2-1/4"

(57 mm)

Dia.

Hole

1-15/16"
(49 mm)

Dia.

2-1/4"

(57 mm)

Dia.

Hole

1-15/16"
(49 mm)

DIA.

2-7/8"

(73 mm)

Dia.

2-7/8"

(73 mm)

Dia.

2-1/8" (54 mm) Minimum Recess

1-5/8" (42 mm) Maximum Recess

2 1/8" (54 mm) Minimum Recess

1-3/8" (35 mm) Maximum Recess

2-5/8"

(67 mm)

Dia

Hole.

2-5/16"

(58 mm)

Dia.

3-1/4"

(83 mm)

Dia.

1-1/4" (32 mm)

+/- 1/4" (6 mm)

Face of fitting
to face of wall

1-3/8" (35 mm) Minimum Recess

7/8" (22 mm) Maximum Recess

3/8" (16 mm)

+/- 1/4" (6 mm)

Face of fitting
to face of wall

1/2" (12 mm)

+/- 3/8" (10 mm)

Face of fitting
to face of wall

4" - 12"
(102 mm - 305 mm)

Deflector to ceiling

F1_REC_HSW_SWC

Reducing

Fitting

Reducing

Fitting

Reducing

Fitting

9/16" [14mm]

Model F1FR Horizontal Sidewall Sprinkler

with Model FP Recessed Escutcheon

 1/2" (13mm) Nominal Adjustment

Model F1FR Horizontal Sidewall Sprinkler

with Model F2 Recessed Escutcheon

1/2" (13mm) Nominal Adjustment

Model F1FR Horizontal Sidewall Sprinkler

with Model F1 Recessed Escutcheon

3/4" (19mm) Nominal Adjustment

4" - 12"
(102 mm - 305 mm)

Deflector to ceiling

9/16" [14mm]

4" - 12"
(102 mm - 305 mm)

Deflector to ceiling

9/16" [14mm]

Note: Model FP recessed assemblies may not be used where the pressure in the space behind

the  sprinkler  is  positive  with  respect  to  the  space  in  the  protected  area.  Ensure  that  the
openings in the Model FP cup are unobstructed following installation.

Vented Cup

1-1/4" (32 mm)
+/- 1/4" (6 mm)

Face of Fitting to

face of wall

1 9/16" (40 mm) NOMINAL PROJECTION

2-5/8"

(67 mm)

Dia

Hole.

2-5/16"

(58 mm)

Dia.

Reducing

Fitting

Vented Cup

9/16" [14mm]

4" - 12"
(102 mm - 305 mm)

Deflector to ceiling

3 5/16" [84mm]

Model F1FR Horizontal Sidewall Sprinkler

with Model SWC Concealed Cover Plate

1/2" (13mm) Nominal Adjustment

Note:  Model  SWC  concealed  assemblies  may  not  be  used  where  the  pressure  in  the  space
behind the sprinkler is positive with respect to the space in the protected area. Ensure that the
openings in the Model SWC cup are unobstructed following installation.

Recessed and Concealed Installation: Horizontal Sidewall Sprinklers

Figure 5

SWC Cover Plate

Bulletin 077

October 2022

Page 6 of 8

www.reliablesprinkler.com

Summary of Contents for F1FR56-300 Series

Page 1: ...lers are 300 psi 20 7 bar rated quick response standard spray automatic fire sprinklers utilizing a sensitive 3 0 mm glass bulb thermal element Pendent and horizontal sidewall sprinklers may be instal...

Page 2: ...response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C Guards Shields New Frames F 1 Guard F 3 Guard with Shield Guards and Shields Legacy Frames C 3 Guard with Shield D...

Page 3: ...rd F 8 Guard with Shield S 1 Shield Guards and Shields Legacy Frames 2 D 1 Guard D 5 Guard with Shield S 1 Shield Sprinkler Wrenches Model W2 non recessed Model W4 recessed or concealed Model J new fr...

Page 4: ...3 F 7 Guard Guards Shields Legacy Frames 3 D 1 Guard Sprinkler Wrenches Model W2 non recessed Model W4 recessed or concealed Model J new frame with guard installed Model JD legacy frame with guard in...

Page 5: ...Reducing Fitting Reducing Fitting Reducing Fitting Note Model FP recessed assemblies may not be used where the pressure in the space above the ceiling is positive with respect to the protected area En...

Page 6: ...djustment 4 12 102 mm 305 mm Deflector to ceiling 9 16 14mm 4 12 102 mm 305 mm Deflector to ceiling 9 16 14mm Note Model FP recessed assemblies may not be used where the pressure in the space behind t...

Page 7: ...tallation sprinklers should remain in the original cartons and packaging until used This will minimize the potential for damage to sprinklers that could cause improper operation or non operation Do no...

Page 8: ...inkler technical specifications Sprinkler Finish See Table B Recessed Escutcheon F1 F2 FP Escutcheon Finish See Table B CCP or SWC Cover Plate Temperature Rating 135 F 57 C For use with 135 F 57 C and...

Reviews: