14.  Install the impeller subassembly into the new inlet opening and fasten with eight ¼-20 bolts 

to retain to the side rails and front and back tabs. Make sure the motor harness connector 
is towards the front of the unit.

15. Connect the motor harness.
16.  Repeat Steps 14–15 for other impeller subassembly if required.
17.  Tidy up any wire harnesses that were moved making sure motor wires are taut and away 

from the impeller blades.

Summary of Contents for HE ERV Series

Page 1: ...HE1 5XINH HE1 5XINV HE SERIES ERV Installation Operation and Maintenance Manual Model HE1 5XINH shown...

Page 2: ...Allow the motor to fully cool to reset the thermal protector you should feel or hear a click when the thermal protector resets while pushing the reset button WARNING ARC FLASH AND ELECTRIC SHOCK HAZA...

Page 3: ...data from the Option Code H 5 1 I E J N Option Code Serial Number SO NOTE This page is to be completed by the installing contractor The completed document is to be turned over to the owner after start...

Page 4: ...ipped loose Backdraft damper OA or EA Digital time clock wall mount TC7D W in exterior enclosure TC7D E Carbon dioxide sensor control wall mount CO2 W duct mount CO2 D IAQ sensor wall mount IAQ W duct...

Page 5: ...tions Typ EA Model HE1 5XINH Drawing Type Unit Dimension Version MAY18 ABBREVIATIONS EA Exhaust Air to outside OA Outside Air intake RA Room Air to be exhausted FA Fresh Air to inside INSTALLATION ORI...

Page 6: ...e Backdraft damper OA or EA Digital time clock wall mount TC7D W in exterior enclosure TC7D E Carbon dioxide sensor control wall mount CO2 W duct mount CO2 D IAQ sensor wall mount IAQ W duct mount IAQ...

Page 7: ...Unit Configurations Typ Model HE1 5XINV Drawing Type Unit Dimension Version MAY18 ABBREVIATIONS EA Exhaust Air to outside OA Outside Air intake RA Room Air to be exhausted FA Fresh Air to inside INST...

Page 8: ...Wire Control Unpowered 21 5 6 2 Control Sending 24 VAC On Signal 21 5 6 3 Control System with two Non Powered Relay Contacts 21 5 6 4 Control System Sending two 24 VAC On Signals from an external powe...

Page 9: ...endent Blower Control 20 Figure 5 6 0 A Switch or Non Powered Control Using Unit s 24 VAC Power Supply 21 Figure 5 6 1 24 VAC from an External Source 21 Figure 5 6 2 Two External Non Powered Relay Con...

Page 10: ...er both Airstreams with no Bypass Digit 24 Paint and Customization E Motorized Damper EA Airstream with no Bypass None F Motorized Damper FA Airstream with no Bypass W White Paint S Backdraft Damper O...

Page 11: ...e HE1 5XRT Installation and Operation Manual These ERVs are commonly installed as part of an air handling system that provides heating and cooling of Supply Air They can also be installed to operate a...

Page 12: ...ic plate enthalpic core The enthalpic cores transfer both latent and sensible energies between the airstreams Gasketing is pre installed on the cores and must be positioned to provide a proper air sea...

Page 13: ...t The hoisting slings must be positioned around the ends of the unit so they do not touch the unit doors Unit hoisting weights and Center of Gravity are detailed in Sections 3 1 and 3 2 in this manual...

Page 14: ...HE1 5XINH_CORNER_WEIGHTS_ AUG19 dwg HE1 5XINH Corner Weights LR RR RF LF UNIT COG RANGE BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 75 HP 365 86 81 96 101 ADDITIONAL WEIGHTS FOR OPTIONS lbs Motors...

Page 15: ...Comply with all local building codes in the positioning of the duct openings Do not position the exhaust air outlet in a location where it will dump exhaust air into any enclosed or occupied space Th...

Page 16: ...INSTALLATION 5 2 FLOOR INSTALLATION Most units are installed in a location specified by others In general it is preferable to install the unit on a flat reasonably level surface such as a concrete fl...

Page 17: ...pt s pour une utilisation avec regulateur de vitesse elec tronique 5 4 1 Electronically Commutated Motors These ERVs may be ordered with factory installed features including Electronically Commutated...

Page 18: ...transformer When it trips the circuit breaker s button pops up Shut off the primary side power to the unit and remove the excessive load or the short The circuit breaker can be reset about fifteen sec...

Page 19: ...BK BK RD BK BK BU RD OR YL YL FIGURE 5 5 0 HE1 5XIN SINGLE PHASE UNIT STANDARD CHANGES NAME REV DATE Description Family Config No Damper RenewAire A B C D E New 0 11 3 2017 austine 1 6 7 2018 austine...

Page 20: ...BL YL FIGURE 5 5 2 HE1 5XIN SINGLE PHASE UNIT WITH INDEPENDENT BLOWER CONTROL CHANGES NAME REV DATE Description Family Config No Damper RenewAire 1 A B C D E New 0 11 3 2017 austine 1 6 7 2018 austine...

Page 21: ...IED 24VAC FROM AN EXTERNAL SOURCE Isolation Relay Coil Image 3 from filename Control Connections EV450 HE1XIN_DEC14 KMC 12 11 14 RED YEL YEL BLUE Unit 24VAC Power Supply Connect Blue First Yellow Lead...

Page 22: ...ower is available at the blue and red leads u Connect one of the yellow leads to the blue lead u Connect the switched output of the Control to the red lead to operate the ERV s isolation relay FIGURE...

Page 23: ...sary 2 Support the impeller subassembly Remove the eight 20 bolts B retaining the impeller subassembly plate to the side rails and front and back tabs 3 Lift the entire impeller subassembly C out of t...

Page 24: ...ation from the desired opening 3 Seal the edges of the cut insulation to prevent erosion of the insulation edges and having debris in the airstream 4 Install the patch pan over the undesired opening 5...

Page 25: ...mer wired for 208 VAC If the unit is receiving 230 VAC make sure the black primary side wire on the transformer s 208 V terminal has been moved to the 230 V terminal 6 2 3 Inspect Filters Clean filter...

Page 26: ...eams are properly balanced IMPORTANT NOTE Make sure clean filters are installed before balancing airflow Dirty or clogged filters reduce airflow through the unit 6 4 BALANCING AIRFLOW Equipment Requir...

Page 27: ...0 1400 1600 Clean filter Pressure Drop in w g Unit Airflow CFM Initial Pressure Drop of MERV 8 Filters supplied with this unit FIGURE 6 4 1 INITIAL PRESSURE DROP OF MERV 8 FILTERS SUPPLIED WITH THIS U...

Page 28: ...TENANCE 24 HRS AFTER START UP 24 hours after unit start up u In new installations check the air filters since they will often collect dust dirt and debris at time of start up 7 2 MAINTENANCE 30 DAYS A...

Page 29: ...aterial that must be kept clean at all times As a minimum cores should be cleaned once per year u DO NOT WASH OR ALLOW THE ENTHALPIC CORES TO GET WET u DO NOT EXPOSE THE ENTHALPIC CORES TO HIGH HEAT O...

Page 30: ...800 627 4499 30 HE Series Indoor ERV MAINTENANCE 7 7 MAINTENANCE RECORDS MAINTENANCE LOG ENTER DATES OF SERVICE OA FILTER CHANGE RA FILTER CHANGE INSPECTION CLEANING CLEAN CORE CLEAN BLOWERS INITIALS...

Page 31: ...you have the information called for in the Unit Information page in the front of this manual The person you speak with at the factory will need that information to properly identify the unit To contac...

Page 32: ...bility derived from innovative design practices expert workmanship and Quick Response Manufacturing QRM As the pioneer of static plate core technology in North America RenewAire is the largest ERV pro...

Reviews: