12
Remeha Gas 460 S
06/02/06 - 300005247-001-B
3 Changing the burner injectors
- Close the gas valve.
- Lift out the injector with a number 12 spanner assemble the new
injectors with their new joint.
First tighten the injectors by hand and carefully lock them using
a spanner.
- Carry out a leak tightness check.
Natural gas H
Natural gas L
Nozzle marking
390A
450A
Nozzle diameter
3.9 mm
4.5 mm