RenewAire BR130 SERIES Installation, Operation & Maintenance Manual Download Page 10

ERV

BR70 AND BR130

RENEWAIRE.COM  

INSTALLATION, OPERATION AND MAINTENANCE MANUAL  

1.800.627.4499

10

INSTALLATION

INSTALLING OUTSIDE AIR AND EXHAUST AIR DUCTS

For duct hung applications, the exhaust outlet and fresh air inlet on the outside of the building should be 
at least ten feet apart to avoid cross-contamination. Keep the length of the two flexible ducts roughly 
equal and as short and straight as possible. Normally, six inch insulated flexible duct is used. Band or tape 
inner duct liner to inner flange of appropriate collar. Drive a sheet metal screw through liner to secure duct 
spiral wire to collar. Straighten insulation, and slide outer duct jacket onto the outer flange of the duct 
collar. Secure with band or tape.

If duct runs are exceedingly long (over 10 feet of flex duct for 130 CFM) or have excessive bends or 
elbows or if maximum air flow rates are required, eight inch insulated flexible duct should be used. The 
outer flange of the duct collar can be used for both the inner and outer jacket of the flexible duct. Care 
must be taken to ensure that the duct is securely fastened and sealed to the duct collar. Ducts connecting 
the unit to the outside must be insulated with sealed vapor barrier on both inside and outside of the 
insulation.

The inlets and outlets should be screened against insects and vermin and shielded from the weather to 
prevent the entry of rain or snow. The exhaust outlet should not dump air into an enclosed space or into 
any other structure.

INSTALLATION INSTRUCTIONS

INSIDE DUCTWORK SYSTEM (FOR WALL MOUNTED UNITS ONLY)

Collect Stale Air from the House 

Locate stale air return grilles (RA) in rooms where moisture and odors are generated: stale air returns 
(which pick up stale household air to be exhausted) should be located in bathrooms and the kitchen. A 
central location such as a hallway is also acceptable but won't clear humidity and odors from baths and 
kitchens as rapidly.

Connect Fresh Air from the Unit to the House 

Use a five foot section of flexible insulated duct to connect the unit to the return air duct at the port 
labeled Fresh Air (FA). Note that the flex duct is not required for the room air connection (RA). This will cut 
noise transmitted from the unit. Stretch the flex duct tightly in order to maintain good airflow.

For houses with forced-air heating and cooling systems

 

Most units are installed with the fresh air duct connected directly to a return duct for the main heating 
and cooling system. Be careful to connect the fresh air duct at least three feet from the return plenum to 
minimize suction from the furnace blower. A connection closer to the furnace may result in unbalanced 
flow and associated problems.

For houses without ducted heating or cooling systems

 

In most houses one or two fresh air grilles in a central part of the house provide effective distribution of 
the fresh air into the home, particularly when the stale exhaust air is picked up at several points. Because 
the fresh air is usually somewhat cooler than the household air, the fresh air supply grilles should be 
located in a traffic area like a hallway or stairway rather than in a sitting area.

CAUTION

INSTALL FRESH AIR INLET 
AWAY FROM SOURCES OF 

CONTAMINANTS.

•  Do not locate the fresh air 

inlet where vehicles may be 
serviced or left idling.

•  The fresh air inlet should be at 

least ten feet away from any 
exhaust such as dryer vents, 
chimneys, furnace, and water 
heater exhausts or other 
sources of contamination or 
carbon monoxide. 

•  Never locate the fresh air inlet 

inside a structure.

Summary of Contents for BR130 SERIES

Page 1: ...INSTALLATION OPERATION MAINTENANCE MANUAL ENERGY RECOVERY VENTILATOR BR70 BR130 RENEWAIRE COM MODEL BR70 MODEL BR130...

Page 2: ...2 13 Maintenance 14 15 TABLE OF CONTENTS There is no known safe level of cigarette smoke Any ventilation system may provide noticeable improvement in spaces where cigarettes are smoked but it cannot b...

Page 3: ...ps 1 3 Exhaust Air Transfer Ratio 1 6 0 2 in wg 50 PA and 1 6 0 4 in wg 100 Pa BR130 Ventilation Performance Ext Static Pressure Net Supply Airflow Gross Airflow Supply Exhaust Pa in wg L S CFM L S CF...

Page 4: ...as shown in dimension drawing 2 1 1 8 36 Line Cord 29 5 8 Overall with Duct Collars 25 1 8 Case 2 1 4 Typ 27 1 8 Overall C L 6 1 8 C L 5 5 8 18 1 8 Case C L 4 1 2 1 2 5 8 19 1 8 Overall 6 Typ 8 Typ 1...

Page 5: ...ion drawing 30 7 8 Overall 33 1 4 Overall with Duct Collars 28 7 8 Case 20 3 8 2 1 8 5 3 4 1 1 8 EA TW FA DH OA TW RA DH Cut Hole in Duct Minimum Size 36 Line Cord 2 1 4 Typ C L 4 5 8 C L 6 1 8 FA TW...

Page 6: ...ith velocities not exceeding 750 fpm at the point in the return air duct where the BR unit is attached An alternate field measurement would be to locate the BR unit where the static pressure measureme...

Page 7: ...rigid un insulated wall mounted units only Ducts from unit to house in unconditioned spaces All ducts from unit to house in unconditioned spaces like attics and crawl spaces must be insulated DUCT SI...

Page 8: ...gh the flue chimney of fuel burning equipment that might be installed in the area affected by this equipment If this unit is exhausting air from a space in which chimney vented fuel burning equipment...

Page 9: ...gure F6 The interior plate is attached to the interior of the wall Using the holes in the plate as a reference cut 6 holes to the outside allowing for a downward tilt to the outside of for 12 of duct...

Page 10: ...ors are generated stale air returns which pick up stale household air to be exhausted should be located in bathrooms and the kitchen A central location such as a hallway is also acceptable but won t c...

Page 11: ...tomatic Proportional Runtime Control All installations include a Primary Operating Control on the unit to ensure appropriate operation of the system The control terminal on the unit must be connected...

Page 12: ...n also be used to determine when filters should be cleaned or changed Use Static Taps to Measure Aiflow Rates See Cross Core Static Drop in MEASURING AIRFLOW table on page 13 Use Damper to Balance Air...

Page 13: ...SCFM of Room Air RA install the high pressure side of your measuring device to the Room Air RA port and the low pressure side to the Exhaust Air EA port If gauge drops below zero reverse tubing connec...

Page 14: ...ERV BR70 AND BR130 RENEWAIRE COM INSTALLATION OPERATION AND MAINTENANCE MANUAL 1 800 627 4499 14 MAINTENANCE SERVICE PARTS BR Units BR70 shown www renewaire com 800 627 4499 support renewaire com...

Page 15: ...mes The primary contact for replacement filters for your RenewAire unit is the installing contractor As an alternative you may wish to produce your own filters following these instructions Filters may...

Page 16: ...8 UNMATCHED VENTILATION SUPPORT As much as our unsurpassed quality and performance our customers can also depend on our professional support staff for swift professional assistance with all their tech...

Reviews: