14.

Installation Instructions

Model F3-80 Dry sprinklers must only be installed in the 

following fittings:
1.  The side outlet of an ANSI B 16.3 class 150 (malleable 

or ductile) or ANSI B16.4 class 125 (cast) iron pipe 
tee

2.  The run outlet of an ANSI B 16.3 class 150 (malleable 

or ductile) or ANSI B16.4 class 125 (cast) iron pipe 
tee, with the side outlet plugged (wet-pipe systems 
only)

3.  Spears Manufacturing Company Brass Thread In-

sert Style or Special Reinforced Plastic Thread Style 
Listed adapter or tee (wet-pipe systems only) (gasket 
sealed outlets shall not be used)

4.  Any Listed CPVC sprinkler adapter or tee only in ac-

cordance with Fig. 9 and upon verification that the 
CPVC adapter or tee does not interfere with the sprin-
kler’s inlet (wet-pipe systems only) (gasket sealed 
outlets shall not be used)

Model F3-80 Dry sprinklers must not be installed into cou-

plings, elbows, welded outlets, or gasket sealed outlets. In-
stallation of the Model F3-80 Dry sprinkler is not recommend 
in copper pipe systems, as this may reduce the life expec-
tancy of the sprinkler.

In all dry-pipe system installations, the Model F3-80 Dry 

sprinkler must be installed with protrusion into the fitting in 
accordance with Fig. 1 through Fig. 7 in this Bulletin.  Do not 
install Model F3-80 Dry sprinklers with the standard (long) 
inlet fitting into CPVC fittings that have an internal obstruc-
tion (see Fig. 9); this will damage the sprinkler, the fitting, or 
both. Model F3-80 Dry sprinklers are available with a short 
“PL” inlet fitting for installation on CPVC fittings of wet-pipe 
sprinkler systems only.

Model F3-80 Dry sprinklers connected to wet-pipe sys-

tems must be installed with the Exposed Minimum Barrel 
Length required by Fig. 8 located in a Heated Area.

An orange protective clip is factory installed on the sprin-

kler to protect the glass bulb thermal element from dam-
age. The clip should remain in place during installation of 
the sprinkler and be removed when the sprinkler system is 
placed in service. 

Use the following steps for installation:

1.  Cut a hole in the wall or ceiling directly in-line with 

the outlet of the fitting. See the Installation Data table 
for the recommended hole diameter based on the es-
cutcheon or cover plate option selected.

2.  Apply pipe joint compound or PTFE tape to the male 

threads of the sprinkler’s inlet fitting.

3.  Install the sprinkler in the fitting using the installation 

wrench specified in the Installation Data table. The 
Model F3R wrenches are designed to be inserted into 
the groves in the sprinkler’s wrench boss as shown 
in Fig. 10. The Model XLO2 wrench is designed to fit 
into the cup and engage the wrench boss as shown 
in Fig. 11. Do NOT wrench any part of the sprinkler 
assembly other than the wrench boss. When inserting 
or removing the wrench from the sprinkler, care 

should be taken to prevent damage to the sprinkler. 
The sprinkler is then tightened into the pipe fitting to 
achieve a leak free connection. The recommended 
minimum to maximum installation torque is 22 - 30 lb-
ft (30 – 40 N-m).
3a. Alternatively, where access to the outer tube of the 

sprinkler is available, the Model F3-80 Dry sprinkler 
may be installed using a pipe wrench. The pipe 
wrench shall only be permitted to interface with 
the galvanized steel outer tube portion of the 
sprinkler (Item #8 in Fig. 12). Do NOT wrench any 
other portion of the sprinkler assembly. A pipe 
wrench can install the sprinkler into the fitting with 
a large amount of torque; consideration should be 
given to the need for future removal of the sprinkler 
because the installation torque will have to be 
matched or exceeded to remove the sprinkler. The 
recommended minimum to maximum installation 
torque is 22 - 30 lb-ft (30 – 40 N-m).

4.  Standard and Model HB escutcheons can be 

installed by slipping the escutcheon over the can until 
the escutcheon is seated against the ceiling or wall.  
The Model FP escutcheon is installed by pressing 
or threading the escutcheon into the cup by hand; 
the escutcheon can be tightened against the ceiling 
or wall by turning the escutcheon in a clockwise 
direction and removed by turning the escutcheon in a 
counter-clockwise direction. To install the Model CCP 
cover plate, first remove the protective clip. Install the 
Model CCP cover plate on the sprinkler by pressing 
or threading the cover plate into the cup by hand; the 
cover plate can be tightened against the ceiling by 
turning the cover plate in a clockwise direction and 
removed by turning the cover plate in a counter-
clockwise direction. 

5.  Remove the orange protective clip when placing the 

sprinkler system in service.

Summary of Contents for F3-80 Dry Horizontal Sidewall

Page 1: ...able in this Bulletin for available temperature rat ings Model F3 80 Dry sprinklers are intended for installa tion on wet pipe dry pipe or preaction sprinkler systems in accordance with NFPA 13 Model...

Page 2: ...range 135 F 57 C 135 F 57 C 100 F 38 C cULus NYC Red 155 F 68 C Intermediate Yellow 175 F 79 C 165 F 74 C 150 F 66 C Intermediate Green 200 F 93 C 165 F 74 C 150 F 66 C High Blue 286 F 141 C None 225...

Page 3: ...en escutcheon is in nominal position Escutcheon adjustment provides 6mm to 1 32mm A dimension adjustment range Fig 1 Model F3 80 Dry Pendent Sprinkler with Standard Escutcheon SIN RA6012 A Dim 2 to 36...

Page 4: ...HB Extended Escutcheon SIN RA6012 A Dim 3 to 36 89mm to 914mm in 1 4 6mm increments Note The sprinkler can protrudes 1 when escutcheon is in nominal position Escutcheon adjustment provides 12 7mm to...

Page 5: ...dent sprinkler with the Model FP escutcheon in ceilings which have positive pressure in the space above Fig 3 5 Model F3 80 Dry Pendent Sprinkler with Model FP Recessed Escutcheon SIN RA6012 A Dim 31...

Page 6: ...del CCP Cover Plate SIN RA6012 A Dim 31 2 to 36 89mm to 914mm in 1 4 6mm increments Note Do not install the Model F3 80 Dry Pendent sprinkler with the Model CCP cover plate in ceilings which have posi...

Page 7: ...ustment provides 6mm to 1 32mm A dimension adjustment range Fig 5 7 Model F3 80 Dry Horizontal Sidewall Sprinkler with Standard Escutcheon SIN RA6032 A Dim 2 to 48 51mm to 1219mm in 1 4 6mm increments...

Page 8: ...31 2 to 48 89mm to 1219mm in 1 4 6mm increments for 1 connections or 3 to 36 89mm to 914mm in 1 4 6mm increments for 3 4 connections Note The sprinkler can protrudes 1 when escutcheon is in nominal po...

Page 9: ...48 89mm to 1219mm in 1 4 6mm increments for 1 connections or 3 to 36 89mm to 914mm in 1 4 6mm increments for 3 4 connections Note Do not install the Model F3 80 Dry Horizontal Sidewall sprinkler with...

Page 10: ...10 Fig 8...

Page 11: ...Fig 9 11...

Page 12: ...Fig 11 Model XLO2 Wrench Fig 10 Model F3R Wrench 12...

Page 13: ...Fig 12 13...

Page 14: ...he es cutcheon or cover plate option selected 2 Apply pipe joint compound or PTFE tape to the male threads of the sprinkler s inlet fitting 3 Install the sprinkler in the fitting using the installatio...

Page 15: ...een the bulb supporting cup and the wrenching boss Do not replace this wax with a substitute substance An Alternate substance may interfere with proper operation of the sprinkler Do not clean sprinkle...

Reviews: