2. Adjust the fan speed (if necessary) for the gas type used according to
the table below. The setting can be changed with a parameter setting.
Tab.32 Adjustment for gas type G30/G31 (butane/propane)
Code
Description
Adjustment range
160
200
250
300
DP003
Maximum fan speed on Domestic Hot
Water
1000 Rpm - 7000 Rpm
6400
4400
5400
5550
GP007
Maximum fan speed during Central Heating
mode
1000 Rpm - 8500 Rpm
6400
4400
5400
5550
GP008
Minimum fan speed during Central Heating
+ Domestic Hot Water mode
900 Rpm - 8500 Rpm
2150
1400
1550
1700
GP009
Fan speed at appliance start
900 Rpm - 5000 Rpm
3000
2200
2200
2200
3. Check the setting of the gas/air ratio.
See
Checking/setting combustion, page 47
7.3.2
Checking/setting combustion
1. Unscrew the cap from the flue gas measuring point.
2. Insert the probe for the flue gas analyser into the measurement
opening.
Important
During measurement, seal the opening around the sensor fully.
The flue gas analyser must have a minimum accuracy of
±0.25% O
2
/CO
2
.
3. Measure the percentage of O
2
/CO
2
in the flue gases. Take
measurements at full load and at part load.
Enable full load
1. Press the two keys on the left simultaneously to select chimney sweep
mode.
The device is now running at part load. Wait until L:XX° appears on
the display.
2. Press the key twice.
The device is now running at full load. Wait until H:XX° appears on
the display.
Checking/setting values for O
2
/CO
2
at full load
1. Measure the percentage of O
2
/CO
2
in the flue gases.
2. Compare the measured value with the checking values in the table.
Tab.33 Checking/setting values for O
2
/CO
2
at full load for G20 (H
gas)
Values at full load for G20 (H gas)
O
2
%
CO
2
%
Gas 220 Ace 160
4.8 - 5.2
- 9.0
Gas 220 Ace 200
4.8 - 5.2
- 9.0
Fig.55
Flue gas measuring point
AD-0001179-01
Fig.56
Step 1
MW-3000325-01
Fig.57
Step 2
MW-3000326-01
7 Commissioning
7665063 - v.05 - 18102018
47