Installation

Model G series sprinklers must be installed with the Reliable Model 

W2 sprinkler installation wrench as identified in this Bulletin. Any 

other wrench may damage the sprinkler.  The Model W2 wrench 

has two sets of jaws.  Use the smallest set of jaws that fit on the 

wrench flats of the sprinkler.  A leak tight sprinkler joint can be 
obtained with an appropriate thread sealant and a torque of 6 to 12 
lb-ft (8 to 16 N

.

m) for 3/8” threads, 8 to 18 lb-ft (11 to 24 N

.

m) for 

1/2” threads, and 14 to 20 lb-ft (19 to 27 N

.

m) for 3/4” threads. Do 

not tighten sprinklers over the maximum recommended installation 
torque. Exceeding the maximum recommended installation torque 
may cause leakage or impairment of the sprinkler.

Maintenance

Reliable Model G series sprinklers should be inspected and the 
sprinkler system maintained in accordance with NFPA 25, as well 
as the requirements of any Authorities Having Jurisdiction.

Prior to installation, sprinklers should remain in the original 

cartons and packaging until used. This will minimize the potential 

for damage to sprinklers that could cause improper operation or 
non-operation.

Do not clean sprinklers with soap and water, ammonia liquid or 
any other cleaning fluids. Remove dust by gentle vacuuming 
without touching the sprinkler.

Replace any sprinkler which has been painted (other than factory 
applied). A stock of spare sprinklers should be maintained to 
allow quick replacement of damaged or operated sprinklers.  
Failure to properly maintain sprinklers may result in inadvertent 

operation or non-operation during a fire event.

Standard Finishes

Special Application Finishes

Bronze

Bright Brass

(3)

Chrome Plated

Black Plated

White Polyester

Lead Plated

Wax Coated

(4)

Wax

(4)

 over Lead

Notes:

1. 

Other finishes and colors are available on special order. 

Consult your Reliable sales representative for details.

2. 

Paint or any other coating applied over the factory finish will 

void all approvals and warranties.

3.  For 212°F (100°C) maximum temperature rated sprinklers 

only.

4.  Clear wax used on ordinary temperature rated sprinklers; 

brown wax used on intermediate temperature rated 
sprinklers.  Brown wax may be used on high temperature 
rated sprinklers where the ambient temperature does not 
exceed 150°F (66°C).

Sprinkler Finishes

(1)(2)

Table B

Guarantee

For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms, 
and conditions, visit www.reliablesprinkler.com.

Ordering Information

Specify the following when ordering:

Model

• 

G

Threads/K Factor

• 

3/8” BPST, 4.10 (59.1 metric)

• 

1/2” BPST, 5.62 (81.0 metric)

• 

3/4” BPST, 8.2 (118.2 metric)

Temperature Rating

• 

See Sprinkler Specification Page

Sprinkler Rating

• 

See Table B

Sprinkler Wrench

• 

Model W2

Model W2 Wrench

Figure 5

P/N 9999970629

Bulletin 079
May 2021

Page 6 of 6

www.reliablesprinkler.com

Summary of Contents for G Series

Page 1: ...t the ceiling and the remainder downward to the floor and may be used in either the upright or pendent position Reliable Model G Conventional Sprinklers are standard response fire sprinklers utilizing a solder capsule strut and lever thermal element These sprinklers are available in 4 10 59 1 metric 5 62 81 0 metric and 8 2 118 2 metric K factor When used in the pendent position sprinklers may be ...

Page 2: ...nkler Frame Leaded Red Brass Alloy Cap Brass Alloy with PTFE Load Screw Brass CDA Alloy Deflector Brass CDA Alloy Sprinkler Finishes See Table B Sensitivity Standard Response Temperature Ratings 135 F 57 C 165 F 74 C 212 F 100 C 286 F 141 C Sprinkler Wrench Model W2 Listings and Approvals Pleniere Assemblee Model G 3 8 Conventional Sprinkler Components and Dimensions Figure 1 Bulletin 079 May 2021...

Page 3: ... Leaded Red Brass Alloy Cap Brass Alloy with PTFE Load Screw Brass CDA Alloy Deflector Brass CDA Alloy Sprinkler Finishes See Table B Sensitivity Quick Response Temperature Ratings 135 F 57 C 165 F 74 C 212 F 100 C 286 F 141 C Sprinkler Wrenches Model W2 Listings and Approvals LPCB Pleniere Assemblee CE 1438 CPR 0052 Model G 1 2 Conventional Sprinkler Components and Dimensions Figure 2 Bulletin 07...

Page 4: ...Leaded Red Brass Alloy Cap Brass Alloy with PTFE Load Screw Brass CDA Alloy Deflector Brass CDA Alloy Sprinkler Finishes See Table B Sensitivity Standard Response Temperature Ratings 135 F 57 C 165 F 74 C 212 F 100 C 286 F 141 C Sprinkler Wrenches Model W2 Listings and Approvals LPCB Pleniere Assemblee CE 1438 CPR 0052 Model G 3 4 Conventional Sprinkler Components and Dimensions Figure 3 Bulletin ...

Page 5: ...ce any sprinkler which has been painted other than factory applied A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers Failure to properly maintain sprinklers may result in inadvertent operation or non operation during a fire event Standard Finishes Special Application Finishes Bronze Bright Brass 3 Chrome Plated Black Plated White Polyeste...

Reviews: