SPECIFICATIONS & DIMENSIONS
Specifications may be subject to change without notice.
INDOOR UNIT
Duct Mounted or Thru-the-Wall
SPECIFICATIONS
Ventilation Type:
Static plate, heat and humidity transfer
Typical Airflow Range:
40-70 CFM
Standard Features:
Painted cabinet
Line-cord power supply
Built-in control
Unit may be mounted in any orientation
Control:
Built-in proportional runtime control and switched
terminals for furnace/AC interconnect
Filters:
Total qty. 2, MERV 8, spun-polyester media:
7 1/2" x 10 1/2" x 1"
Unit Dimensions & Weight:
29 3/4" L x 19 1/4" W x 10 3/4" H
38 lbs.
Max. Shipping Dimensions & Weight (in carton):
30" L x 22" W x 15" H
50 lbs.
Motor(s):
Qty. 1, Double-shaft standard motor
Accessories:
Backdraft damper 6"
Wall cap 6" - white, brown
Exterior thru-the-wall installation kit
Duct collar kit
UNIT DIMENSIONS
UNIT MOUNTING & APPLICATION
Can be mounted in any orientation. If duct-mounted,
airstreams cannot be switched. If mounted with
exterior Thru-the-wall installation kit, the RA/EA
airstreams are switched with the OA/FA airstreams.
If four ducts are connected using duct collar kit,
airstreams may be switched.
AIRFLOW CONFIGURATION
Available as shown in dimension drawing.
2"
1 1/8"
36" Line Cord
29 5/8" Overall
(with Duct Collars)
25 1/8" Case
2 1/4" Typ.
27 1/8" Overall
CL 6 1/8"
CL 5 5/8"
18 1/8" Case
CL 4 1/2"
1/2"
5/8"
19 1/8" Overall
6" Typ.
8" Typ.
10 5/8" Case
CL 5 1/8"
10 5/8" Overall
18 1/8" Minimum
Service Area
18 1/8" Minimum
Service Area
6"
17 5/8"
Door
Swing
24V AC
Control
Terminal
Proportional
Runtime
Control
EA (TW)
FA (DH)
Cut Hole in Duct
(Minimum Size)
OA (TW)
RA (DH)
TOP VIEW
RIGHT VIEW
FRONT VIEW
LEFT VIEW
OA (TW) RA (DH)
RA (TW)
OA (DH)
EA (TW) FA (DH)
FA (TW)
EA (DH)
Model: BR70
Drawing Type: Unit Dimension
Version: MAR16
ABBREVIATIONS
EA: Exhaust Air to outside
OA: Outside Air intake
RA: Room Air to be exhausted
FA: Fresh Air to inside
TW: Thru Wall
DH: Duct Hung
INSTALLATION ORIENTATION
Unit may be installed in any
orientation.
NOTE
1.UNLESS OTHERWISE SPECIFIED,
DIMENSIONS ARE ROUNDED TO THE
NEAREST EIGHTH OF AN INCH.
2. SPECIFICATIONS MAY BE SUBJECT
TO CHANGE WITHOUT NOTICE.
ELECTRICAL DATA
HP
Volts
HZ
Phase
Input Watts
FLA
0.08
120
60
Single
94 @ 69 CFM
1.0
UNIT PERFORMANCE
CORE PERFORMANCE
Airflow CFM
ESP in H
2
0
Temp EFF%
Total EFF%
Winter/Summer*
46
0.40
80
75/62
59
0.30
77
72/58
73
0.20
75
69/54
86
0.10
72
66/51
* See performance ratings per CSA C439 on page 165 of RenewAire’s Full Line Volume XVIII Catalog.
Note:
Electric Duct Heater and Indirect Gas-Fired Duct Furnace are not available on the BR70.
70
BR
Energy Recovery Ventilator
Standard
Download specification at:
renewaire.com/specifications