Installation

Model F1FR Series sprinklers must be installed in accordance 
with NFPA13 and the requirements of all applicable authorities 
having jurisdiction.  Model F1FR56-300 Series sprinklers must be 

installed with the Reliable sprinkler installation wrench identified 

in this Bulletin. Any other wrench may damage the sprinkler.  The 
Models W2 and W4 wrenches have two sets of jaws.  Use the 

smallest set of jaws that fit on the wrench flats of the sprinkler.  

A leak tight sprinkler joint can be obtained with a torque of 8 
to 18 lb-ft (11 to 24 N

.

m). Do not tighten sprinklers over the 

maximum recommended installation torque. Exceeding the 
maximum recommended installation torque may cause leakage 

or impairment of the sprinkler.

Glass bulb sprinklers have orange bulb protectors or protective 

caps to minimize bulb damage during shipping, handling and 

installation. Reliable sprinkler installation wrenches are designed 
to install sprinklers with bulb protectors in place. Remove the 
bulb protector at the time when the sprinkler system is placed in 

service for fire protection. Removal of the bulb protector before 

this time may leave the bulb vulnerable to damage. Remove bulb 
protectors by undoing the clasp by hand. Do not use tools to 
remove bulb protectors.

Maintenance

Reliable Model F1FR56-300 series sprinklers should be 
inspected and the sprinkler system maintained in accordance 

with NFPA 25, as well as the requirements of any Authorities 

Having Jurisdiction.

Prior to installation, sprinklers should remain in the original 

cartons and packaging until used. This will minimize the potential 
for damage to sprinklers that could cause improper operation or 
non-operation.

Do not clean sprinklers with soap and water, ammonia liquid or 

any other cleaning fluids. Remove dust by gentle vacuuming 
without touching the sprinkler.

Replace any sprinkler which has been painted (other than factory 
applied). A stock of spare sprinklers should be maintained to 
allow quick replacement of damaged or operated sprinklers.  
Failure to properly maintain sprinklers may result in inadvertent 

operation or non-operation during a fire event.

 Wrenches

Model W2 (upright, pendent)

Model J (New frame with guard installed)

Model JD (Legacy frame with guard installed, similar but with zinc finish)

Model W4

(recessed, concealed pendent)

Notes:

1. 

Paint or any other coating applied over the factory finish will void all approvals and warranties.

2. 

Model FP escutcheons, Model CCP sprinklers, and Model SWC sprinklers utilize a galvanized steel cup with a finished trim ring or cover plate.

3. 

cULus Listed as corrosion resistant.

4. 

For 200°F (93°C) maximum temperature rated sprinklers only.

Finishes

(1)

Table B

Standard Finishes

Special Application Finishes

Sprinkler

F1, F2 and FP

(2)

Escutcheons

CCP & SWC 

Cover Plates

(2)

Sprinkler

F1, F2 and FP

(2)

Escutcheons

CCP & SWC

 Cover Plates

(2)

Bronze

Brass

Chrome

Electroless Nickel PTFE

(3)

Bright Brass

Bright Brass

Chrome

Chrome

White Paint

Bright Brass

(4)

Satin Chrome

Satin Chrome

White Polyester

(3)

White Polyester

Satin Chrome

Custom Color 

Polyester

Custom Color Paint

Custom Color Polyester

(3)

Bulletin 077

October 2022

Page 7 of 8

www.reliablesprinkler.com

Summary of Contents for F1FR56-300 Series

Page 1: ...lers are 300 psi 20 7 bar rated quick response standard spray automatic fire sprinklers utilizing a sensitive 3 0 mm glass bulb thermal element Pendent and horizontal sidewall sprinklers may be instal...

Page 2: ...response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C Guards Shields New Frames F 1 Guard F 3 Guard with Shield Guards and Shields Legacy Frames C 3 Guard with Shield D...

Page 3: ...rd F 8 Guard with Shield S 1 Shield Guards and Shields Legacy Frames 2 D 1 Guard D 5 Guard with Shield S 1 Shield Sprinkler Wrenches Model W2 non recessed Model W4 recessed or concealed Model J new fr...

Page 4: ...3 F 7 Guard Guards Shields Legacy Frames 3 D 1 Guard Sprinkler Wrenches Model W2 non recessed Model W4 recessed or concealed Model J new frame with guard installed Model JD legacy frame with guard in...

Page 5: ...Reducing Fitting Reducing Fitting Reducing Fitting Note Model FP recessed assemblies may not be used where the pressure in the space above the ceiling is positive with respect to the protected area En...

Page 6: ...djustment 4 12 102 mm 305 mm Deflector to ceiling 9 16 14mm 4 12 102 mm 305 mm Deflector to ceiling 9 16 14mm Note Model FP recessed assemblies may not be used where the pressure in the space behind t...

Page 7: ...tallation sprinklers should remain in the original cartons and packaging until used This will minimize the potential for damage to sprinklers that could cause improper operation or non operation Do no...

Page 8: ...inkler technical specifications Sprinkler Finish See Table B Recessed Escutcheon F1 F2 FP Escutcheon Finish See Table B CCP or SWC Cover Plate Temperature Rating 135 F 57 C For use with 135 F 57 C and...