Maintenance (Continued)

3. Allow the heater to attempt ignition for 3-5 seconds, during

which time you may hear a loud "grinding" or vibration sound.

4. If your heater has not ignited, re-start the ignition sequence.

Once the heater has ignited, turn the Air Vent Screw clockwise
until fully hand-tightened.  See Figure 15.  

Any air trapped in the fuel pump will have been purged.
5. Your heater is now ready for operation.
6. Re-fill your heater with fuel before it runs out.  This will prevent

the fuel lines and fuel pump from drawing in air and having to
go through the air bleeding procedure again.

Page 11

NEVER LEAVE HEATER 

UNATTENDED WHILE BURN-

ING OR WHILE CONNECTED

TO A POWER SOURCE

Kerosene

Forced Air Heaters

Figure 15 – Tightening Air Vent Screw

Wiring Diagram

©2014 Pinnacle Products International, Inc.  Kerosene Heater User’s Manual

Summary of Contents for HH-400T-KFA

Page 1: ...de poisoning can result Only persons who can follow and understand these instructions should use or service this heater If you need heater information such as an instruction manual labels etcetera con...

Page 2: ...such as headaches dizziness and or nausea If you have these symptoms your heater may not be working properly Get fresh air at once Have the heater serviced Some people are more affected by carbon mon...

Page 3: ...ities having jurisdiction Never use this heater in living or sleeping areas NEVER use this heater where flammable vapors may be present Risk of electric shock Use only the electrical power voltage and...

Page 4: ...ng Remove the heater and all of the packaging materials from the shipping carton NOTE Save the box and packaging materials for future storage Check the chart below to be sure that you have all of the...

Page 5: ...1 Slide axle through wheel support frame Install wheel bushings flat washers S and wheel on axle NOTE When installing wheels tube valve should face out from support frame Figure 5 2 Place flat washers...

Page 6: ...ignites the fuel and air mixture The Air System The heavy duty motor turns a fan that forces air into and around the combus tion chamber Here the air is heated and then forced out the front of the hea...

Page 7: ...ater while heater is running Heater must go through cooling cycle The cooling cycle cools the combustion chamber Damage to heater can occur if combustion chamber is not cooled Do not restart heater un...

Page 8: ...ell See air intake filter Use Allen wrench to loosen set screw which holds fan blade to motor shaft Slip fan blade off motor shaft Clean fan blade using soft cloth moistened with kerosene or solvent D...

Page 9: ...k plug wire to spark plug Reinstall upper shell PHOTOCELL CLEAN PHOTOCELL ANNUALLY OR AS NEEDED Remove upper shell Remove fan See fan blades Remove photocell from its mounting bracket Clean photocell...

Page 10: ...se unsafe operating conditions 8 Stop heater See OPERATION page 7 9 If accessory pressure gauge is being used remove pressure gauge 10 Replace pressure gauge and plug in end of filter cover NOTE If he...

Page 11: ...ny air trapped in the fuel pump will have been purged 5 Your heater is now ready for operation 6 Re fill your heater with fuel before it runs out This will prevent the fuel lines and fuel pump from dr...

Page 12: ...UNATTENDED WHILE BURN ING OR WHILE CONNECTED TO A POWER SOURCE Kerosene Forced Air Heaters Figure 16 Repair Parts Illustration for Portable Oil Fired Heater 2014 Pinnacle Products International Inc Ke...

Page 13: ...0107 2 24 Wheel Bushing 70 041 0109 2 25 Flat Washer A 70 041 0105 2 26 Wheel Cap 70 041 1111 2 27 Fan Guard 70 016 0300 1 28 Left Side Cover 1 29 Socket Cover 70 030 0100 1 30 Electrical Outlet Assem...

Page 14: ...tween motor and Main PCB assembly 1 See Pump Pressure Adjustment Page 10 2 See Fuel Filter Page 10 3 See Nozzle Page 8 4 Clean Photocell Lens Page 9 5 Make sure photocell boot is properly seated in br...

Page 15: ...extending beyond heater Low heat output 2 Power Failure No power supply to heater A Check limit control thermostat B Check sensor connection Wait until unit cools down 1 Poor Combustion Align the red...

Page 16: ...item freight pre paid If Pinnacle Products International Inc finds the item to be in normal operating condition or not defective the item will be returned freight collect This Limited Warranty is in l...

Reviews: