HEATING
MODE
Heating mode operational sequence
> 6 Min.
> 3 Min.
> 6 Min.
30 sec.
30 sec.
Nominal tempe5 °C
Nominal tempe2 °C
Fan operation IT
Fan operation AT
Compressor operation AT
Actual
temperature
Stop Heating mode
Heating mode
Start Heating mode
Functional diagram
Operation
Stop
Reverse flow valve
30 sec.
30 sec.
During the defrosting cycle, the indoor unit vaporiser fan and the
outdoor unit liquefier fan are switched off.
After the cycle is concluded, the fans are switched to their previous
settings.
< 7 Min.
Defrost period
15 sec.
60 sec.
Fan operation IT
Fan operation AT
Compressor operation AT
Operation
Stop
Reverse flow valve
30 sec.
30 sec.
30 sec.
3 Min.
▲
▼
OR
Hr.
ON TIMER
Hr.
Off TIMER
SET TEMP
Turbo
Hr.
ON TIMER
Hr.
Off TIMER
Turbo
SET TEMP
MODE
Hr.
ON TIMER
Hr.
Off TIMER
Turbo
SET TEMP
Hr.
ON TIMER
Hr.
Off TIMER
SET TEMP
Auto
Turbo
In the heating mode, you can simultaneously heat all of the rooms in
spring or fall. The desired room temperature is set with the
▲
/
▼
buttons
in 1 °C increments. If the room temperature is 1 °C below the selected
target temperature, the indoor unit starts to heat the air in the room.
The inverter controller checks the difference between the adjusted target
temperature and the actual room temperature.
In the event of a greater difference, a higher cooling performance is
created.
In the event of a smaller difference, a lower cooling performance is
created.
This serves to maintain the air discharge temperature and the room
temperature.
If the set room temperature is exceeded by approx. 2 °C, then the
control system turns the heating function off. To protect the compressor,
the regulation only turns the heater on again after a waiting period of
3 minutes.
In heating mode, the indoor unit fan motor is switched on after a delay,
in order to prevent the discharge of cold air.
The fins on the outdoor unit could crack at low outdoor temperatures.
Regular reversal of the cooling circuit results in a defrosting action. The
display shows "H1" during the defrosting period.
HEATING Mode
Hr.
ON TIMER
Hr.
Off TIMER
SET TEMP
Turbo
FAN
Heating mode has priority!
If an indoor unit switches
over to heating mode, then
cooling is switched off for the
other indoor devices in cooling
mode.
Cooling is not possible during
heating operation.
CAUTION
REMKO MXW
12