Installation
Model G series sprinklers must be installed with the Reliable Model
W2 sprinkler installation wrench as identified in this Bulletin. Any
other wrench may damage the sprinkler. The Model W2 wrench
has two sets of jaws. Use the smallest set of jaws that fit on the
wrench flats of the sprinkler. A leak tight sprinkler joint can be
obtained with an appropriate thread sealant and a torque of 6 to 12
lb-ft (8 to 16 N
.
m) for 3/8” threads, 8 to 18 lb-ft (11 to 24 N
.
m) for
1/2” threads, and 14 to 20 lb-ft (19 to 27 N
.
m) for 3/4” threads. Do
not tighten sprinklers over the maximum recommended installation
torque. Exceeding the maximum recommended installation torque
may cause leakage or impairment of the sprinkler.
Maintenance
Reliable Model G series sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA 25, as well
as the requirements of any Authorities Having Jurisdiction.
Prior to installation, sprinklers should remain in the original
cartons and packaging until used. This will minimize the potential
for damage to sprinklers that could cause improper operation or
non-operation.
Do not clean sprinklers with soap and water, ammonia liquid or
any other cleaning fluids. Remove dust by gentle vacuuming
without touching the sprinkler.
Replace any sprinkler which has been painted (other than factory
applied). A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprinklers.
Failure to properly maintain sprinklers may result in inadvertent
operation or non-operation during a fire event.
Standard Finishes
Special Application Finishes
Bronze
Bright Brass
(3)
Chrome Plated
Black Plated
White Polyester
Lead Plated
Wax Coated
(4)
Wax
(4)
over Lead
Notes:
1.
Other finishes and colors are available on special order.
Consult your Reliable sales representative for details.
2.
Paint or any other coating applied over the factory finish will
void all approvals and warranties.
3. For 212°F (100°C) maximum temperature rated sprinklers
only.
4. Clear wax used on ordinary temperature rated sprinklers;
brown wax used on intermediate temperature rated
sprinklers. Brown wax may be used on high temperature
rated sprinklers where the ambient temperature does not
exceed 150°F (66°C).
Sprinkler Finishes
(1)(2)
Table B
Guarantee
For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms,
and conditions, visit www.reliablesprinkler.com.
Ordering Information
Specify the following when ordering:
Model
•
G
Threads/K Factor
•
3/8” BPST, 4.10 (59.1 metric)
•
1/2” BPST, 5.62 (81.0 metric)
•
3/4” BPST, 8.2 (118.2 metric)
Temperature Rating
•
See Sprinkler Specification Page
Sprinkler Rating
•
See Table B
Sprinkler Wrench
•
Model W2
Model W2 Wrench
Figure 5
P/N 9999970629
Bulletin 079
May 2021
Page 6 of 6
www.reliablesprinkler.com