Code
Description
Range
160
200
250
300
AP079
Inertia of the building used for heat
up speed
0 - 255
0
0
0
0
AP080
Outside temperature below which
the antifreeze protection is activated
-32 °C - 10 °C
0
0
0
0
AP110
Parameter to activate the 2nd return
sensor
0 = Inactive
1 = Active
0
0
0
0
CP000
Maximum Flow Temperature
setpoint zone
0 °C - 90 °C
90
90
90
90
CP010
Zone flow temperature setpoint,
used when the zone is set to a fixed
flow setpoint.
0 °C - 90 °C
90
90
90
90
CP020
Functionality of the zone
0 = Disable
1 = Direct
2 = Mixing Circuit
3 = Swimming pool
4 = High Temperature
5 = Fan Convector
6 = DHW tank
7 = Electrical DHW
8 = Time Program
9 = ProcessHeat
10 = DHW Layered
11 = DHW Internal tank
12 = DHW Commercial
Tank
31 = DHW FWS EXT
1
1
1
1
CP040
Pump post runtime of the zone
0 Min - 20 Min
0
0
0
0
CP060
Wished room zone temperature on
holiday period
5 °C - 20 °C
6
6
6
6
CP070
Max Room Temperature limit of the
circuit in reduced mode, that allows
switching to comfort mode
5 °C - 30 °C
15
15
15
15
CP210
Comfort footpoint of the temperature
of heat curve of the circuit
15 °C - 90 °C
15
15
15
15
CP220
Reduced footpoint of the
temperature of heat curve of the
circuit
15 °C - 90 °C
15
15
15
15
CP230
Heating curve temperature gradient
of the zone
0 - 4
2,5
2,5
2,5
2,5
CP240
Adjustment of the influence of the
zone room unit
0 - 10
3
3
3
3
CP250
Calibration of Zone Room Unit
-5 °C - 5 °C
0
0
0
0
CP340
Type of reduced night mode, stop or
maintain heating of circuit
0 = Stop heat demand
1 = Continue heat
demand
0
0
0
0
CP470
Setting of the screed drying program
of the zone
0 Days - 30 Days
0
0
0
0
CP480
Setting of the start temperature of
the screed drying program of the
zone
20 °C - 50 °C
20
20
20
20
CP490
Setting of the stop temperature of
the screed drying program of the
zone
20 °C - 50 °C
20
20
20
20
CP730
Selection of heat up speed of the
zone
0 = Extra Slow
1 = Slowest
2 = Slower
3 = Normal
4 = Faster
5 = Fastest
0
0
0
0
9 Settings
54
7665063 - v.05 - 18102018