Models F1 & F1FR Pendent Sprinkler

with Model F1 Recessed Escutcheon

3/4" (19mm) Nominal Adjustment

2-7/8" (72 mm) Dia.

1-3/4"

(44 mm)

2-1/4"

(57 mm) Dia.

Hole in Ceiling

1-15/16"

(49 mm) Dia.

Minimum

Recess

Maximum

Recess

1"

(25 mm)

Face of Fitting

to Face of Ceiling

1-1/8" (29 mm) at
Max. Recess

3/8" (10 mm) at
Min. Recess

Models F1 & F1FR Pendent Sprinkler

with Model FP Recessed Escutcheon

1/2" (13mm) Nominal Adjustment

1"

(25 mm)

2-5/16"

(59 mm) Dia.

Minimum

Recess

Maximum

Recess

1/2"

(12 mm)

3-3/16" (78 mm) Dia.

Face of Fitting

to Face of Ceiling

1-1/2" (38 mm) at
Max. Recess
1" (25 mm) at
Min. Recess

2-7/8" (72 mm) Dia.

1-3/4"

(44 mm)

Minimum

Recess

Maximum

Recess

1-1/4"

(32 mm)

Face of Fitting

to Face of Ceiling
7/8" (22 mm) at

Max. Recess
3/8" (10 mm) at
Min. Recess

2-1/4"

(57 mm) Dia.

Hole in Ceiling

1-15/16"

(49 mm) Dia.

2-1/2"

 (64 mm) Dia.

Hole in Ceiling

Models F1 & F1FR Pendent Sprinkler

with Model F2 Recessed Escutcheon

1/2" (13mm) Nominal Adjustment

Reducing
Fitting

Reducing
Fitting

Reducing
Fitting

Note: Model FP recessed assemblies may not be used where the
pressure in the space above the ceiling is positive with respect to

the protected area. Ensure that the openings in the Model FP cup
are unobstructed following installation.

Vented Cup

Model F1FR56 CCP Conical Concealed Sprinkler

1/2" (13mm) Nominal Adjustment

(Nominal Cover Plate Projection is 1" (25 mm))

1"

(25 mm)

2-5/16"

(59 mm) Dia.

Minimum

Recess

Maximum

Recess

1/2"

(12 mm)

3-5/16" (84 mm) Dia.

Face of Fitting

to Face of Ceiling

1-1/2" (38 mm) at
Max. Recess
1" (25 mm) at
Min. Recess

2-1/2"

 (64 mm) Dia.

Hole in Ceiling

F1_REC_PEND_CCP

Reducing
Fitting

Note: Model CCP concealed assemblies may not be used where

the  pressure  in  the  space  above  the  ceiling  is  positive  with

respect  to  the  protected  area.  Ensure  that  the  openings  in  the
Model CCP cup are unobstructed following installation.

Vented Cup

Recessed and Concealed Installation: Pendent Sprinklers

Figure 4

FP Recessed Escutcheon

F1 Recessed Escutcheon 

(F2 Similar)

CCP Cover Plate

Bulletin 077

October 2022

Page 5 of 8

www.reliablesprinkler.com

Summary of Contents for F1FR56-300 Series

Page 1: ...lers are 300 psi 20 7 bar rated quick response standard spray automatic fire sprinklers utilizing a sensitive 3 0 mm glass bulb thermal element Pendent and horizontal sidewall sprinklers may be instal...

Page 2: ...response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C Guards Shields New Frames F 1 Guard F 3 Guard with Shield Guards and Shields Legacy Frames C 3 Guard with Shield D...

Page 3: ...rd F 8 Guard with Shield S 1 Shield Guards and Shields Legacy Frames 2 D 1 Guard D 5 Guard with Shield S 1 Shield Sprinkler Wrenches Model W2 non recessed Model W4 recessed or concealed Model J new fr...

Page 4: ...3 F 7 Guard Guards Shields Legacy Frames 3 D 1 Guard Sprinkler Wrenches Model W2 non recessed Model W4 recessed or concealed Model J new frame with guard installed Model JD legacy frame with guard in...

Page 5: ...Reducing Fitting Reducing Fitting Reducing Fitting Note Model FP recessed assemblies may not be used where the pressure in the space above the ceiling is positive with respect to the protected area En...

Page 6: ...djustment 4 12 102 mm 305 mm Deflector to ceiling 9 16 14mm 4 12 102 mm 305 mm Deflector to ceiling 9 16 14mm Note Model FP recessed assemblies may not be used where the pressure in the space behind t...

Page 7: ...tallation sprinklers should remain in the original cartons and packaging until used This will minimize the potential for damage to sprinklers that could cause improper operation or non operation Do no...

Page 8: ...inkler technical specifications Sprinkler Finish See Table B Recessed Escutcheon F1 F2 FP Escutcheon Finish See Table B CCP or SWC Cover Plate Temperature Rating 135 F 57 C For use with 135 F 57 C and...

Reviews: