background image

4.

Hydrostatic Testing of DDX-LP Valves and DDX-
LP Systems 

As required by NFPA 13, fire sprinkler systems with working 

pressures up to and including 150 psi are to be hydrostatically 
tested at a water pressure of 200 psi. Fire sprinkler systems with 
working pressures above 150 psi are required to be hydrostati-
cally tested at 50 psi above the system working pressure. In ad-
dition to the hydrostatic tests described above, dry pipe systems 
require an additional low pressure air test. 

In some cases, hydrostatic testing (in accordance with the 

NFPA 13 requirements noted above) will result in pressures that 
exceed the working pressure of the valve and trim kit for the two-
hour test period. 

The valve and applicable trim kit have been tested, approved 

and listed under these conditions and as such, hydrostatic test-
ing in accordance with NFPA 13 is acceptable. In addition, the 
clapper can remain in the closed position and the trim kit need 
not be isolated, as each has been designed to withstand hydro-
static testing as required by NFPA 13. 

Subjecting the valve and trim to pressures higher than their 

rating is limited to the hydrostatic test as referenced by NFPA13. 
It does not address the occurrence of a “water hammer” effect, 
which may damage the valve. A “water hammer” in the water 
supply piping of the valve can create pressures in excess of the 
rated pressure and should be avoided by all necessary means. 

This  condition  may  be  created  from  improper  fire  pump  set

-

tings, underground construction work, or an improper venting 
of trapped air in the water supply piping. 

System Supervisory Pressure Requirements 

The DDX-LP PrePaK system includes gauges indicating the 

air/nitrogen  and water pressures on the Model DDX-LP sys-

tem. Table A specifies the air or nitrogen pressure to be main

-

tained in the sprinkler system piping based on the water supply 
pressure.  The factory installed Pressure Maintenance Device 
in the unit automatically regulates makeup air or nitrogen flow 
to maintain pressure with normal leakage from system piping, 
while restricting the flow of makeup air or nitrogen to the sys-
tem.  Please note that when the optional Model B1 Accelerator 
is to be utilized to expedite water-delivery time, the air or nitro-
gen pressure must be not less than 15 psi (1.0 bar). 

The factory-installed system low air pressure switch may need 

on-site adjustment to correspond with the air pressure values 
found in Table A.  Adjustment, if required, should be made ac-
cording to Potter Bulletin 5401564 included with the switch. 

System Electrical Requirements

All 24 VDC electrical connections in the Reliable Model DDX-

LP PrePaK system are translated to a water tight terminal box 

mounted on the inside of the enclosure.  All field wiring connec

-

tions are made at this terminal box.

A separate power connection is provided for the optional air 

compressor.

Note: 

The air compressor must  be connected to a grounded 

metallic, permanent wiring system, or an equipment grounding 
terminal or lead on the product. Power supply wiring must con-

form to all required safety codes and be installed by a qualified 

person. Check that the supply voltage agrees with that listed on 
compressor nameplate. 

Maintenance

The Reliable DDX-LP PrePaK system and associated equip-

ment shall periodically be given a thorough inspection and test. 
NFPA 25, Standard for Inspection, Testing and Maintenance of 
Water Based Fire Protection Systems, provides minimum main-
tenance requirements. Systems should be tested, operated, 
cleaned and inspected at least annually, and parts replaced as 
required. Periodically open the condensate drain valve beneath 
the air tank to drain any condensate accumulation. Reliable 
Technical Bulletins 338 and 519 provide additional information 
for maintaining the Model DDX-LP Deluge Valve.

System Setup (Refer to Figure 2)

1.  Close the main valve controlling water supply to the Model 

DDX-LP deluge valve.  Also, close the two ¼” valves sup-
plying air or nitrogen to the system.

2.  Close the pushrod chamber supply valve.
3.  Open the main drain valve and drain the system.  
4.  Open all drain valves and vents at low points throughout 

the system, closing them when flow of water has stopped. 

5.  Open the Manual Emergency Release valve. 

Note:

  The 

above steps accomplish the relieving of pressure in the 
pushrod chamber of the deluge valve. 

6.  Push in the plunger of ball drip valve to force the ball from 

its seat, and drain any water in the alarm line.

7.  Push in and rotate the deluge valve’s external reset knob 

counter-clockwise (when facing valve) until you hear a dis-
tinct clicking noise, indicating that the clapper has reset. 

Note:

 The reset knob can be rotated only after pressure 

in the pushrod chamber is reduced to atmospheric condi-
tions (0 psig).

Water Pressure psi (bar)

System Air or Nitrogen Pressure 

psi (bar)

Maximum

Not Less Than

20 (1.4)

8 (0.6)

30 (2.1)

10 (0.7)

50 (3.4)

12 (.8)

75 (5.2)

13 (.9)

100 (6.9)

15 (1.)

125 (8.6)

16 (1.1)

150 (10.3)

17 (1.2)

175 (12.1)

18 (1.2)

200 (13.8)

19 (1.3)

225 (15.5)

21 (1.4)

250 (17.2)

22 (1.5)

275 (19.0)

23 (1.6)

300 (20.7)

24 (1.7)

Table A

Notes:

1. 

Supervisory air or nitrogen pressure should not exceed 30 psi (2.1 bar).  
Excess pressure may result in damage to the actuator.

2. 

Fastest valve operation is achieved with supervisory air or nitrogen 
pressure indicated; however, pressure must never be less than the 

minimum specified in the table above.

3. 

Air maintenance devices that maintain a constant pressure are 
recommended; however, if a tank-less compressor is used, the 
“compressor on” setting of the pressure switch must never be lower than 
the minimum pressure in the table above.

Summary of Contents for N2-Blast DDX-LP PrePaK

Page 1: ...rePaK system incor porates a South Tek Systems FPS 900 pressure swing adsorp tion N2 Blast nitrogen generator complete with independent air compressor nitrogen storage tank and control system The nitr...

Page 2: ...ar The 2 2 1 2 3 and 8 sizes are rated for a maximum pressure of 250 psi 17 2 bar and the 4 and 6 sizes are rated for a maximum pressure of 300 psi 20 7 bar Water temperature must be maintained betwee...

Page 3: ...3 Fig 1...

Page 4: ...nal box mounted on the inside of the enclosure All field wiring connec tions are made at this terminal box A separate power connection is provided for the optional air compressor Note The air compress...

Page 5: ...16 Secure the handle of the Model B Manual Emergency Station in the OFF position with a nylon tie supplied with the assembly Inspection And Testing Of The DDX LP PrePaK Systems Refer to Figure 2 1 Wat...

Page 6: ...6 Fig 2 Model DDX LP Low Pressure Dry Pipe System Valve Legend Note Some items omitted for clarity...

Page 7: ...7 Fig 3...

Page 8: ...er has drained then close Note Leaving the condensate drain open for an extended pe riod of time may allow excess air nitrogen to bleed off and result in accidental release of the Model LP Dry Pilot A...

Page 9: ...r can lead to incorrect gas supply The nitrogen generator produces nitrogen at a low flow rate which quickly dissipates into the air Nitrogen is not poison ous but do not directly inhaled since high c...

Page 10: ...not adjust the factory preset cut in and out pressure without first consulting with South Tek Systems Patented BlastOff Leak Detection System The BlastOff Leak Detection is a patented feature which se...

Page 11: ...r further troubleshoot ing Low System Pressure Alarm Mode Lo n2 The low system pressure alarm activates when a sys tem pressure is detected below the normal functioning limits of the nitrogen generato...

Page 12: ...esponding filter housings Hand tighten only After replacing the filters check the filter bowls for leaks by turn ing on the unit momentarily Turn the unit off to reinstall the front cover and then pow...

Page 13: ...Fig 5 Nitrogen Generator Filter Locations 13...

Page 14: ...o 580 gallons 9 Nitrogen Generator Model B1 Accelerator 3 3 2 1 HP 115 VAC Systems up to 1170 gallons 4 4 3 1 2 HP 220 VAC 60 Hz Systems up to 580 gallons A 2 w System Side Control Valve 4 1 HP 220 VA...

Reviews: