background image

Model F1FR56-300 Upright Sprinkler 

SIN RA2625

Technical Specifications

Style: 

Upright

 Threads:

 1/2” NPT or ISO 7-R1/2

 Nominal K-Factor:

 5.6 (80 metric)

 Max. Working Pressure:

 300 psi (20.7 bar)

Material Specifications

Thermal Sensor: 

3 mm Glass Bulb

Sprinkler Frame: 

Brass Alloy

Cap: 

Bronze Alloy

Sealing Washer: 

Nickel with PTFE

Load Screw: 

Copper Alloy

Deflector: 

Brass Alloy

Sprinkler Finishes 

(See Table B)

Sensitivity

Quick response

Temperature Ratings

 135°F (57°C)
 155°F (68°C)
 175°F (79°C)
 200°F (93°C)
 286°F (141°C)

Guards & Shields (New Frames)

F-1 Guard
F-3 Guard with Shield

Guards and Shields (Legacy Frames)

C-3 Guard with Shield
D-1 Guard
D-3 Guard with Shield

Sprinkler Wrench

Model W2
Model J (new frame with guard installed)
Model JD (legacy frame with guard 
installed)

Listings and Approvals

 cULus

Model F1FR56-300 Upright Sprinkler Components and Dimensions 

Figure 1

Deflector

Glass Bulb

(3 mm)

Wrench Flat

Threads

1 3/8" [33mm]

Cap/Seal Assembly

Load Screw

2 3/8" [60mm]

F1_HALF_UPR

Bulletin 077

October 2022

Page 2 of 8

www.reliablesprinkler.com

Summary of Contents for F1FR56-300 Series

Page 1: ...lers are 300 psi 20 7 bar rated quick response standard spray automatic fire sprinklers utilizing a sensitive 3 0 mm glass bulb thermal element Pendent and horizontal sidewall sprinklers may be instal...

Page 2: ...response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C Guards Shields New Frames F 1 Guard F 3 Guard with Shield Guards and Shields Legacy Frames C 3 Guard with Shield D...

Page 3: ...rd F 8 Guard with Shield S 1 Shield Guards and Shields Legacy Frames 2 D 1 Guard D 5 Guard with Shield S 1 Shield Sprinkler Wrenches Model W2 non recessed Model W4 recessed or concealed Model J new fr...

Page 4: ...3 F 7 Guard Guards Shields Legacy Frames 3 D 1 Guard Sprinkler Wrenches Model W2 non recessed Model W4 recessed or concealed Model J new frame with guard installed Model JD legacy frame with guard in...

Page 5: ...Reducing Fitting Reducing Fitting Reducing Fitting Note Model FP recessed assemblies may not be used where the pressure in the space above the ceiling is positive with respect to the protected area En...

Page 6: ...djustment 4 12 102 mm 305 mm Deflector to ceiling 9 16 14mm 4 12 102 mm 305 mm Deflector to ceiling 9 16 14mm Note Model FP recessed assemblies may not be used where the pressure in the space behind t...

Page 7: ...tallation sprinklers should remain in the original cartons and packaging until used This will minimize the potential for damage to sprinklers that could cause improper operation or non operation Do no...

Page 8: ...inkler technical specifications Sprinkler Finish See Table B Recessed Escutcheon F1 F2 FP Escutcheon Finish See Table B CCP or SWC Cover Plate Temperature Rating 135 F 57 C For use with 135 F 57 C and...

Reviews: