19
06/02/06 - 300005247-001-B
Remeha Gas 460 S
Maintenance
1 Checking and cleaning the main components
1.1
Cleaning heater body
The extent of clogging on the heating body must be checked once a
year.
If it is necessary to sweep the boiler, remove the burner drawer to
prevent deposits and soot blocking the orifices in the gas trains.
With the burner out:
- Remove the upper casing of the boiler
- Take out the insulation
- Remove the sweeping hatch from the draught diverter
- If necessary, clean the boiler body using the special brush
provided
- Clean the combustion chamber using a vacuum cleaner
835
022
8N