Regular care and observation
of some basic points will ensure
trouble-free operation and a long
service life.
Care and maintenance
Prior to performing any
work, ensure the equipment
is isolated from the voltage
supply and secured to prevent
accidental switch-on!
CAUTION
Temporary Shutdown
1. Allow the indoor unit to run for
2 to 3 hours in air circulation
mode or in cooling mode at the
maximum temperature setting
in order to remove any residual
moisture from the unit.
2. Shut down the system using
the remote control.
3. Switch off the voltage supply
to the unit.
4. Check the unit for visible signs
of damage and clean it as
described in the chapter "Care
and maintenance".
Permanent Shutdown
Ensure that equipment and
components are disposed of
accordance with local regulations,
e.g. through authorised disposal
and recycling specialists or at
collection points.
Contact REMKO GmbH & Co. KG
or your contract partner for a list
of specialist companies near you.
Shutdown
Care
■
Ensure the unit is protected
against dirt, mould and other
deposits.
■
Clean the indoor and outdoor
unit using a damp cloth. Do
not use any caustic, abrasive
or solvent-based cleaning
products. Do not use a jet of
water.
■
Clean the fins on the unit prior
to long shutdown periods.
Maintenance
■
It is recommended that
maintenance contract with
annual maintenance interval
with an appropriate specialist
company.
This ensures the operational
reliability of your equipment!
TIP
Type of task
Checks/Maintenance/Inspections
Commissioning
Monthly
Six-monthly
Yearly
General
•
•
Measure voltage and current
•
•
Check compressor/fans are functioning correctly
•
•
Check fan is functioning correctly
•
•
Dirt on liquefier/vaporiser
•
•
Check refrigerant fill quantity
•
•
Check condensation drain
•
•
Test insulation
•
•
Check moving parts
•
•
Sealing test for refrigerant circuit
•
•
1)
The statutory regulations
require an annual sealing
test for the refrigerant circuit
in relation to the refrigerant
filling level. The inspection
and documentation is to be
carried out by corresponding
specialist engineers.
NOTE