Care and maintenance
Shutdown
Temporary shutdown
1.
Shut down the cold water
consumers connected
to the system.
2. Switch the unit off via
the internal controller in
the chiller (or using the remote
control).
3. Check the percentage
concentration of glycol.
4. Check the unit for visible signs
of damage and clean it as
described in the "Care and
maintenance" chapter.
5. As much as possible, cover
the unit with a plastic foil
to protect it against the
weather.
Permanent shutdown
Ensure that units and components
are disposed of in accordance with
local regulations, e.g. through
authorised disposal and recycling
specialists or at collection points.
REMKO GmbH & Co. KG or your
contractual partner will be pleased
to provide a list of certified firms
in your area.
Regular care and observation
of some basic points will ensure
trouble-free operation and a long
service life.
Wearing appropriate
protective clothing is necessary
when working on the units.
Care
■
Ensure the unit is protected
against dirt, mould and other
deposits.
■
Clean the unit using a damp
cloth.
Do not use a jet of water.
■
Do not use any caustic, abrasive
or solvent-based cleaning
products.
■
Clean the fins on the unit prior
to long shutdown periods.
Maintenance/leak testing
■
We recommend that you take
out a maintenance contract
with an annual service from
an appropriate specialist firm.
■
The legally stipulated
maintenance intervals are
defined in EC ordinance no.
517/2014 of the European
Council.
Type of task
Checks / Maintenance/Inspection
Commis
-
sioning
Monthly
Half-yearly
Yearly
General
•
Clean dirt traps
•
•
Check medium filling
•
•
Check circulation pump
•
•
Dirt/damage condenser
•
•
Check quality of the glycol
•
•
Measure voltage and current
•
•
Check direction of rotation
•
•
Check compressor
•
•
Check fan
•
•
Check the refrigerant volume
•
•
Check condensate drainage
•
•
Check insulation
•
•
Sealing test for cooling cycle
•
•
1)
Statutory regulations require
a leak test for the cooling cycle
dependent on the GWP value.
Inspection and documentation
of the work performed is
to be carried out by specialist
technicians.
NOTE
1) see note
!
CAUTION
If only water and not a
mixture of water and glycol
is used, in regions subject
to freezing, water must be
drained from components
when these are at standstill.
The drained water volume
must be replaced when
components are put back into
operation!
CAUTION
!
Prior to performing any work,
ensure that the equipment
is isolated from the power
supply and secured to prevent
accidental switch-on!
CAUTION
!
REMKO series RVS
26