Malfunction Possible cause
Checks
Remedial measures
Major
F032
Fan motor 1 defective
Check:
- Fan motor operation
- Fan motor current draw
- Replace the fan motor.
X
E081
Communication fault between
motherboard and fan speed
controller
Check:
- Connections between
motherboard and fan speed
controller
- Replace fan speed controller
- Replace motherboard
Temperature
[°C]
Resistance
(k
Ω
)
-30
63.73
-29
60.32
-28
57.12
-27
57.12
-26
51.27
-25
48.60
-24
46.09
-23
43.72
-22
41.49
-21
39.38
-20
37.40
-19
35.53
-18
33.76
-17
32.09
-16
30.52
-15
29.03
-14
27.62
-13
26.29
-12
25.03
-11
23.84
-10
22.72
-9
21.65
-8
20.64
-7
19.68
-6
18.77
Resistance table
Temperature
[°C]
Resistance
(k
Ω
)
-5
17.91
-4
17.10
-3
16.32
-2
15.59
-1
14.89
0
14.23
1
13.60
2
13.01
3
12.44
4
11.90
5
11.39
6
10.90
7
10.44
8
10.00
9
9.58
10
9.18
11
8.80
12
8.44
13
8.09
14
7.76
15
7.45
16
7.15
17
6.87
18
6.59
19
6.33
Temperature
[°C]
Resistance
(k
Ω
)
20
6.09
21
5.85
22
5.62
23
5.40
24
5.20
25
5.00
26
4.81
27
4.63
28
4.46
29
4.29
30
4.13
31
3.98
32
3.83
33
3.70
34
3.56
35
3.43
36
3.31
37
3.19
38
3.08
39
2.97
40
2.97
41
2.77
42
2.67
43
2.58
44
2.49
The resistance values for the probes: AT (ambient), CT (register), SUT (suction gas), OT (medium outlet), IT
(medium inlet) are shown in the following table.
The ET (compressor outlet) probe is an NTC 50.