RenewAire BR130 SERIES Installation, Operation & Maintenance Manual Download Page 11

ERV

BR70 AND BR130

11

 

1.800.627.4499  

INSTALLATION, OPERATION AND MAINTENANCE MANUAL  

RENEWAIRE.COM 

INSTALLATION INSTRUCTIONS

INSTALLATION

ELECTRICAL CONTROLS

NOTE:

 Proper Wiring Size Selection and Wiring Installation Is the Responsibility of the Electrical Contractor.

NOTE:

 Electrostatic discharge (static electricity) may have an adverse effect on the control board. Use 

proper grounding techniques when handling the control board.

Automatic Proportional Runtime Control 

All installations include a Primary Operating Control on the unit to ensure appropriate operation of 
the system. The control terminal on the unit must be connected to the furnace/air conditioner and/or 
thermostat only for proper operation. The thermostat and furnace/air conditioner control circuit must be 
Class II circuits. See Figure F7 for a wiring diagram.

DANGER OF ELECTRICAL SHOCK WHEN SERVICING AN INSTALLED UNIT. 

ALWAYS DISCONNECT POWER SOURCE BEFORE WIRING OR SERVICING.

WARNING

F7

Wiring Diagram

This connection required when 
a central air conditioner is or 
will be part of the system.

Summary of Contents for BR130 SERIES

Page 1: ...INSTALLATION OPERATION MAINTENANCE MANUAL ENERGY RECOVERY VENTILATOR BR70 BR130 RENEWAIRE COM MODEL BR70 MODEL BR130...

Page 2: ...2 13 Maintenance 14 15 TABLE OF CONTENTS There is no known safe level of cigarette smoke Any ventilation system may provide noticeable improvement in spaces where cigarettes are smoked but it cannot b...

Page 3: ...ps 1 3 Exhaust Air Transfer Ratio 1 6 0 2 in wg 50 PA and 1 6 0 4 in wg 100 Pa BR130 Ventilation Performance Ext Static Pressure Net Supply Airflow Gross Airflow Supply Exhaust Pa in wg L S CFM L S CF...

Page 4: ...as shown in dimension drawing 2 1 1 8 36 Line Cord 29 5 8 Overall with Duct Collars 25 1 8 Case 2 1 4 Typ 27 1 8 Overall C L 6 1 8 C L 5 5 8 18 1 8 Case C L 4 1 2 1 2 5 8 19 1 8 Overall 6 Typ 8 Typ 1...

Page 5: ...ion drawing 30 7 8 Overall 33 1 4 Overall with Duct Collars 28 7 8 Case 20 3 8 2 1 8 5 3 4 1 1 8 EA TW FA DH OA TW RA DH Cut Hole in Duct Minimum Size 36 Line Cord 2 1 4 Typ C L 4 5 8 C L 6 1 8 FA TW...

Page 6: ...ith velocities not exceeding 750 fpm at the point in the return air duct where the BR unit is attached An alternate field measurement would be to locate the BR unit where the static pressure measureme...

Page 7: ...rigid un insulated wall mounted units only Ducts from unit to house in unconditioned spaces All ducts from unit to house in unconditioned spaces like attics and crawl spaces must be insulated DUCT SI...

Page 8: ...gh the flue chimney of fuel burning equipment that might be installed in the area affected by this equipment If this unit is exhausting air from a space in which chimney vented fuel burning equipment...

Page 9: ...gure F6 The interior plate is attached to the interior of the wall Using the holes in the plate as a reference cut 6 holes to the outside allowing for a downward tilt to the outside of for 12 of duct...

Page 10: ...ors are generated stale air returns which pick up stale household air to be exhausted should be located in bathrooms and the kitchen A central location such as a hallway is also acceptable but won t c...

Page 11: ...tomatic Proportional Runtime Control All installations include a Primary Operating Control on the unit to ensure appropriate operation of the system The control terminal on the unit must be connected...

Page 12: ...n also be used to determine when filters should be cleaned or changed Use Static Taps to Measure Aiflow Rates See Cross Core Static Drop in MEASURING AIRFLOW table on page 13 Use Damper to Balance Air...

Page 13: ...SCFM of Room Air RA install the high pressure side of your measuring device to the Room Air RA port and the low pressure side to the Exhaust Air EA port If gauge drops below zero reverse tubing connec...

Page 14: ...ERV BR70 AND BR130 RENEWAIRE COM INSTALLATION OPERATION AND MAINTENANCE MANUAL 1 800 627 4499 14 MAINTENANCE SERVICE PARTS BR Units BR70 shown www renewaire com 800 627 4499 support renewaire com...

Page 15: ...mes The primary contact for replacement filters for your RenewAire unit is the installing contractor As an alternative you may wish to produce your own filters following these instructions Filters may...

Page 16: ...8 UNMATCHED VENTILATION SUPPORT As much as our unsurpassed quality and performance our customers can also depend on our professional support staff for swift professional assistance with all their tech...

Reviews: