FPS-900-RS Nitrogen Generator

General

This manual provides instruction for the proper use and 
maintenance of South-Tek Systems N2-Blast

®

 FPS-900-RS. 

South-Tek Systems and Reliable are not responsible for dam-
ages when using this in manners not approved by South-Tek 
Systems and Reliable. The user(s) of this document should 

confer  any  questions  with  a  qualified  South-Tek  Systems 

representative on its commissioning and correct use. Please 
contact South-Tek Systems with any question or concerns at:

South-Tek Systems, LLC
2940 Orville Wright Way Ste 600
Wilmington, NC, 28405
Tel: (888) 526-6284
Email: [email protected]
http://www.southteksystems.com/

Important Information

All personnel (and their supervisors) installing, operating, and 
maintaining the N2-Blast

®

 must read and fully understand 

this manual prior to installing, operating or performing main-
tenance. The N2-Blast

®

 produces nitrogen (N

2

) at a low flow 

rate, which quickly dissipates into the air. N

2

 gas is not poison-

ous, but do not directly inhale since high concentrations can 
cause asphyxiation. Install the unit in a well-ventilated room 
that is not sealed off from normal living space air changes. 
All personnel involved with the installation, operations, and 
maintenance of the N2-Blast

®

 must follow safe working prac-

tices, including OHSA and local health/safety code regula-
tions.

Safety Guidelines

  The following section outlines the basic safety consider-
ations about installation and operation of the N2-Blast

®

 FPS-

900-RS. For other equipment used with the nitrogen genera-
tor, such as external air compressors, and dryers, refer to the 
manufacturer’s safety guidelines.
  Using the N2-Blast

®

 FPS-900-RS correctly is important 

for safety and trouble-free operation. Wrong use can cause 
damages to the system or can lead to incorrect gas supply. 
The nitrogen generator produces nitrogen at a low flow rate, 
which quickly dissipates into the air. Nitrogen is not poison-
ous, but do not directly inhaled, since high concentrations, 
can cause asphyxiation. Install the unit in a well-ventilated 
room, unsealed off from normal living space air changes.

Warning:

 Install the unit in a within a well-ventilated room, 

one that is not sealed off from normal living space air chang-
es.

 

Read carefully and act accordingly before operating or re-

pairing the unit:

• 

The operator must use safe working practices and 
rules when running the nitrogen generator.

• 

The owner is responsible for always keeping the unit 
in safe working conditions.

• 

Always use approved parts when performing mainte-
nance and repairs. Make sure that replacement parts 

meet or exceed the original parts’ specification.

• 

Only competent individuals, trained and authorized, 
can install, operate, perform maintenance and repair.

• 

Isolate incoming and outgoing pressures to the gen-
erator, and depressurize the service or repair section 
before performing any mechanical work, including 

changing the filters.

• 

Vent the nitrogen generator’s exhaust gas outside or 
to a large, well-ventilated room to avoid suffocation 
due to lack of oxygen.

• 

Wear safety glasses if the cabinet door is open while 
the machine is running.

• 

Use ear protection when the equipment is running.

NOTE: Always following local and site safety regulations 
in conjunction with this manual.  Correct use of the nitro-
gen generator is important for personal safety. Incorrect 
safety practices can cause damage to the individual and 
equipment.

 Follow safe working practices, OSHA, and local health and 
safety regulation when maintaining the N2-Blast

® 

FPS-900-RS.

Air Supply

 

The N2-Blast

®

 FPS-900-RS includes a built-in air compres-

sor to supply gas to the nitrogen generator. It is not for perform-

ing  quick  fills;  a  separate  suitable  air  compressor  should  be 
used to fill the system.

9.

Summary of Contents for N2-Blast DDX-LP PrePaK

Page 1: ...rePaK system incor porates a South Tek Systems FPS 900 pressure swing adsorp tion N2 Blast nitrogen generator complete with independent air compressor nitrogen storage tank and control system The nitr...

Page 2: ...ar The 2 2 1 2 3 and 8 sizes are rated for a maximum pressure of 250 psi 17 2 bar and the 4 and 6 sizes are rated for a maximum pressure of 300 psi 20 7 bar Water temperature must be maintained betwee...

Page 3: ...3 Fig 1...

Page 4: ...nal box mounted on the inside of the enclosure All field wiring connec tions are made at this terminal box A separate power connection is provided for the optional air compressor Note The air compress...

Page 5: ...16 Secure the handle of the Model B Manual Emergency Station in the OFF position with a nylon tie supplied with the assembly Inspection And Testing Of The DDX LP PrePaK Systems Refer to Figure 2 1 Wat...

Page 6: ...6 Fig 2 Model DDX LP Low Pressure Dry Pipe System Valve Legend Note Some items omitted for clarity...

Page 7: ...7 Fig 3...

Page 8: ...er has drained then close Note Leaving the condensate drain open for an extended pe riod of time may allow excess air nitrogen to bleed off and result in accidental release of the Model LP Dry Pilot A...

Page 9: ...r can lead to incorrect gas supply The nitrogen generator produces nitrogen at a low flow rate which quickly dissipates into the air Nitrogen is not poison ous but do not directly inhaled since high c...

Page 10: ...not adjust the factory preset cut in and out pressure without first consulting with South Tek Systems Patented BlastOff Leak Detection System The BlastOff Leak Detection is a patented feature which se...

Page 11: ...r further troubleshoot ing Low System Pressure Alarm Mode Lo n2 The low system pressure alarm activates when a sys tem pressure is detected below the normal functioning limits of the nitrogen generato...

Page 12: ...esponding filter housings Hand tighten only After replacing the filters check the filter bowls for leaks by turn ing on the unit momentarily Turn the unit off to reinstall the front cover and then pow...

Page 13: ...Fig 5 Nitrogen Generator Filter Locations 13...