background image

IM 812 / Page 23 of 28

1.

Indoor and outdoor fans will not operate in cool
mode.

2.

Indoor fan operates on cool but compressor
does not start.

3.

Indoor fan runs on cool and compressor starts
but stops after a short interval.

4.

Indoor and outdoor fans run on cool and com-
pressor starts and runs, but compressor occa-
sionally stops (on overload device).

5.

Compressor starts and runs on cool but
indoor or outdoor fan does not run.

6.

Equipment gives electrical shock.

7.

Dip switch function does not work.

8.

Insufficient cooling capacity.
(Continues on page 22)

a.

No power to unit.

b.

Faulty control pad or control box PC boards.

c.

Loose connections to control pad or control box
PC board.

a.

Temperature setting too high.

b.

Low voltage.

c.

Faulty control pad or control box PC boards.

d.

Loose wire connections to control pad or control
box PC board.

e.

Defective compressor overload.

f.

Loose connections at compressor terminals.

g.

Wiring to compressor terminals defective.

h.

Loose connections in compressor overload
device.

i.

Starting capacitor malfunctions.

j.

Defective compressor.

k.

Built in time delay

a.

Compressor overload is activated due to over-
loading.

a.

Low voltage due to overload circuits within build-
ing or throughout the local power system. Due
to varying power demands, this condition might
exist only at certain times during the day or on
very hot days.

b.

High voltage due to fluctuations in local power
system; usually occurs during low load periods
of the day.

c.

Partial short circuit in compressor motor. Under
normal loading a compressor with a partial short
circuit might appear to be operating all right;
increased condensing air temperature might
then cause a short.

a.

Faulty control pad or control box PC boards.

b.

Open circuited blower motor.

c.

Blower rubbing against its housing.

d.

Bearings on blower motor seized.

e.

Loose wiring connection.

a.

Grounded electrical circuit.

a.

Function has not been activated by momentary
loss of power.

b.

Dip switch did not connect

c.

Built-in time delays

a.

Equipment standing too long without being run.

b.

Insufficient airflow through condenser due to:

1) Dirty condenser.
2) Obstructed outdoor louver.
3) Condenser fan not running.

4) Condenser fan not up to speed.

5) Condenser fan slipping on motor shaft.
6) Recirculation of condenser air.

a.

Check supply line fusses, circuit breakers, and
be sure the power is on. Blown fuses would
indicate circuit overloading, a short circuit or
a grounded condition in the circuit. Voltage
supply to the equipment should be checked.
Voltage under load must be within 5% of
voltage given on date plate.

b.

Replace.

c

Tighten.

a.

Lower the setting.

b.

Must be within 5% of data plate rating.

c.

Replace.

d.

Tighten.

e.

Replace.

f.

Tighten.

g.

Replace.

h.

Tighten.

i.

Replace.

j.

Replace.

k.

Wait up to 4 minutes

a.

Check voltage supply. Clean outdoor coil inside
and out. Check for recirculation of condenser
air. Put air “splitters” in, if missing. Check com-
pressor for short circuit. If defective, replace.

a.

Run separate electric line to equipment. Con-
sult local power company.

b.

Consult local power company.

c.

Replace compressor.

a.

Replace.

b.

Replace.

c.

Adjust blower motor or blower wheel position.

d.

Replace blower motor.

e.

Tighten.

a.

Repair and check equipment ground.

a.

Unplug the power cord then plug it back in.

b.

Slide it back and forth to make sure it has
mechanically switched.

c.

There are time delays built-in to the control to
prevent overlap of functions. Wait up to 4
minutes.

a.

If the air conditioner is allowed to stand for an
extended length of time without being run on
cool, it is possible for all the refrigerant to be-
come absorbed in the oil inside the compressor
and refrigeration circuit. If this should happen
there will be no cooling until the necessary work-
ing pressures have been established. This will
take about 5 minutes of continuous running.

b.

1) Clean.
2) Remove obstructions.
3) Check same as in the case of malfunctioning

condenser air blower.

4) Check for correct voltage. Replace motor

if necessary.

5) Adjust fan position and tighten setscrews.
6) Make corrections.

Trouble

Possible Causes

Treatment

Troubleshooting Chart

Troubleshooting can present hazards of electricity, rotating parts, sharp edges and weight. Troubleshooting must be done by trained,
experienced technicians only. Improper troubleshooting can result in equipment damage, severe personal injury or death.

WARNING

!

Summary of Contents for IM 812-2

Page 1: ...Installation Maintenance Data IM 812 2 Group PTAC PTHP Date April 2006 McQuay Remington Packaged Terminal Air Conditioners and Heat Pumps C Vintage 2006 McQuay International...

Page 2: ...2 Wall Sleeve 3 Outdoor Louver 4 Subbase Optional for 208V and 230V units but manda tory for all 265V 5 Separate plug in power cord selects heater size NOTE Some units with fixed heaters are also avai...

Page 3: ...nal kW 30A Electric Heater7 Z 5 0 Nominal kW 20A 265V Electric Heater8 C Chassis Mounted Control9 W Wall Mounted Control10 Notes 1 All chassis ship with an Installation Manual and mounting screws 2 Fa...

Page 4: ...on the indoor fan will operate continuously When dip switch 8 is in the ON position the indoor fan will cycle on and off with the compressor or heater In cycle fan dip switch 8 ON the fan will start e...

Page 5: ...y using a G11 hand held remote con troller available from your sales representative Programming P1 using the G11 control press and hold the upper button for 3 seconds until P1 starts flashing on the G...

Page 6: ...e used to provide support over each opening The rough opening should measure 161 4 high x 421 4 wide see Figure 2 Note 2 When a subbase is used the opening must start 31 4 or 41 4 above the finished f...

Page 7: ...n using the outdoor drain kit the sleeve must be flush or beyond the outside finished wall do not recess Install the outdoor drain kit as follows 1 Assemble the drain kit as shown in Figure 4 2 Choose...

Page 8: ...60 from where it exits the conditioner Do not use extension cords When a subbase is not used the receptacle is generally mounted beneath the conditioner or on the wall beside it 208 230V only An elect...

Page 9: ...subbase or from other field supplied materials or it can be floor mounted for 208 230V Install as follows 1 Clean the opening of all debris that may interfere with installation 2 If the unit is to be...

Page 10: ...lace a thin pad of mastic on bottom of the opening and slide in the wall sleeve Be sure to recess the wall sleeve enough to accommodate outside louvers This recess is 3 8 for stamped louvers and 11 8...

Page 11: ...optional drain kit is to be employed heat pumps only refer to page 7 before proceeding 4 If wall thickness exceeds dimensions shown in Table 1 a wall sleeve extension must be used Install the extensio...

Page 12: ...the caulking does not block the weep holes 3 Attach indoor drain kit if used according to the instruc tions on page 7 Outdoor drain kits are not designed to be used with sleeve extensions Louver Fram...

Page 13: ...blade design that will not cause recir culation of condenser air Free area is defined by ASHRAE as the minimum area of the openings in an air inlet or outlet through which air can pass Have your local...

Page 14: ...the room The chassis weighs approximately 150 lbs Use blocking and lifting devices Do not raise over any body parts 1 Remove the shipping carton and inspect for any shipping damage Report any found t...

Page 15: ...located at the lower left end of the chassis See Figure 15 Note Remove shipping screw from door if it needs to be opened 4 If the conditioner will use the standard control pad continue to step 5 If a...

Page 16: ...the room and close the door Wait 6 minutes then re enter the room The unit should now show mode and temperature pro grammed for P1 Remove the short from the T SHRT prongs to restore the normal 15 minu...

Page 17: ...emoval Also see pages 5 and 8 2 If a subbase is used under the unit wall sleeve a small hole may be drilled and grommeted in the subbase front to allow passage of the low voltage wires 3 When using a...

Page 18: ...Disconnect all electric power including remote disconnects before servicing Failure to discon nect power before servicing can cause severe personal injury or death Use copper conductors only Unit term...

Page 19: ...age Disconnect all electric power including remote disconnects before servicing Failure to discon nect power before servicing can cause severe personal injury or death Use copper conductors only Unit...

Page 20: ...Voltage Disconnect all electric power including remote disconnects before servicing Failure to discon nect power before servicing can cause severe personal injury or death Use copper conductors only U...

Page 21: ...rce 2 Remove the front panel and clean it 3 Remove the chassis from the wall sleeve and move it to the maintenance department Replace it with spare chassis or weather plate 4 Check all seals and insul...

Page 22: ...and the temperature of the conditioned space is 80o F Figure 20 Refrigeration Cycle 80o F Room Air to Evaporator 45o F R22 Liquid and Gas to Evaporator Capillary Restrictor 120o F Condenser Air to Out...

Page 23: ...h condenser due to 1 Dirty condenser 2 Obstructed outdoor louver 3 Condenser fan not running 4 Condenser fan not up to speed 5 Condenser fan slipping on motor shaft 6 Recirculation of condenser air a...

Page 24: ...air flow 3 Clean or replace 4 Remove obstructions 5 Check motor 6 Check for correct voltage 7 Adjust blower wheel position and tighten set screw d Refer to original load calculations recalculate heat...

Page 25: ...Loose plug connec tion defective control pad or PC board a Replace b Replace c Replace d Clean coils fans or filters Replace fan motor Check baffles in sleeve extension Check free area of louver Repla...

Page 26: ......

Page 27: ......

Page 28: ...visit us at www mcquay com and click on training or call 540 248 9646 and ask for the Training Department Warranty All McQuay equipment is sold pursuant to its standard terms and conditions of sale i...

Reviews: