background image

5.

8.  Inspect and replace any portion of the sprinkler system 

subjected to fire conditions.  

9.  Verify that the following valves are in their respective posi-

tions prior to continuing: 
Manual Emergency Release - open
Main Drain Valve - open
Alarm Line Valve - open
Alarm Test Valve - closed
Condensate Drain valve - closed
Air/Nitrogen Supply Valves - closed

10.  Open pushrod chamber supply valve and allow water to 

fill the pushrod chamber. Close the Manual Emergency 

Release valve after any trapped air has had a chance to 
escape from the deluge valve’s pushrod chamber. 

11.  Upon seeing this solid flow of water coming out of the 

Model LP Dry Pilot Actuator, open the Rapid-Air Fill Valve 
thereby rapidly applying compressed air or nitrogen into 
the Model LP Dry Pilot Actuator and the sprinkler system 
until the pressure conforms to Table A levels, as indicat-
ed by the system air pressure gauge.  The Model LP Dry 
Pilot Actuator will eventually close during this pressuriz-
ing process and water will stop flowing through the drain 
tube. At this point, the pressure gauge on the pushrod 
chamber pressure will equalize to the available water 
supply pressure.  Once the actuator is set up correctly, 
close the Rapid-Air Fill Valve and open the Regulated Air 
Shutoff Valve. 

 

Note: 

For systems using nitrogen as the primary source, 

the system may be set up using the nitrogen source fol-
lowing the steps above.  The air compressor, if present, 
may then be placed into operation as the backup pneu-
matic source.

12.  Open the alarm line valve.
13.  If the Model B1 Accelerator Kit is installed, open valve P.  

Prior to opening valve P, be sure that the Model B1 Ac-
celerator has been successfully reset per Reliable Tech-
nical Bulletin 323.  

Note:

 The B1 Accelerator requires a minimum of 15 psi 

(1,0 bar) supervisory air or nitrogen pressure for proper 
operation. 

14.  Slightly open the main valve controlling water supply to 

the Model DDX-LP Deluge Valve.  This will begin to fill the 

deluge valve beneath the clapper with water.  Once any 
trapped air has been vented, close the main drain valve. 
Observe if water leaks through the ball drip valve into the 
1” drain manifold through the clear tubing. If no leakage 
occurs, the deluge valve clapper is sealed. Fully open 
the main valve controlling the water supply to the Model 
DDX-LP Deluge Valve and that it is properly monitored

15.  Verify that the pushrod chamber supply valve is open. 
16.  Secure the handle of the Model B Manual Emergency 

Station in the OFF position with a nylon tie (supplied with 
the assembly). 

Inspection And Testing Of The DDX-LP PrePaK 
Systems (Refer to Figure 2)

1.  Water supply

 — Verify that the valve controlling water 

supply to the deluge valve is opened fully and properly 
monitored.

2.  Pushrod Chamber supply

 — Verify that the valve sup-

plying water to the pushrod chamber is open.

3.  Other trimming valves

 — Verify that the alarm line valve  

is open as well as all of the pressure gauge valves. The 
main drain valve, alarm test valve, and condensate drain 
valve should be closed.

4.  Ball drip valve

 — Push in on the plunger to be sure the 

ball check is off its seat. If no water appears, the deluge 
valve’s water seat is tight. Inspect the small bleed hole lo-
cated on the underside of the Model DDX-LP Deluge Valve 
pushrod chamber for leakage.

5.  System air pressure

 — Verify that system air pressure 

is in conformance with the values posted in Table A for the 
supply water pressure.

6.  Releasing device

 — Check the outlet of the (Model LP 

Dry Pilot Actuator and Model B Manual Emergency Sta-
tion) for leakage. Also verify that tubing drain lines from 
releasing devices are not pinched or crushed which could 
prevent proper releasing of the deluge valve.

7.  Testing alarms

 — Open the alarm test valve permitting 

water from the supply to flow to the alarm pressure switch 
and to the mechanical sprinkler alarm (if present).  After 
testing, close this valve completely. Push in on the plunger 
of ball drip until all of the water has drained from the alarm 
line.

8.  Operational test

 — Open the Model B Manual Emergen-

cy Station or, alternatively, reduce air/nitrogen pressure on 
the system.  

Note:

 An operational test will cause the Del-

uge Valve to open and flow water into the sprinkler system.

9.  Secure the Model B Manual Emergency Station

 in the 

OFF position with a nylon tie (included with the assembly) 
after the deluge valve is reset.

Testing the Model DDX-LP Deluge Valve With-
out Flowing Water  (Refer to Figure 2)

1.  Close the valve controlling water supply to deluge valve 

and open the main drain. 

2.  Verify that the pushrod chamber supply valve is open, al-

lowing water to enter the pushrod chamber. 

3.  Close the air/nitrogen supply to the sprinkler system. 
4.  Decrease pneumatic pressure in the system by opening 

the condensate drain valve, until the Model LP Dry Pilot 
Actuator operates. Doing so will result in a sudden drop of 
water pressure in the deluge valve pushrod chamber. 

5.  Reset the system per the directions listed in “System Set-

up” section of this bulletin.

(cont. bottom of page 8)

Summary of Contents for N2-Blast DDX-LP PrePaK

Page 1: ...rePaK system incor porates a South Tek Systems FPS 900 pressure swing adsorp tion N2 Blast nitrogen generator complete with independent air compressor nitrogen storage tank and control system The nitr...

Page 2: ...ar The 2 2 1 2 3 and 8 sizes are rated for a maximum pressure of 250 psi 17 2 bar and the 4 and 6 sizes are rated for a maximum pressure of 300 psi 20 7 bar Water temperature must be maintained betwee...

Page 3: ...3 Fig 1...

Page 4: ...nal box mounted on the inside of the enclosure All field wiring connec tions are made at this terminal box A separate power connection is provided for the optional air compressor Note The air compress...

Page 5: ...16 Secure the handle of the Model B Manual Emergency Station in the OFF position with a nylon tie supplied with the assembly Inspection And Testing Of The DDX LP PrePaK Systems Refer to Figure 2 1 Wat...

Page 6: ...6 Fig 2 Model DDX LP Low Pressure Dry Pipe System Valve Legend Note Some items omitted for clarity...

Page 7: ...7 Fig 3...

Page 8: ...er has drained then close Note Leaving the condensate drain open for an extended pe riod of time may allow excess air nitrogen to bleed off and result in accidental release of the Model LP Dry Pilot A...

Page 9: ...r can lead to incorrect gas supply The nitrogen generator produces nitrogen at a low flow rate which quickly dissipates into the air Nitrogen is not poison ous but do not directly inhaled since high c...

Page 10: ...not adjust the factory preset cut in and out pressure without first consulting with South Tek Systems Patented BlastOff Leak Detection System The BlastOff Leak Detection is a patented feature which se...

Page 11: ...r further troubleshoot ing Low System Pressure Alarm Mode Lo n2 The low system pressure alarm activates when a sys tem pressure is detected below the normal functioning limits of the nitrogen generato...

Page 12: ...esponding filter housings Hand tighten only After replacing the filters check the filter bowls for leaks by turn ing on the unit momentarily Turn the unit off to reinstall the front cover and then pow...

Page 13: ...Fig 5 Nitrogen Generator Filter Locations 13...

Page 14: ...o 580 gallons 9 Nitrogen Generator Model B1 Accelerator 3 3 2 1 HP 115 VAC Systems up to 1170 gallons 4 4 3 1 2 HP 220 VAC 60 Hz Systems up to 580 gallons A 2 w System Side Control Valve 4 1 HP 220 VA...

Reviews: