11
06/02/06 - 300005247-001-B
Remeha Gas 460 S
Adapting to another gas
These actions must be carried out by a qualified
technician.
Belgium: The operations required to switch from one gas
to another must be carried out by a SERV'elite technician.
1 Changing gas
The boilers are factory-set to operate on natural gas H (G20 - 20
mbar). To convert it to natural gas L, use the gas L conversion kit
(optional). Carry out the operations described below.
2 Changing the ignition burner injector
Operations to be carried out to convert from natural gas H to natural
gas L and vice versa:
Remove the gas supply pipe from the ignition burner (13 mm
spanner).
Remove the seal.
Unscrew the nozzle using a screwdriver and screw in the new
injector.
- Reassemble the parts
- Carry out a leak tightness check
Natural gas H
Natural gas L
Nozzle marking
80
100
Nozzle diameter
0.80 mm
1.00 mm